Professional Documents
Culture Documents
Figure 1 Positive and negative electric charges are sources of an electric field
A time-varying E and D will give rise to B and H, and vice versa where
the relation depends on the properties of the medium. Far enough from
the source the magnetic field, H, will be perpendicular to the electric
field, E, and both are normal to the direction of propagation, as shown
in the following figure:
Figure 2 A time-varying electric field, E, will give rise to a perpendicular magnetic field, H, and vice
versa. Far enough from the source it will become a uniform plane wave and the ratio between E and
H will be the intrinsic impedance of the medium.
Far enough from the source, the wave-front, which will become almost
spherical, can be seen as an almost plane front if the sphere is large
enough. Then we have a uniform plane wave where the ratio between
the electric field and the magnetic field, called the wave impedance:
Equation 1
Equation 2
Equation 3
Equation 4
Equation 5
[ ]
2 Maxwells Equations
James Clerk Maxwell (1837-1879) gathered all
prior knowledge in electromagnetics and
summoned the whole theory of electromagnetics
in four equations, called the Maxwells equations.
To evolve the Maxwells equations we start with
the fundamental postulates of electrostatics and
magnetostatics. These fundamental relations are
considered laws of nature from which we can
build the whole electromagnetic theory.
According to Helmholtzs theorem, a vector field
is determined to within an additive constant if both its divergence and
its curl are specified everywhere [8]. From this an electrostatic model
and a magnetostatic model are derived only by defining two
fundamental vectors, the electric field intensity E and the magnetic flux
density B, and then specifying their divergence and their curls as
postulates. Written in their differential form we have for the
electrostatic model the following two relations' [8]:
Equation 6
Equation 7
[C/m3]
Equation 8
These are based on the electric field intensity vector, E, as the only
fundamental field quantity in free space. Then to account for the effect
of polarisation in a medium the electric flux density, D, is defined by
the constitutive relation:
Equation 9
Equation 10
Equation 11
where J is the current density. To account for the material here as well,
we define another fundamental field quantity, the magnetic field
intensity, H, and we get the following constitutive relation:
Equation 12
Table 1 Fundamental Relations for Electrostatic and Magnetostatic Models (The Governing
Equations)
Equation 14
Magnetostatic Model
Equation 15
Equation 16
Maxwells Equations
Faradays law
Equation 17
Equation 18
Equation 20
Gausss law
Equation 21
Equation 22
Equation 24
Equation 25
Equation 26
where:
Equation 27
Equation 28
When both the vector magnetic potential A and the scalar electric
potential V are known, the electric field intensity E is derived by:
Equation 29
Equation 30
Equation 31
where:
Equation 32
Equation 33
Equation 34
Equation 35
Equation 36
Equation 37
Equation 38
Equation 39
Equation 40
Equation 41
Equation 42
Equation 44
Equation 45
where:
Figure 4 The significance of the different terms for the electric field strength
and
When r <<
only the first term in each equation is significant and will
in this case mean that the wave impedance will be:
Equation 46
that is much greater than the free space impedance Z0 i.e. we will have
a high E-field and a low H-field. If the current element had been a
current loop with a low circuit impedance instead of the high circuitimpedance of the current element, the first term, or the electrostatic
term, in the first two equations (Equation 43 and Equation 44) would
disappear and a similar equation would appear in Equation 45. In this
case the wave impedance would be:
Equation 47
When r >>
the last term proportional to r-1 in Equation 43 and
Equation 45 will dominate and the wave impedance will approach the
free space impedance Z0 = 377 . This is called the far-field or
radiation field. The E and the H fields will then be in phase and
orthogonal to each other producing plane waves. This is illustrated in
Figure 5 below:
Figure 5 Wave impedance at different distances from either an electric source or a magnetic source
Equation 48
4 Transmission Line
4.1 Lossy Transmission Line Model
A transmission line can be approximated by a distributed-parameter
network with the circuit parameters distributed throughout the line.
One line segment with the length z can be approximated with an
electric circuit as in the following figure:
Note that this model is actually for an unbalanced line but the model
for a balanced line is the same except for R and L which is divided
symmetrically on both conductors with R/2 and L/2 both on the upper
conductor and the lower conductor in Figure 6. This lossy transmission
line model is described by four lumped parameters, which will be
derived later in this section:
where R and G is zero under lossless conditions. We will also derive the
propagation constant and the characteristic impedance in this section.
Equation 49
Equation 50
Equation 51
Equation 52
Equation 53
Equation 54
Equation 55
Equation 56
Equation 57
Equation 58
Equation 59
Equation 60
Equation 61
Equation 62
Equation 63
Equation 64
[ ]
Note that it is independent of z.
If the distance D between the two wires is much greater than the
radius, a, of a conductor, the capacitance per unit length, C, can be
written as:
Equation 65
[F/m]
And then by comparing Equation 61 with the propagation constant for
a transverse electromagnetic wave in a medium with the constitutive
parameters , and written as:
Equation 66
-1
[m ]
and assuming that the following relationship is known:
Equation 67
we get:
Equation 68
Equation 69
[H/m]
and
Equation 70
[S/m]
To derive the series resistance R we look at the ohmic power dissipated
per unit length of both conductors. Assuming the surface current Js to
flow in a very thin surface layer and to be uniform over the
circumference of both conductors the current in each conductor is
then:
Equation 71
Since copper, and other materials used in transmission lines, are good
conductors (i.e. c >> c) and the radius a is much larger than the
skin depth the above assumptions will hold for transmission lines and
then the surface impedance can then be written as the intrinsic
impedance, c, of a good conductor:
Equation 72
[ ]
The dissipated power per unit length, p , assuming the presence of a
non-vanishing axial electric field at the surface, will then be:
[W/m2]
Equation 73
[W/m]
Equation 74
Equation 75
[ /m]
where the parameters c and c is that of the material in the
conductors. The real part of the surface impedance, Rs, is calculated
as:
Equation 76
[ ]
Having the distance, D, between the conductors and the radius, a, of
the conductors, the characteristic impedance from Equation 64 can be
simplified using Equation 65, Equation 69, Equation 70 and Equation
75 into:
Equation 77
[ ]
It can also be shown that for a balanced pair of wires near ground the
characteristic impedance will also depend on the height over ground, h,
as:
Equation 78
[ ]
The derived equations is collected in the following table:
Table 4 Basic transmission line equations
Description
Paramet
er
Equation
Unit
Resistance
R
/m
H/m
S/m
F/m
Z0
Z0
Z0
m-1
Inductance
Conductance
Capacitance
Characteristic
Impedance
Characteristic
Impedance
(simplified)
Characteristic
Impedance
(at height h above
ground)
Propagation
Constant
[A]
Equation 79
Equation 80
where z = l-z is the distance measured backward from the load. These
equations are derived from Equation 62 and Equation 63 by looking at
z=0 and z=l. These equations are solved using the fact that:
Equation 81
[ ]
and then using the hyperbolic functions to simplify. Having the voltage
and current distribution the input impedance, Zi, can be calculated,
which is the impedance that the source sees at z = 0 or z= l:
Equation 82
[ ]
Notice that when ZL equals Z0 the input impedance will be equal to the
characteristic impedance. So the voltage source only sees an
impedance Zi and the input current, Ii. The voltage, Vi, can then easily
be calculated from the source voltage, Vg, and the internal impedance
of the source Zg as:
Equation 83
Equation 84
Equation 85
Equation 86
This means that the voltage and current distribution on a matched line
are exactly the same as though the line has been extended to infinity.
The average input power delivered by the source can then be
calculated as:
Equation 87
Equation 88
Equation 89
Equation 90
Figure 7 Radiation from common-mode signals and radiation from differential-mode signals.
Figure 7 illustrates simulated radiation from a wire, carrying a commonmode current to the left and a differential-mode current to the right.
The magnitudes of the currents were the same and the differences in
field strength between the two lines are also the same in both figures.
The existing radiation from the line to the right is due to the distance
between the conductors.
If the wire is not perfectly balanced a common-mode signal will appear
due to introduced differences in amplitude and phase. The effect of this
phenomenon can be calculated with the use of the longitudinal
conversion loss (LCL). In recommendation G.117 from ITU-T a
standardised method is described for determination of LCL [4]. First EL
is applied and VT is measured according to the following figure:
Equation 91
[dB]
To see the relation between the longitudinal conversion loss (LCL), as
measured in Figure 8, the unbalance of the line and the conversion
from differential signals to common-mode signals, we will study a
model of a telecommunication line as in the following figure:
Figure 10 Equivalent circuit of the LCL measurement set-up (Figure 8) applied to the
telecommunication line in Figure 9.
Equation 92
Furthermore the currents, I1 and I2, in each conductor of the line are
given by:
Equation 93
Equation 94
Equation 95
Equation 96
Equation 97
Equation 98
Equation 99
Equation 100
, give
Equation 101
In the next step of the study this expression is more practical to use
than Equation 91. From Equation 101 it can easily be observed that
LCL is inversely dependent of the unbalance Z. In addition larger load
impedance to ground, ZL, will increase LCL and thus less current will be
converted from differential-mode to common-mode.
Figure 11 Equivalent circuit of Figure 9 showing differential mode and common mode currents
Equation 102
Equation 103
Equation 104
Equation 105
Equation 106
Equation 107
Equation 108
Equation 109
Equation 110
Equation 111
[dB V]
Equation 112
Where ZCM is the common-mode impedance and Z0 is the differentialmode impedance. This relation between the differential-mode voltage
(VD) and the common-mode voltage (VC) is the most commonly used for
calculations on balanced transmission lines.
When the common-mode voltage is known it is possible to estimate the
interference field strength (E) by the use of a conversion factor (FAV)
from common-mode voltage to an electric field determined at a
specified distance from the cable [1].
[dB V/m]
Equation 113
or if we use the relationship in Equation 112 and replace the commonmode voltage in Equation 113 we get:
[dB V/m]
Equation 114
The relation between LCL and the radiated electric field strength have
also been measured [1] (in Figure 12 below) and it have been shown
that the radiated field strength is approximately inversely proportional
to LCL.
Figure 12 Relationship between LCL of the telecommunication line and the radiated field strength
Figure 13 Three different kinds of baluns with their equivalent schematic to the right
These can be divided into two distinct categories. The first two baluns
are voltage baluns causing equal and opposite voltages to appear at
the two output terminals. The third balun is a current balun, or choke
balun, forcing equal and opposite currents to flow on the line. If the line
and the terminating load is perfectly symmetrical, the voltage baluns
will force the voltages to be equal and opposite and thus the currents
flowing from the balun output terminals will be equal and opposite and
there will be no CM-current on the line. If, however, the line is not
perfectly symmetrical unequal currents, resulting in CM-currents, will
appear leading to line radiation.
A solution, that is good in the aspect of reducing line radiation, would
be to use a current balun, which makes it possible for opposite currents
to flow and rejects CM-currents. Another solution is to use a voltage
balun in combination with a current balun. Notice that even if the
voltage is perfectly balanced at the ends of the line, some CM-currents
will still appear due to non-symmetrical line and load. When using a
current balun on a balanced line it will function as a CM-suppressor.
The wire is wrapped around a ferrite core as in Figure 13. Then the
differential currents of opposite phase will produce magnetic fluxes of
opposite phase in the core that cancel each other and there will be no
remaining reactance in the core for differential-mode signals. The
common-mode current will however produce a magnetic flux that
appears as a reactance in series with the line.
Ferrite cores are well suited as core material but the characteristic will
vary a lot with the frequency and with the ferrite material as shown in
Figure 14 above.
5 Models
Following are models derived to, in theory, determine the important
factors affecting the coupling between an aerial telecommunication
line and an antenna. We will also try to find the main contributions to
the radiated electromagnetic field in different situations. Since these
models are going to be used in the study of xDSL signals we will focus
on frequencies up to 30MHz. The models are divided into eight
different coupling paths. They are initially divided into four near-field
models and four far-field models. The near-field models, based on the
mutual impedance, will have more significant contributions to the
coupling when the distance between the emitting line and the
receiving antenna r is much less than
and the far-field models,
based on the radiated field, will dominate when the distance is much
greater than
(see Equation 43 to Equation 45). At distances
between the near-field and the far-field the contribution will be a
combination between the far-field models and the near-field models.
Both the near-field models and the far-field models are divided into
looking at the magnetic coupling or fields and the electric coupling or
fields separately. This is because of the different characteristics of the
two. All cases are finally divided into one model for the common-mode
signals and one model for the differential-mode signals. For the
common-mode signals, the signals on a two-wire line are approximated
with one signal on a single conductor. In almost all cases the
differential-mode models show much less tendency to radiate than the
common-mode model, but since the differential-mode signals usually
are of a much greater magnitude than the common-mode signals in a
balanced transmission system, the contributions from the differentialmode signals can not always be neglected.
Figure 16 Distances to a far-field without fluctuations using a long line compared to the wavelength
Figure 17 Equivalent two-port network of the coupling between the telecommunication line and an
antenna, with the antenna to the right and the coupling impedance Z12 (which is assumed to be equal
to Z21)
Equation 115
Equation 116
where Z11, Z12, Z21 and Z22 are open circuit impedance coefficients. When
the medium between the line and the antenna is bilateral, governing
reciprocity relations, the coupling impedances Z12 and Z21 are equal.
This equivalent network is used in the following theory only by the
near-field models but it will hold for the far-field also since at large
distances, r, between the line and the antenna, the coupling
impedances will become very small:
Equation 117
Then the impedances Z11 and Z22 will be nearly equal to the input
impedances of the line and the antenna ZA and ZB. That means that
with weak coupling Equation 115 could be written as:
Equation 118
Equation 119
Equation 120
Also here we can see that if we are in the far-field and have a weak
coupling, the internal impedance, Zg, for the antenna will be
approximately equal to its input impedance as:
Equation 121
We can write the produced voltage and current in the antenna due to
the current in the telecommunication line as:
Equation 122
Equation 123
when building realistic set-ups to measure the radiation and also when
looking at different reduction techniques.
Notice that the results and reduction techniques can also be applied to
cable-to-cable crosstalk problems or antenna to cable disturbances.
5.1.1 Magnetic Coupling
5.1.1.1 Common-mode Coupling
In this chapter we will study the magnetic coupling of the commonmode current to an antenna due to mutual inductance, M, shown in the
following figure:
Equation 124
Equation 125
where the left side is the induced electromotive force in the antenna,
U2. Notice that C2 does not have to be a physical closed loop. The right
side can be rewritten using Equation 124 and the result is the
Faradays law of electromagnetic induction, which states that the
electromotive force induced in a stationary closed loop circuit is equal
to the negative rate of inverse of the magnetic flux linking the circuit
[8]:
Equation 126
Equation 127
where aR is the unit vector from the source point to the field point and
R is the distance from the wire element dl to the field point. We can see
that B1 is directly proportional to the common-mode current I1 and from
Equation 124 we can see that the mutual flux 12 is also proportional
to I1. If we define that proportionality factor as the mutual inductance,
M, between the telecommunication line and the antenna we have:
Equation 128
which states that the mutual inductance is the magnetic flux linkage
with one circuit per unit current in the other. In a similar way the self
inductance is defined as the magnetic flux linkage per unit current in
the loop itself as:
Equation 129
For a linear medium, the self inductance does not depend on the
current in the loop and exists regardless of whether the loop is open or
closed. The inductances depend on the geometrical shape of the
elements constituting the current and on the permeability of the
medium.
If we consider the wire as one long conductor and a parallel dipole
antenna as another long conductor where both conductors have the
same radius, a, for simplicity reasons. These are separated by a
distance d, which is much larger than a. Both conductors are in free
space. To calculate the mutual inductance we first combine Equation
124 and Equation 128 into:
Equation 130
Equation 131
where the vector magnetic potential for a thin wire, using Equation 26,
is:
Equation 132
Equation 133
where we can see that in this situation the mutual inductance would
vary inversely with the distance R between the antenna and the
telecommunication line. We can also see that for a linear medium, it is
proportional to the permeability and independent of the currents in the
circuits. The contour integrals over C1 and C2 is however hard to
calculate since the contour of a dipole antenna is non-obvious.
Interchanging the subscripts would not change the value of the double
integral which means that the reciprocity relations hold as discussed
earlier, Z12 = Z21. Equation 133 is called the Neumann formula for
mutual inductance.
The mutual inductance M as calculated in Equation 128 or Equation
133 would represent the value of a coupling inductor Z12 in Figure 17.
The self-inductances, as calculated in Equation 129, would be part of
the impedances Z11 and Z22 in the same figure. If Z12 is purely inductive
then -Z12 in the upper impedances in Figure 17 would represent pure
capacitances and the schematic in Figure 17 could be illustrated as in
the following figure:
From Figure 19 we can clearly see the origin of the term mutual
inductance, since both the current I1 and I2 are going through the same
inductance M. From Equation 122 we get the induced current in the
antenna as:
Equation 134
Figure 20 Equivalent circuit of the magnetic coupling between a telecommunication line above and
an antenna below, showing the mutual inductance M and the self inductances L1 and L2.
Equation 135
Equation 136
Equation 137
The most obvious reduction techniques like reducing the loop area (i.e.
reducing the height and the length of the telecommunication line) or
increasing the distance, R, between the interfering and the interfered
object is however hard to do in practice.
Reducing the common-mode current in the line will of cause have a
direct effect on induced voltage in the antenna, as seen in Equation
137. Increasing the balance of the cable would reduce the commonmode current (see Equation 91). Increasing the common-mode
impedance and the use of different common-mode rejection
techniques could also be utilised to reduce the common-mode current.
The common-mode current is also reduced by reducing the differentialmode current since that is the source of the common-mode current.
Operating at lower frequencies, if possible, would decrease the
reactance of M.
With differential-mode currents on the line, the two wires will cause
almost equal and opposite magnetic fluxes that will tend to cancel
each other. We denote the mutual inductance from one wire to the
antenna M13 and the mutual inductance from the other wire to the
antenna M23, as in the following figure:
Figure 21 The magnetic (mutual inductance) coupling between a two wire telecommunication line
carrying differential-mode currents above and an antenna below.
Equation 138
Equation 139
Equation 140
where we can see that if the mutual inductances are equal, there
would not be an induced emf in the antenna. Due to slight differences
in the distances between the antenna and the two lines and
differences in the self inductances in the lines there will however be
some coupling.
5.1.1.4 Reduction of Differential-mode Magnetic Coupling
Equation 141
where the unit is coulomb per volt or farad, F. Recall that for a parallel
plate capacitor of area S the capacitance C is expressed as:
Equation 142
where d and are the distance between the plates and the permittivity
of the dielectric that space.
Consider an infinitely long line charge with a charge density
will cause a cylindrical electric field with intensity E at the
perpendicular distance r from the line charge.
[C/m]. It
Equation 143
Figure 23 Cross section of a line charge, in P, and its image in a parallel conductor
Figure 24 Cross section of a telecommunication cable in parallel with the conductor of a dipole
antenna and equivalent line charges
Equation 144
Equation 145
If l is the length for which the transmission line and the dipole antenna
are parallel, the mutual capacitance can simply be expressed as (using
Equation 141):
Equation 146
That the left side is the same as the right side in Figure 25 is realised
when calculating the voltage out on the right, V2, from applying a
voltage, V1, to the left (voltage dividing), first on the left circuit (in
Figure 25):
Equation 147
Equation 148
The equivalent circuit will then be the same as in Figure 19 with the
capacitance C as the value of M. The resistance 1/R will be neglectible
compared to Z11 in Figure 19 since R is very large. Then we get the
following relation of the current in the antenna due to the commonmode current in the telecommunication line (as in Equation 134):
Equation 149
Equation 134 and thus these two contributions will be additive and not
cancel each other.
5.1.2.2 Reduction of Common-mode Electric Coupling
Since we can not control the antennas ground impedance, the only
factors we can change are either the common-mode voltage or the
capacitance between the line and the antenna. The capacitance is hard
to reduce since we can not separate the line and the antenna or
reduce the radius of the wires. A possibility is ofcourse to operate at
lower frequencies to increase the reactance caused by C. Reducing the
common-mode voltage is done by increasing the balance of the cable
(see Equation 91), increasing the common-mode impedance and the
use of different common-mode rejection techniques (these methods
also increases LCL as seen in Equation 101). The common-mode
voltage is also reduced by reducing the differential-mode voltage since
that is the source of the common-mode voltages.
5.1.2.3 Differential-mode Coupling
With differential-mode voltages on the line, the two wires will cause
almost equal and opposite currents in the antenna which will tend to
cancel each other. We denote the mutual capacitance from one wire to
the antenna C13 and the mutual capacitance from the other wire to the
antenna C23, as in the following figure
Figure 26 The electric (capacitive) coupling between a two wire telecommunication line carrying
differential-mode signals above and an antenna below.
Equation 150
where I1 is the current in one conductor in the line and I2 is the current
in the other conductor. But since these are differential currents only, I2
will have the same magnitude as I1 but opposite direction:
Equation 151
Equation 152
Figure 27 The main radiation direction and polarisations for a rectangular loop
In this chapter we will study the magnetic radiation due to commonmode current flowing as shown in the following figure:
Figure 28 The common-mode current loop causing magnetic fields, with aerial telecommunication
lines. The common-mode signals on the two wire line are approximated with one signal on a single
conductor.
[Am2]
Equation 153
Equation 154
Equation 155
Then the electric and magnetic field intensities, E and H, can be solved
by deriving the magnetic flux from the vector magnetic potential, A,
for the magnetic field and then the electric field can be calculated from
the curl of the magnetic field intensity as:
Equation 156
Equation 157
From this we get the electric and magnetic field intensities as:
Equation 158
Equation 159
Equation 160
Notice the similarity with the equations for the electric dipole, derived
in Equation 43, Equation 44 and Equation 45, and that the nature of
the near and far-field discussed earlier also applies to these equations.
For the far-field (R >> /2 ) these equations will simplify to:
Equation 161
[V/m]
Equation 162
[A/m]
where =2 c/ . We can see that the far-field intensities vary
inversely as R and their ratio E /H equals the intrinsic impedance of
free space, 0. We can also see that the maximum fields are produced
in the same plane as the current loop, where is /2.
The vector magnetic moment, m, is the current, I, times the area of the
loop which we denote S. That means that the electric (and the
magnetic) field intensity vary linearly with the current in the loop and
the area of the loop. If we look at the electric field intensity in a point in
the same plane as the loop, in the x-y plane, where we have the
maximum field intensity, we could write the electric field intensity as a
constant depending only on the frequency and the distance R times the
current and the area of the loop (in free space):
Equation 163
Equation 164
The current loop can be either a small loop or a large loop which will
affect the input impedance of the loop and therefor the current flowing
in the loop. We have earlier derived the input impedance for a
transmission line (Equation 82) repeated here:
Equation 165
Equation 166
From Equation 166 we can see that for small loops with l << (often
written as l < /10) we will have the input impedance, Zi, almost equal
to the load impedance, ZL. If we have the line as illustrated in Figure 30
we will have a current in the circuit as:
Equation 167
Equation 168
and we will have a purely reactive input impedance with poles and
zeros at different frequencies depending on the relation between the
line length, load impedance and the characteristic impedance of the
line.
If we look at the common-mode current loop as illustrated in Figure 28
we know that the electric and magnetic field intensity in the far-field is
proportional to the loop area which is the medium height over ground
times the length of the line and to the common-mode current flowing
in the loop. Notice that in the aerial telecommunication line case, the
loop will often become a large loop.
5.2.1.2 Reduction of Common-mode Magnetic Radiation
The most obvious way would be to reduce the loop area by reducing
the height over ground or reducing the length of the cable, but since
this would be to expensive, the reduction techniques are focusing on
The theory presented above for common-mode signals will hold in this
case too except for the fact that the loop area will be much less than in
the case of common-mode current in aerial cables. The loop area for
the differential mode signal will be the area between the conductors of
the cable, as illustrated in the following figure:
Note that this area will be even less in a real cable since the cables are
twisted, intentionally or unintentionally. The different parts of a twisted
cable will not radiate in the same direction and will in some cases tend
to cancel each other. Also what was said about the input impedance,
see Figure 30, depending on the length of the cable can be applied to
this situation, see Equation 166 and about the maxima and minima in
Equation 168.
5.2.1.4 Reduction of Differential-mode Magnetic Coupling
Also here the radiation will be proportional to the current in the loop,
see Equation 163, which means that a reduction of the differentialmode current would have a direct effect on the amount of radiated
fields, by the same amount. It is also direct proportional to the loop
area, Equation 163, and inversely proportional to the distance, R, to the
point of observation (Equation 161 and Equation 162).
The most common reduction technique is the use of twisted pairs. The
reduction of the differential mode coupling that is offered by twisted
pair can be written as [8]:
Equation 169
[dB]
where n is the number of twists per meter, l is the length of the wire in
meters and is the wavelength in meters. The reduction of differentialmode coupling offered by twisted pair is plotted in the following figure:
The x-axis is the total number of twists along the whole wire and each
curve corresponds to the product of the number of twists per meter, n,
and the wavelength, .
5.2.2 Electric Fields
5.2.2.1 Common-mode Radiation
Equation 170
[A/m]
Equation 171
[V/m]
By examining the relationships in these equations we see that the
magnitude of the fields in the far field is proportional to the current
through the element I, the length of the element dl and inversely
dependent of the distance R and that the ratio between E and H
equals the intrinsic impedance of free space, 0. Another important
observation is that the magnitude of the field is maximised
perpendicular to the conducting element where = /2, and minimised
along the axis of the conducting element where =0, see Figure 3.
Consider a typical aerial telecommunication line with horizontally and
vertically oriented segments according to Figure 33. According to the
theory above, the common mode current will produce an
electromagnetic field. The current distribution will also give rise to a
charge distribution that also will produce an electromagnetic field. The
value of the common-mode impedance will decide whether the
Figure 33 The model for the electric fields generated by common-mode signals on the line. The
common-mode signals on the two wire line are approximated with one signal on a single conductor.
Figure 34 Simulated electric fields from a telecommunication line above ground using the method of
images
Equation 172
At points where the distance to the line and its image differs by an
uneven fractions of a wavelength, radiation will occur.
Figure 35 Radiation pattern of a travelling wave antenna ( is the elevation angle above earth)
Again, this is not the case at ground level in the far field.
If the common-mode impedance instead is relatively large then the
resulting radiation is mainly due to the charge distribution. In this case
the radiation caused by the potential of the horizontal oriented
segment of the line and its image will form a electrical dipole radiating
a vertical polarised electric field.
Figure 36 A telecommunication line over ground containing a charge distribution, and its
corresponding image.
Equation 173
where
Equation 174
Equation 175
To be able to derive the electric field intensity in the far field we need
to integrate Equation 173 to get:
Equation 176
Equation 177
Equation 178
Equation 179
Equation 180
Equation 181
Equation 182
Equation 183
Equation 184
where FSPL is the Free Space Propagation Loss, R is the distance to the
point of observation and f is the frequency in MHz.
Figure 39 The model for the electric fields generated by differential-mode signals on the line.
The theory for common-mode radiation above applies to this case too,
if we consider having the opposite charges located in the two wires
instead of in the line and its image. This will cause the distance
between the opposite charges to be much smaller in this case for an
aerial communication line. The capacitance between the two wires
(Equation 65) is larger than the capacitance between the line and
earth. As in the case of differential-mode magnetic radiation in the far
field the magnitude of the radiation is also dependent on how the
telecommunication line is twisted. As in illustrated in Figure 7 the
electrical fields generated from the two conductors will tend to cansel
each other.
5.2.2.4 Reduction of Differential-mode Electric Radiation
Quantity
Symbol
Length
Unit
Abbreviation
meter
m
l
Mass
kilogram
kg
m
Time
second
s
t
Current
ampere
A
I, i
Table 7 Derived Quantities
Quantity
Symbol
Unit
Abbreviatio
n
Admittance
siemens
S
Y
Angular frequency
Attenuation constant
Capacitance
radian/second
rad/s
neper/meter
Np/m
farad
F
C
Charge
coulomb
C
Q, q
Charge density
(linear)
Charge density
(surface)
Charge density
(volume)
l
s
Conductance
coulomb/meter
C/m
coulomb/meter2
coulomb/meter3
Current density
(surface)
Current density
(volume)
Dielectric constant
C/m3
siemens
S
G
Conductivity
C/m2
siemens/meter
S/m
siemens/meter
A/m
Js
siemens/meter2
J
A/m2
r
coulomb/meter2
C/m2
volt/meter
V/m
E
Electric potential
volt
V
V
Electromotive force
volt
V
Energy
joule
J
W
joule/meter3
Energy density
w
Frequency
hertz
Hz
f
Impedance
Z,
Inductance
ohm
henry
H
L
ampere-meter2
Magnetic dipole
moment
Magnetic field
intensity
A/m
weber
Wb
tesla
T
B
Magnetic potential
weber/meter
Wb/m
Permittivity
Phase
Phase constant
0
0
Power
henry/meter
H/m
farad/meter
F/m
radian
rad
radian/meter
rad/m
watt
W
P
Propagation constant
A.m2
ampere/meter
Magnetic flux
Permeability
J/m3
Reactance
meter-1
m-1
ohm
X
Relative permeability
Relative permittivity
r
r
Resistance
ohm
R
Voltage
volt
V
V
Wavelength
Wavenumber
meter
m
radian/meter
rad/m
k
Work
joule
J
Appendix B - Constants
Table 8 Constants of Free Space
Constant
Symbol
Velocity of light
c
Permittivity
Permeability
Intrinsic impedance
Value
3.108 [m/s]
[H/m]
0
0
120 or 377 [ ]
Constant
Symbol
[F/m]
Value
9.107.10-31 [kg]
-1.602.10-19 [C]
Charge of electron
-e
-1.759.1011 [C/kg]
2.81.10-15 [m]
Radius of electron
Re
1.673.10-27 [kg]
Material
Value
Material
Value
Air
1.0
Plexiglas
3.4
Backelite
5.0
Polyethylene
2.3
Glass
4-10
Polystyrene
2.6
Mica
6.0
Porcelain
5.7
Oil
2.3
Rubber
Paper
2-4
Soil
3-4
Paraffin wax
2.2
Teflon
2.1
2.3-4.0
Material
Value
Material
Ferromagnetic
:
Value
Diamagnetic:
Nickel
Bismuth
250
Cobalt
0.99983
Gold
600
Iron
0.99996
Silver
4000
0.99998
Mumetal
Copper
100000
0.99999
Paramagnetic:
Aluminium
1.000021
Magnesium
1.000012
Palladium
1.00082
Titanium
1.00018
Table 12 Conductivities (average low-frequency values at room temperature)
Material
Value [S/m]
Material
Value [S/m]
Silver
6.17.107
Distilled water
2.10-4
Copper
5.80.107
Dry soil
10-5
Gold
4.10.107
Transformer oil
10-11
Aluminium
3.54.107
Glass
10-12
Brass
1.57.107
Porcelain
2.10-13
Bronze
107
Rubber
10-15
Iron
107
Fused quartz
10-17
Surface Type
Salt water
81
5.0
80
0.001
Excellent
Ground
Fresh water
Pastoral, low hills, rich soil type
Very good
20
0.03
13
0.007
13
0.006
Average
13
0.005
12
0.002
10
0.002
Poor
Very poor
5
0.001
0.001