You are on page 1of 3

TECHNICAL SCHEDULE - 8

SCHEDULE OF TECHNICAL PARTICULARS OF GENERATOR TRANSFORMER& STATION AUXILIARY TRANSFORMER & OLTC FOR GENERATOR TRANSFORMER
TRANSFORMERS
Description

Generator Transformer
Offered Particulars

Unit Auxiliary Transformer


Offered Particulars

1. Name of manufacturer & Type

CGL,ABB,GEPROLEC,ALSTOM,EMCO

Schnieder,CGL,T&R

2. Full load rating:HV

25/30MVA

500KVA

3. Rated no load voltage:HV

220KV/11KV

11KV/415V

4. Rated current(HV/LV)

78.73/1574.59
ONAN/ONAF

ONAN

6. Rated % impedance

12.5% (@30MVA Base)

4.00%

7. Rated frequency :

50Hz

50Hz

8. Winding connections:HV/LV

Star/Delta

Delta/Star

9. Vector group:LV

YNd11(*)

Dyn11(*)

10. Tapings on windings

HV

HV

11. Winding insulation & category as per IS:2026(HV/LV)

Uniform/Uniform

12. Impulse withstand voltage(HV/LV)

1050/75

13. Power frequency withstand voltage(HV/LV/HVN)

460/28/28 kV rms

28/3 KV rms

14. Guaranteed maximum temp. rise


a. Winding:
b. Oil

55 C
50 C

55 C
50 C

a. No load :

20 KW

1.1KW

b. Load loss at 75 degrees C :

80 KW

6.5KW

16. Flux density at rated voltage

1.6T

< 1.72 T

17. Current density :HV

< 3A/sqmm

< 3A/sqmm

18. Dial size of meters :LV

150mm

150mm

19. Weights

DETAILS SHALL BE PROVIDED LATER

DURING DETAILED ENGINEERING

a. Core & Winding :Kg


b. Oil:Kg
c. Tank & Fittings :Kg
d. Total
20. Overall dimensions

DETAILS SHALL BE PROVIDED LATER


DETAILS SHALL BE PROVIDED LATER
DETAILS SHALL BE PROVIDED LATER
DETAILS SHALL BE PROVIDED LATER
DETAILS SHALL BE PROVIDED LATER

DURING DETAILED ENGINEERING


DURING DETAILED ENGINEERING
DURING DETAILED ENGINEERING
DURING DETAILED ENGINEERING
DURING DETAILED ENGINEERING

21. Winding material:

Electrolytic Copper

Electrolytic Copper

22. i. Buchholz relay

PROVIDED

PROVIDED

ii.Oil temperature:

PROVIDED

PROVIDED

iii. Winding temperature

PROVIDED

PROVIDED

iv. Minimum oil gauge provided

PROVIDED

PROVIDED

5. Type of cooling :

@25MVA base

Uniform/Uniform
If insulation is uniform
the value should be
same as HV i.e. 460KVrms.
If the insulation is
75/non-uniform, the value should be 70KVrms.

15. Losses

All accessories shall be as per specification Cl No - 8.32 (Power Transformer) & 8.33(Aux Transformer) of Sub Section -8
23. Tapings for HV/LV variation
a. Range :
b. number of steps :

-15 % TO 15%
@1.875%

5%
@2.5%

c. value of the step:

16

99.67
99.71
99.73

98.5
98.75
98.92

a. At unity power factor

1.05

1.39

b. 0.80 power factor lagging :

8.2

3.66

26. Number of radiators / coolers

As per manufacture's Standard

As per manufacture's Standard

27. Rating of each radiator / cooler in percentage of load:

1X100%

1X100%

a. Separate source power frequency withstand Voltage H.V

460KV

70

b. Induce over voltage withstand voltage At H.V

460KV(As per IS/IEC)

95(As per IS/IEC)

c. Full wave lightning impulse withstand Voltage HV

1050

170

d. Switching Impulse withstand voltage LV/HV:

850KVp/As per IS/IEC-60071-1

NA

24. Efficiencies at 75 degrees C and unit of power factor:


a. At full load
b. At 3/4 full load :
c. At 1/2 full load :
25. Regulation at full load at 75 degrees C

28. Insulation level:

e. System Nuetral Earthing


f. Creepage Distance

Solidly Grounded
25mm/KV

25mm/KV

a. H.V.
b. L.V.

Bare Bushing
Cable Box

Cable Box
Cable Box

c. Neutral

Bare Bushing

Bare Bushing

30. Reference standard

IS: 2026

IS: 2026

1. Make

EASUN MR/BHEL

2. Type

On Load

OCTC

29. Termination arrangement

(II) ON LOAD TAP CHANGE OVER

3. Rating
11KV
During Detailed Engineering
-

a. Rated Voltage
b. Rated current
c. Step voltage
d. Number of steps

123KV

4. Control

Auto/Manual

6. Voltage for control

110V

7. Local switch

YES

1.875%
16

5. Auxiliary supply details

8. Indications provided

YES

9. Protections employed
i. Buchholz relay
ii.Oil temperature
iii. Pressure Relief Device

YES
YES
YES

10. Details of electric drive


i. KW
ii.Voltage

DURING DETAILED ENGINEERING


DURING DETAILED ENGINEERING

DURING DETAILED ENGINEERING


DURING DETAILED ENGINEERING

11. Annunciations provided

YES

YES

12. Approximate overall weight

DETAILS SHALL BE PROVIDED LATER

DURING DETAILED ENGINEERING

13. Approximate overall dimensions

DETAILS SHALL BE PROVIDED LATER

DURING DETAILED ENGINEERING

14. Approximate quantity of oil

DETAILS SHALL BE PROVIDED LATER

DURING DETAILED ENGINEERING