Technical
o
Meets stringent sag / clearance requirements that could not be met by other
solutions (river crossings cruise lines)
Value Proposition :
Special permitting
Detail
The following are steps adopted to initiate a project with utilities. Input information accuracy (questionnaire)
is the most critical step because all designs are based on it and if done correctly will save time and money.
It is often updated, corrected because many times it is furnished by non transmission engineers. The
whole approach is a team effort among utilities, manufacturers, designers, and application engineers.
2 Increase Ampacity by replacing existing conductor with same size high performance one.
Increase Ampacity & lower sag using smaller conductor of lower cost (comparable corrosion resistance)
PLS-CADD Verify Sag Tension Line Clearance For Violation (Ampacity doubled using high
performance type of conductor); Blue is ACCR Ostrich (300 kcmil), Red is Wolf ACSR (336.4 kcmil)- Same
tension- lower sag- Line profile shown here is a portion of the actual line analyzed (line is > 100 Km)
Method
Inhouse
NESC
240C
Sag 10
NESC
240C
Plscadd
NESC
240C
Maximum Ampacity,
amps
2020 (0.5. 0.5)
35.06
45.15
10028
3318
35.18
45.34
Conclusions
Congested and thermally limited transmission lines performance can be upgraded using higher capacity
conductors. This project shows the approach used to design these conductors and predict their
performance.
Sag 10 is another analytical tool used to predict conductor performance (sag, tension and ampacity). Data
from this software are not included here so as to reduce file size but could be provided if need.
Line design applications involve practically acceptable analysis approaches and are not perfect tool.
Therefore after installation line monitoring is needed to verify design predictions and find out how close
such designs are to real life situation. It is always beneficial to compare results from more than one line
design software. The following table summarizes predicted performance of conductors using three
methods (software); very good agreement is seen among these methods. NESC refers to National
Electrical Safety Code condition.
PLSCADD Use
The advantage of using Plscadd is that it predicts the conductor performance for the whole transmission
line that is under consideration for upgrading. It shows regions which could potentially violate clearance
above ground and may reveal other potential problems affecting performance and safety.
To see the resume of the expert associated with this case study, see the link below.