You are on page 1of 5

BTS / Power TSP/BOOL ALARM Start

DATE REGION SITE ID SITE NAME / TX TSP/BOOL DETAILS TIME


25-Feb-10 CBE CBE156 Omshakthi Nagar Power C O&M GTL 15:45
25-Feb-10 CPT VDC008 Karukudal Road Power BOOL TV 8:51
25-Feb-10 CPT VDC003 Virdhachalam Power Colocation Airtel 8:51
25-Feb-10 CPT PGPU01 Pungampattunadu Power USO USO 9:26
25-Feb-10 CPT NYL002 Indranagar Power C O&M GTL 11:00
25-Feb-10 CPT OMR001 Omandur Power C O&M GTL 11:00
25-Feb-10 CPT DVA001 Deevanur Power C O&M GTL 11:27
25-Feb-10 CPT NYL009 Keelakollai Power C O&M GTL 11:43
25-Feb-10 CPT MADP01 Madampattu Power C O&M GTL 13:52
25-Feb-10 CPT DVA001 Deevanur Power C O&M GTL 14:30
25-Feb-10 CPT KGE001 Kangiradadu Power C O&M Icomm 14:27
25-Feb-10 CPT TDM002 Jeyapuram Power C O&M GTL 15:30
25-Feb-10 CPT TDM004 Rosen pettai Power C O&M GTL 15:30
25-Feb-10 CPT TPAR01 Thenpasiyar Power Colocation TTSL 15:30
25-Feb-10 CPT KATI01 Kattalai Power USO USO 15:30
25-Feb-10 CPT SVT001 Siruvanthadu Power C O&M GTL 15:50
25-Feb-10 MDU MDU063 Arasaradi Power C O&M Aster 6:15
25-Feb-10 MDU KKN006 Observatory Power Colocation Railtel 10:10
25-Feb-10 MDU PIKI01 Pallikottai Power C O&M Aster 10:33
25-Feb-10 MDU VKV001 Valliyoor ( BTS) Power C O&M Aster 11:00
25-Feb-10 MDU MDU015 Classic Residency Power C O&M Aster 12:47
25-Feb-10 SLM PMP001 Periyampatti Power C O&M Icomm 10:00
25-Feb-10 SLM KUU001 Kugalur Power BOOL GIL 11:00
25-Feb-10 SLM SLM006 Kondalampatty Power C O&M Icomm 12:00
25-Feb-10 SLM KBKI01 Kannumuthal (kombuthooki Power USO USO 13:20
25-Feb-10 SLM DVP002 Divattipatti Power C O&M Icomm 14:05
25-Feb-10 SLM SLM117 Chinna Seeragapatty Power C O&M Icomm 14:45
25-Feb-10 SLM SLM010 Junction Power C O&M Icomm 15:30
25-Feb-10 TRY KKD014 Koppudaiyamman Koil Power BOOL GIL 7:00
25-Feb-10 TRY KKD018 Devakottai Raod Power C O&M Aster 7:00
25-Feb-10 TRY TVRI01 Thiyagavancheri Power USO USO 8:00
25-Feb-10 TRY PTHP01 Pothapatty Power BOOL TVS (ITIL) 8:00
25-Feb-10 TRY PRPV01 Pirapanavalasai Power C O&M Aster 10:00
25-Feb-10 TRY NGA001 Nangamangalam Power BOOL GIL 10:00
25-Feb-10 TRY PRPV01 Pirapanavalasai Power C O&M Aster 14:45
25-Feb-10 TRY NRK001 Narikudi Power Colocation TTSL 17:30
25-Feb-10 TRY IRJI01 Irunjirai Power USO USO 17:30
25-Feb-10 TRY ARMP01 Arimadam Power C O&M Aster 17:30
25-Feb-10 TRY TPKI01 T.Pudukkottai Power C O&M Aster 17:30
25-Feb-10 TRY VEC001 Veerachozan Power C O&M Aster 17:30
25-Feb-10 TRY PTB001 Parthibanur Power C O&M Aster 17:30
Alarm Ceasing DURATION Regular/PM/P Available
TIME (Min) roject TCH
17:31 106 Regular 87
10:26 95 Regular 126
10:06 75 Regular 126
10:02 36 Regular 84
14:58 238 Regular 84
13:23 143 Regular 26
12:22 55 Regular 84
13:02 79 Regular 84
15:56 124 Regular 64
17:21 171 Regular 84
15:25 58 Regular 39
16:06 36 Regular 177
16:06 36 Regular 69
16:06 36 Regular 87
16:06 36 Regular 69
16:45 55 Regular 46
8:09 114 Regular 156
13:45 215 Regular 54
12:00 87 Regular 84
13:54 174 Regular 180
14:10 83 Regular 196
11:00 60 Regular 84
12:21 81 Regular 84
17:33 333 Regular 177
15:35 135 Regular 39
17:31 206 Regular 83
23:50 545 Regular 129
17:41 131 Regular 129
7:56 56 Regular 84
7:56 56 Regular 39
9:20 80 Regular 39
11:40 220 Regular 87
10:27 27 Regular 87
12:00 120 Regular 70
16:45 120 Regular 87
20:10 160 Regular 87
20:10 160 Regular 39
20:10 160 Regular 39
20:10 160 Regular 84
20:10 160 Regular 46
20:10 160 Regular 84
REASON FOR OUTAGE
Due to non availability of power and DG fault/Came up after rectification of DG fault
Due to non availability of EB power supply/came up after restoration of EB power supply
Due to non availability of EB power supply/came up after restoration of EB power supply
Due to non availability of power supply and DG automation problem/came up after power restored
Due to non availability of power supply /Came up after power restored(Non-DG)
Due to non availability of power supply and DG automation problem/came up after DG switched ON manually
Due to non availability of power supply and DG automation problem/came up after power restored
Due to non availability of power supply and DG automation problem/came up after DG switched ON manually
DG automation problem(non-EB)/came up after DG switched ON manually
Due to non availability of power supply and DG automation problem/came up after DG switched ON manually
Due to non availability of power supply and DG automation problem/came up after DG switched ON manually
Due to non availability of power supply and DG automation problem at TDM002 site/came up after DG switched ON manually at TDM002
Due to non availability of power supply and DG automation problem at TDM002 site/came up after DG switched ON manually at TDM002
Due to non availability of power supply and DG automation problem at TDM002 site/came up after DG switched ON manually at TDM002
Due to non availability of power supply and DG automation problem at TDM002 site/came up after DG switched ON manually at TDM002
Due to Battery mode(non-DG) / came up after restoration of EB supply
Due to non Availability of EB & DG Running problem/Came up after restoration of power supply.
Due to non Availability of EB (Non DG)/Came up after restoration of power supply.
Due to non Availability of EB & DG Engine fault/Came up after restoration of power supply.
Due to non Availability of EB & DG Alternator/Came up after restoration of power supply.
Due to non Availability of EB (Non DG)/Came up after restoration of power supply.
Due to DG problem/Came up after solving DG problem
Due to voltage fluctuation problem/Came up after voltage fluctuation problem solved
Due to DG fault and non availability of EB/Came up after restoration of EB power supply
Due to non availability of EB and non DG site/Came up after restoration of EB power supply
Due to DG fault and non availability of EB/Came up after restoration of EB power supply
Due to non availability of EB and DG fault/Came up after rectification of DG starting problem
Due to DG fault and non availability of EB/Came up after restoration of EB power supply
Due to prolonged battery mode and DG fail to start at KKD014/Came up after DG made ON manually at KKD014
Due to prolonged battery mode and DG fail to start at KKD014/Came up after DG made ON manually at KKD014
Due to Eb problem at USO end /After rectification of EB problem at USO end
Due to prolonged battery mode and DG fail to start /Came up after DG made ON manually
Due to MCB tripped at the site/Came up after Switching On the MCB at the site.
Due to prolonged battery mode and DG fail to start /Came up after DG made ON manually
Due to power plant rectifier unit faulty at site/came up after replaced the power plant rectifier unit at site
Due to battery mode and DG fault at PTB001 site/ Came up after connecting with hired mobile DG at PTB001 site.
Due to battery mode and DG fault at PTB001 site/ Came up after connecting with hired mobile DG at PTB001 site.
Due to battery mode and DG fault at PTB001 site/ Came up after connecting with hired mobile DG at PTB001 site.
Due to battery mode and DG fault at PTB001 site/ Came up after connecting with hired mobile DG at PTB001 site.
Due to battery mode and DG fault at PTB001 site/ Came up after connecting with hired mobile DG at PTB001 site.
Due to battery mode and DG fault at PTB001 site/ Came up after connecting with hired mobile DG at PTB001 site.
switched ON manually at TDM002 site
switched ON manually at TDM002 site
switched ON manually at TDM002 site
switched ON manually at TDM002 site
Sum of DURATION (Min)
TSP/BOOL DETAILS Total
Airtel 75
Aster 1301
GIL 257
GTL 1043
Icomm 1333
Railtel 215
TTSL 196
TV 95
TVS (ITIL) 220
USO 447
Grand Total 5182