Chandrashekar
Technical Manager (India & SW Asia)
9/10/2014
Scopenow
includes
groundingof
ITE
TIA-607-B, Generic
Telecommunications
Bonding and
Grounding (Earthing)
for Customer
Premises, is now
approved!
ScopeofTIA607B
What is TIA-607-B?
Scope:Specifiesrequirementsfora
generictelecommunicationsbonding
andgroundinginfrastructure,andits
interconnectiontoothersystems,for
locationswheretelecommunications
equipmentwillbeorareinstalled
MajorrevisionofJSTD607A:
IncludesG&Boftelecommunications
spaces(distributorsandcomputer
rooms)
Continuedharmonizationefforts(as
practicable)onterminologyand
practiceswithinternationalstandards
Distributors
Computer
Rooms
TGB
TMGB
TBB
Ratherthanrelying
ontheacpowercord
groundwire,itis
desirablethat
equipmentbe
groundedinaverifiable
mannerasdescribedin
thisStandard.
Figure7Exampleofthreemethodstobond
equipmentandrackstoground
PurposeofTBBistoreduce
potentialdifferencesbetween
interconnected
telecommunicationssystemson
differentfloors
OriginatesatTMGBandextends
throughoutbuildingusing
telecompathways
ConnectsTGBsthatexistineach
distributor
Size matters!
#6AWGroundwireor2
widecopperstripsbonded
atintersections
Minimumgriddensityis3
m(10ft)centers
Minimum1/0bondto
TGB/TMGB
Examplesupplementalbondinggrid
Conduits
Cabling
pathways
(notshown)
Information
technology
equipment(ITE)
Racksand
cabinets
Supplemental
bondinggrid
(SBG)
Rackbonding
conductor
(RBC)
12
Two-hole
compression
lugs required
on TGB &
TMGB
(Type LCC-W)
13
14
ANSI/NECA/BICSI-607-2011 busbars
Panduit
recommendation
on busbar hole
patterns: pick a
pattern and stick
with it. Its
confusing to have
multiple hole
patterns later.
Recommend using
the BICSI/TIA hole
pattern, as it is well
defined and known
in industry.
OR
17
Panduitresearchoverthelasttwoyearshasfoundthepresenceofphaseimbalanceon
thetelecommunicationsgroundingsysteminthesteadystate
Frequenciesarepowerlineandthefirstcoupleofharmonics
Observations:
High building
steel currents
UPSs are at end
of line-up creating
power imbalance
in the ground
conductor
No noticed
network
degradation on the
part of network
operators
Episodic/transient research
CRAC
Panel
Rackbondingconductor
AHSystemsBCP512Probe
(highbandwidth)
TektronixTPS2024
7MHztransientmeasuredonACEGatCRAH,butnotdetectableatclosestrack
Conclusionsofar:meshbondingandseparatecircuitsfromtheACpanelareeffective
meansofmitigatingissueswithtransients
Flatbraidshavenotbeenshowntoofferatangiblebenefitforthisapplication
19
20
OptimumperformanceofsurgeprotectorsisachievedatfiveOhmsorbelow.Several
manufacturersofelectronicequipmentalsorequirefivetotenOhms asamaximum
resistancefortheirgeartoworkcorrectly.
DitekTechnicalWhitePaper:Grounding101
21
Publicsafetyfacilities
Militaryinstallations
Datacenters
Webhostingfacilities
Centraloffices
Wheretelecommunicationsequipmentisdistributedthroughoutastructureand
maybeinterconnectedbymetalliclinks,theminimallyrequiredgroundingsystem
maynotbeadequate.Facilitieswithadvancedrequirementsordistributed
equipmentwillbenefitfromtheadditionofabuildingperimetergroundloop.
22
Requiremeasurementsofthegroundsystemresistanceasverificationofthedesign
3polefallofpotentialmethod(ifroomisavailable,andthegroundisnotconnectedtothe
powersystem)
Clamponmeter
23
Summary