You are on page 1of 36

Preface

Data in the PROFIBUS-DP


messages

SIPROTEC4

Message in output direction:


PROFIBUS-DP master to the
7SJ62/63

Multifunction protection with


control
7SJ62 / 7SJ63

Message in input direction:


7SJ62/63 to the PROFIBUS-DP
master
Glossary

Communication module
PROFIBUS-DP
Bus mapping

Revision: 1.2
Edition: April 2000
C53000-L1840-B003-01

Index

Cover

1
2
3

Non-liability clause

Copyright

Although we have checked the contents of this publication for


conformance with the hardware and software described we
cannot guarantee complete conformance since differences
cannot be ruled out.

Copyright Siemens AG 2000. All rights reserved.

The information in this manual is checked at regular intervals,


and necessary corrections are included in the next releases.
Your suggestions are welcome.

Passing on or reproduction of this document, utilization and revelation


of its contents is not permitted without express permission.
Violations shall be cause for damage claims.
All rights reserved, in particular when a patent is issued or a general
model registered.

Subject to change without prior notice.

Registered trademarks
SIPROTEC und DIGSI are registered trademarks of Siemens AG.
Other designations in this manual may be trademarks that if used by
third parties for their own purposes may violate the rights of the owner.

Siemens Aktiengesellschaft

C53000-L1840-B003-01

Preface
Contents of this
manual

The manual is devided into the following topics:


Data in the PROFIBUS-DP messages
Message in output direction: PROFIBUS-DP master to the 7SJ62/63
Message in input direction: 7SJ62/63 to the PROFIBUS-DP master

Additional
literature

This manual describes the data in the PROFIBUS-DP messages of the


SIPROTEC devices 7SJ62 and 7SJ63.
The following additional manuals inform you about the data types, bus
specific parameters and hardware description of the PROFIBUS-DP
slave modul and the function, operation, assembly and commissioning
of the SIPROTEC devices:
Manual

Contents

Order number

Overcurrent, overload
and motor protection with
control
SIPROTEC 7SJ61

Function, operation, assembly


and commissioning of the
SIPROTEC device 7SJ61

C53000-G1140-C118-2

Multifunction protection
with control
SIPROTEC 7SJ62

Function, operation, assembly


and commissioning of the
SIPROTEC device 7SJ62

C53000-G1140-C121-2

Multifunction protection
with control
SIPROTEC 7SJ63

Function, operation, assembly


and commissioning of the
SIPROTEC device 7SJ63

C53000-G1140-C120-2

Input/output unit with


local control
SIPROTEC 6MD63

Function, operation, assembly


and commissioning of the
SIPROTEC device 6MD63

C53000-C1840-C101-2

Data types, bus specific parameters and hardware description


of the PROFIBUS-DP slave
modul of the SIPROTEC devices

C53000-L1840-B001-01

7SJ61/62/63 6MD63
PROFIBUS-DP
Communication profile

7SJ62/63 PROFIBUS-DP Bus mapping


C53000-L1840-B003-01

Preface

The PROFIBUS-DP specification and the structure of the PROFIBUSDP messages are defined in the European standard EN 50170:
!

Notes to this
manual

Validity

PROFIBUS Specification
Normative Parts of PROFIBUS-FMS, -DP., -PA
According to the European Standard
EN 50170 Volume 2
Edition 1.0, May 1998
PROFIBUS Nutzerorganisation e.V.
Order-No. 0.032 or 0.042 on CD ROM

This manual provides you with the following aids to make it easier to
locate the information you are looking for:

At the beginning of this manual you will find a complete table of


contents plus separate lists of figures and tables contained in this
manual.

In the individual chapters, you will find information in the left margin
of each page which will give you an overview of the contents of that
particular paragraph.

Following the last chapter of this manual, you will find a glossary
containing definitions of technical terms and abbreviations used in
this manual.

At the end of this manual, you will find a comprehensive index for
fast access to the information you need.

This manual is valid for

SIPROTEC devices 7SJ62 and 7SJ63 with firmware version 4.2 and
PROFIBUS-DP communication module.

Training courses

See our catalog of courses for a list of available courses or contact our
training center in Nuremberg.

Questions

If you have questions to the SIPROTEC devices, contact your Siemens


representative.

ii

7SJ62/63 PROFIBUS-DP Bus mapping


C53000-L1840-B003-01

Revision index
Modified chapters /
pages

Edition
1.0
1.1

Chap. 2, 3.1
Chap. 2.2

1.2

7SJ62/63 PROFIBUS-DP Bus mapping


C53000-L1840-B003-01

Reasons of modification
First edition
th
Dec 16 , 1999
New document layout
rd
Apr 03 , 2000 / Foe.

Short names for user-definable objects corrected.

Notes for using single commands added.


th
Apr 12 , 2000 / Foe.

iii

Revision index

iv

7SJ62/63 PROFIBUS-DP Bus mapping


C53000-L1840-B003-01

Table of contents
1

Data in the PROFIBUS-DP messages........................................................................... 1-1


1.1

Explanation.......................................................................................................... 1-1

1.2

Notes for parametrization in DIGSI ..................................................................... 1-2

1.3

Configuration data of the standard mappings for the 7SJ62/7SJ63.................... 1-3

Message in output direction: PROFIBUS-DP master to the 7SJ62/63 ...................... 2-1


2.1

Double commands (with checkback indication) .................................................. 2-1

2.2

Single commands (without checkback indication) .............................................. 2-2

2.3

Internal commands.............................................................................................. 2-2

2.4

Application logic CFC .......................................................................................... 2-4

Message in input direction: 7SJ62/63 to the PROFIBUS-DP master ........................ 3-1


3.1
3.1.1
3.1.2
3.1.3
3.1.4
3.1.5
3.1.6
3.1.7
3.1.8
3.1.9
3.1.10
3.1.11
3.1.12
3.1.13
3.1.14
3.1.15
3.1.16
3.1.17
3.1.18
3.1.19
3.1.20
3.1.21

Annunciations...................................................................................................... 3-1
Double commands checkback signals............................................................. 3-1
Single commands status .................................................................................. 3-2
Input channels with allocation to the binary inputs and tagging .......................... 3-2
Application logic CFC .......................................................................................... 3-2
Diagnosis............................................................................................................. 3-3
Automatic recloser status.................................................................................... 3-4
Time overcurrent protection ................................................................................ 3-4
Directional time overcurrent protection ............................................................... 3-5
Unbalanced load protection................................................................................. 3-6
Frequency protection........................................................................................... 3-6
Undervoltage and overvoltage protection............................................................ 3-6
Sensitive ground fault protection ......................................................................... 3-7
Circuit breaker failure protection ......................................................................... 3-7
Thermal overload protection ............................................................................... 3-7
Motor start protection .......................................................................................... 3-8
Startup supervision.............................................................................................. 3-8
Trip coil monitor................................................................................................... 3-8
Cold load pickup setup ........................................................................................ 3-8
Measurement supervision ................................................................................... 3-8
Set point alarms .................................................................................................. 3-9
Status annunciations ........................................................................................... 3-9

7SJ62/63 PROFIBUS-DP Bus mapping


C53000-L1840-B003-01

Table of contents

3.2
3.2.1
3.2.2
3.2.3

Measured values ............................................................................................... 3-10


Reference values for selecting a standard mapping in accordance with the
operating values of the primary equipment ....................................................... 3-10
Recorded measured values .............................................................................. 3-11
Measured values mean values....................................................................... 3-12

3.3

Fault locator....................................................................................................... 3-12

3.4

Metered measurands ........................................................................................ 3-13

Glossary .......................................................................................................................... 4-1

Index ................................................................................................................................ 5-1

vi

7SJ62/63 PROFIBUS-DP Bus mapping


C53000-L1840-B003-01

Data in the PROFIBUS-DP messages

Data in the PROFIBUS-DP


messages
1.1

Explanation
Note
The examples shown in this chapter 1.1 do not necessarily correspond
to the real allocation of the objects in the bus mapping.

The chapters 2 and 3 define the data area of the PROFIBUS-DP


messages for data transfer between the PROFIBUS-DP slave of the
SIPROTEC device 7SJ62/7SJ63 and the PROFIBUS-DP master.
The listed SIPROTEC objects in the PROFIBUS-DP message data area
are sorted after byte offset, beginning with 0.

Variables with data


type greater than
or equal to 1 byte
Offset
2

The offset defines the start of the most significant byte in the message,
e.g.:

Designation of the
SIPROTEC objects
IA

Comments
Current in phase A

Scaling
(32767 corresponds to ...)
1: 3276,7 A
2: 3276,7 A
3: 32,767 kA
4: 3276,7 A

Internal
object no.
601

The measured value IA is assigned to data byte 2 (most significant


byte of the measured value) and data byte 3 (least significant byte of the
measured value) in the PROFIBUS-DP message.

7SJ62/63 PROFIBUS-DP Bus mapping


C53000-L1840-B003-01

1-1

Data in the PROFIBUS-DP messages

Bit variables
(SP/SC, DP/DC)
Offset
0/0
0/1

17/4

The offset indicates the byte, which contains the bit value and the
position of bit 0 of the bit variable, e.g. (input message):

Designation of the
SIPROTEC objects
Q0 ON/OFF
OFF
Q0 ON/OFF
ON
Fail Ph. Seq.

Comments

Circuit breaker

Internal
object no.

1 = Failure: Phase Sequence

171

The checkback signal from the circuit breaker (as double-point indi0
1
cation) is located in data byte 0, bit positions 2 (bit 0) and 2 (bit 1).
The single-point indication "Fail Ph. Seq. is located in byte 17, bit
4
position 2 .

The definitions of data types (single-point indication, double-point


indication, measured value etc.) are contained in the manual
"7SJ61/62/63 6MD63 PROFIBUS-DP - Communication profile" (ref.
to page i).

1.2

Notes for parametrization in DIGSI


Only those SIPROTEC objects can be transmitted or controlled by
PROFIBUS-DP which are listed in the column Designation of the
SIPROTEC objects.
All these objects are already contained in the standard parameter set
and they can be identified by their name or their "Internal object no." (not
all SIPROTEC objects have an internal object number).

For transmission of installation-specific commands and annunciations


user-definable objects are available.
Binary outputs and binary inputs of the SIPROTEC device can be
assigned to these objects using the DIGSI parameterization software
(ref. to chap. 2.2 and 3.1.3).
CFC-Incoming annunciations and CFC-Output indications can be used
to allocate protection annunciations, which are not containd in the
standard mapping to positions in the PROFIBUS-DP messages (ref. to
chap. 2.4 and 3.1.4).

1-2

7SJ62/63 PROFIBUS-DP Bus mapping


C53000-L1840-B003-01

Data in the PROFIBUS-DP messages

1.3

Configuration data of the standard mappings for the 7SJ62/7SJ63

There are four standard mappings (standard mapping 1 to standard


mapping 4) available for the SIPROTEC devices 7SJ62 and 7SJ63,
which have an identical data size and differ in the scaling of the
measured values (ref. to chap. 3.2).

PROFIBUS-DP
configuration data

7SJ62/7SJ63 standard mappings


1FH 1FH 1FH 1FH 1FH 1FH 13H 28H
(100 bytes input- and 9 bytes output direction).

PROFIBUS-DP
master

At the configuration of a PROFIBUS-DP slave of the SIPROTEC devices


in the parameterization system of the PROFIBUS-DP masters are to
select the following modules for the 7SJ62/63 standard mappings and to
allocate associated addresses in the I/O addressing range of the
PROFIBUS-DP master:
Module
0
1
2
3
4
5
6
7

Order number
Input 16 Bytes
Input 16 Bytes
Input 16 Bytes
Input 16 Bytes
Input 16 Bytes
Input 16 Bytes
Input 4 Bytes
Output 9 Bytes

Input
address
Addr_Ix
Addr_Ix+16
Addr_Ix+32
Addr_Ix+48
Addr_Ix+64
Addr_Ix+80
Addr_Ix+96

Output
address

Addr_Ox

Addr_Ix and Addr_Ox indicate arbitrary (as a rule even) addresses in the
I/O addressing range of the PROFIBUS-DP master.
Addr_Ix (base address of the inputs) is identical with offset 0 of the
PROFIBUS-DP message data of the SIPROTEC device in input
direction (ref. to chap. 3).
Addr_Ox (base address of the outputs) is identical with offset 0 of the
PROFIBUS-DP message data of the SIPROTEC device in output
direction (ref. to chap. 2).
Note
There is dependently on the PROFIBUS-DP master in addition possibly
the demand to put the base address of the inputs on a value divisible by
four so that accesses on the metered measurands (unsigned long
values, ref. to chap. 3.4) can be correctly carried out in the PROFIBUSDP master.

7SJ62/63 PROFIBUS-DP Bus mapping


C53000-L1840-B003-01

1-3

Data in the PROFIBUS-DP messages

1-4

7SJ62/63 PROFIBUS-DP Bus mapping


C53000-L1840-B003-01

Message in output direction: PROFIBUS-DP master to the 7SJ62/63

Message in output direction:


PROFIBUS-DP master to the
7SJ62/63

The messages in PROFIBUS-DP output direction allow:

command outputs through the output relays of the SIPROTEC


device (external commands),

manipulation of taggings (internal commands), which can be


changed by PROFIBUS-DP.

Note
The allocation of the output relays to the switching devices and to the
output channels is defined during parametrization of the SIPROTEC
devices.
Depending on the device composition there may be less than indicated
output relays (and corresponding PROFIBUS-DP message positions)
available in the SIPROTEC device.

2.1
Offset
0/0
0/1
0/2
0/3
0/4
0/5
0/6
0/7
1/0
1/1

Double commands (with checkback indication)


Designation of the
SIPROTEC objects
Q0 ON/OFF
OFF
Q0 ON/OFF
ON
Q1 ON/OFF
OFF
Q1 ON/OFF
ON
Q8 ON/OFF
OFF
Q8 ON/OFF
ON
Q2 ON/OFF
OFF
Q2 ON/OFF
ON
Q9 ON/OFF
OFF
Q9 ON/OFF
ON

7SJ62/63 PROFIBUS-DP Bus mapping


C53000-L1840-B003-01

Comments

Internal
object no.

Impulse output,
3 relays (2-pole On, 1-pole Off)

Impulse output,
2 relays, 1-pole

Impulse output,
2 relays, 1-pole

Impulse output,
2 relays, 1-pole

Impulse output,
2 relays, 1-pole

2-1

Message in output direction: PROFIBUS-DP master to the 7SJ62/63

Offset
1/2
1/3
1/4
1/4

2.2
Offset
1/6
1/7
2/0
2/1
2/2
2/3

Designation of the
SIPROTEC objects
Switching device D1 (UsrDC1)
OFF
Switching device D1 (UsrDC1)
ON
Switching device D2 (UsrDC2)
OFF
Switching device D2 (UsrDC2)
ON

Comments

Internal
object no.

Impulse output,
4 relays (2-pole)

Impulse output,
2 relays, 1-pole

Single commands (without checkback indication)


Designation of the
SIPROTEC objects
Output channel E1 (UsrSC5)
OFF
Output channel E1 (UsrSC5)
ON
Output channel E2 (UsrSC6)
OFF
Output channel E2 (UsrSC6)
ON
Output channel E3 (UsrSC10)
OFF
Output channel E3 (UsrSC10)
ON

Comments

Internal
object no.

Impulse output,
1 relay, 1-pole

Impulse output,
1 relay, 1-pole

Continuous output without restauration,


1 relay, 1-pole

Note

2.3
Offset

The command output mode (pulse output, continuous output) is


changeable for the single commands using parametrization software
DIGSI. The command output modes indicated in the table above are
predefined.

The switching direction OFF for single commands with pulse output
is not permitted and is rejected in the SIPROTEC device.

Internal commands

2/4

Designation of the
SIPROTEC objects
Auto recl. OFF

Deactivation of Autoreclosing

2/5

Auto recl. ON

Activation of Autoreclosing

2/6

Protection OFF

Deactivation of protection functions

2/7

Protection ON

Activation of potection functions

3/0

<reserved>

3/1

<reserved>

3/2

Mode REMOTE

Control mode REMOTE = LOCKED

3/3

Mode REMOTE

Control mode REMOTE = UNLOCKED

2-2

Comments

Internal
object no.
127

126

7SJ62/63 PROFIBUS-DP Bus mapping


C53000-L1840-B003-01

Message in output direction: PROFIBUS-DP master to the 7SJ62/63

Offset
3/4

Designation of the
SIPROTEC objects
<reserved>

3/5

<reserved>

3/6

<reserved>

3/7

<reserved>

4/0

Setting group A

4/1

Setting group A

4/2

Setting group B

4/3

Setting group B

4/4

Setting group C

4/5

Setting group C

4/6

Setting group D

4/7

Setting group D

Comments

Internal
object no.

Activation of setting group A

Activation of setting group B

Activation of setting group C

Activation of setting group D

53

54

55

56

Control mode REMOTE


Control mode with control authority is REMOTE, option of unlocked
control with PROFIBUS-DP.

Changing the Control mode REMOTE to UNLOCKED permits one


unlocked control operation via PROFIBUS-DP. After execution of
the command, the Control mode REMOTE in the SIPROTEC
device will automatically be reset to LOCKED.

A programmed test Switch in position for unlocked control


operations will always be executed.

If, after changing the Control mode REMOTE to UNLOCKED, no


command is received via PROFIBUS-DP for a period of 5 minutes,
then the Control mode REMOTE is automatically reset to
LOCKED.

If the Control mode REMOTE was automatically reset to LOCKED


by the SIPROTEC device, then this status can be recognized by the
corresponding bit in the PROFIBUS-DP input message. In this case
the status of Control mode REMOTE in output direction has to be
updated by the PROFIBUS-DP master.

7SJ62/63 PROFIBUS-DP Bus mapping


C53000-L1840-B003-01

2-3

Message in output direction: PROFIBUS-DP master to the 7SJ62/63

Changing the setting group


In order to change the setting group, the value 10 = ON must be
transmitted for the corresponding pair of bits and afterwards be reset to
00 = quiescent status (controlled by an impulse from the PROFIBUSDP master). Switching on one setting group automatically switches off
the current active setting group. Transmission of the value 01 = OFF is
insignificant for the change of the setting group and is refused by the
device.
A change of the setting group is only possible via PROFIBUS-DP if the
parameter CHANGE TO ANOTHER SETTING GROUP (parameter address =
302) has the value "Protocol".

2.4
Offset
5/0
5/1
5/2
5/3
5/4
5/5
5/6
5/7
6/0
6/1
6/2
6/3
6/4
6/5
6/6
6/7
7/0
7/1
7/2
7/3
7/4
7/5

2-4

Application logic CFC


Designation of the
SIPROTEC objects
CFC-Incoming annunciation 1
(UsCfcSpI1) OFF
CFC-Incoming annunciation 1
(UsCfcSpI1) ON
CFC-Incoming annunciation 2
(UsCfcSpI2) OFF
CFC-Incoming annunciation 2
(UsCfcSpI2) ON
CFC-Incoming annunciation 3
(UsCfcSpI3) OFF
CFC-Incoming annunciation 3
(UsCfcSpI3) ON
CFC-Incoming annunciation 4
(UsCfcSpI4) OFF
CFC-Incoming annunciation 4
(UsCfcSpI4) ON
CFC-Incoming annunciation 5
(UsCfcSpI5) OFF
CFC-Incoming annunciation 5
(UsCfcSpI5) ON
CFC-Incoming annunciation 6
(UsCfcSpI6) OFF
CFC-Incoming annunciation 6
(UsCfcSpI6) ON
CFC-Incoming annunciation 7
(UsCfcSpI7) OFF
CFC-Incoming annunciation 7
(UsCfcSpI7) ON
CFC-Incoming annunciation 8
(UsCfcSpI8) OFF
CFC-Incoming annunciation 8
(UsCfcSpI8) ON
CFC-Incoming annunciation 9
(UsCfcSpI9) OFF
CFC-Incoming annunciation 9
(UsCfcSpI9) ON
CFC-Incoming annunciation 10
(UsCfcSpI10) OFF
CFC-Incoming annunciation 10
(UsCfcSpI10) ON
CFC-Incoming annunciation 11
(UsCfcSpI11) OFF
CFC-Incoming annunciation 11
(UsCfcSpI11) ON

Comments

Internal
object no.

Tagging ON/OFF, released as CFC input

Tagging ON/OFF, released as CFC input

Tagging ON/OFF, released as CFC input

Tagging ON/OFF, released as CFC input

Tagging ON/OFF, released as CFC input

Tagging ON/OFF, released as CFC input

Tagging ON/OFF, released as CFC input

Tagging ON/OFF, released as CFC input

Tagging ON/OFF, released as CFC input

Tagging ON/OFF, released as CFC input

Tagging ON/OFF, released as CFC input

7SJ62/63 PROFIBUS-DP Bus mapping


C53000-L1840-B003-01

Message in output direction: PROFIBUS-DP master to the 7SJ62/63

Offset
7/6
7/7
8/0
8/1
8/2
8/3
8/4
8/5
8/6
8/7

Designation of the
SIPROTEC objects
CFC-Incoming annunciation 12
(UsCfcSpI12) OFF
CFC-Incoming annunciation 12
(UsCfcSpI12) ON
CFC-Incoming annunciation 13
(UsCfcSpI13) OFF
CFC-Incoming annunciation 13
(UsCfcSpI13) ON
CFC-Incoming annunciation 14
(UsCfcSpI14) OFF
CFC-Incoming annunciation 14
(UsCfcSpI14) ON
CFC-Incoming annunciation 15
(UsCfcSpI15) OFF
CFC-Incoming annunciation 15
(UsCfcSpI15) ON
CFC-Incoming annunciation 16
(UsCfcSpI16) OFF
CFC-Incoming annunciation 16
(UsCfcSpI16) ON

Comments

Internal
object no.

Tagging ON/OFF, released as CFC input

Tagging ON/OFF, released as CFC input

Tagging ON/OFF, released as CFC input

Tagging ON/OFF, released as CFC input

Tagging ON/OFF, released as CFC input

Note
The CFC-Incoming annunciations allow routing of further protection
annunciations on PROFIBUS-DP, which are not contained in the
standard mapping (e.g. ">BLK 50/51", internal object number = 1704 or
">BLK 50N/51N", internal object number = 1714).

Example

Control of object ">BLK 50/51" using CFC-Incoming annunciation 1


(UsCfcSpI1) via PROFIBUS-DP:

In the DIGSI configuration matrix set the source for ">BLK 50/51" to
CFC output.

All CFC-Incoming annunciations are released as CFC input by


default, therefore no further actions in the DIGSI configuration matrix
are nessesary.

Open a CFC working page and insert a CONNECT module.

Connect the input (BO X) of the CONNECT module with the


operand "UsCfcSpI1 (group Protocol).

Connect the output (Y BO) of the CONNECT module with the


operand ">BLK 50/51" (Gruppe: "50/51 Overcur.).

Save and translate the CFC working page.

The object ">BLK 50/51" (and with that the associated protective
function) can be influenced by changing the value of the CFC-Incoming
annunciation 1 via PROFIBUS-DP now.

7SJ62/63 PROFIBUS-DP Bus mapping


C53000-L1840-B003-01

2-5

Message in output direction: PROFIBUS-DP master to the 7SJ62/63

2-6

7SJ62/63 PROFIBUS-DP Bus mapping


C53000-L1840-B003-01

Message in input direction: 7SJ62/63 to the PROFIBUS-DP master

Message in input direction:


7SJ62/63 to the PROFIBUS-DP
master

The messages in PROFIBUS-DP input direction allow:

3.1

polling of switching devices status and binary inputs,

transmission of annunciations, measurands and meter values to the


PROFIBUS-DP master.

Annunciations
Note
The allocation of the input channels to the binary inputs is defined during
parameterization of the devices.
Depending on the device composition and the existing protection
packages not all of the indicated binary inputs or protection
annunciations (and corresponding PROFIBUS-DP message positions)
may be available in the SIPROTEC device.

3.1.1 Double commands checkback signals


Offset
0/0
0/1
0/2
0/3
0/4
0/5
0/6
0/7

Designation of the
SIPROTEC objects
Q0 ON/OFF
OFF
Q0 ON/OFF
ON
Q1 ON/OFF
OFF
Q1 ON/OFF
ON
Q8 ON/OFF
OFF
Q8 ON/OFF
ON
Q2 ON/OFF
OFF
Q2 ON/OFF
ON

7SJ62/63 PROFIBUS-DP Bus mapping


C53000-L1840-B003-01

Comments

Internal
object no.

Double-point indication ON/OFF

Double-point indication ON/OFF

Double-point indication ON/OFF

Double-point indication ON/OFF

3-1

Message in input direction: 7SJ62/63 to the PROFIBUS-DP master

Offset
1/0
1/1
1/2
1/3
1/4
1/5

Designation of the
SIPROTEC objects
Q9 ON/OFF
OFF
Q9 ON/OFF
ON
Switching device D1 (UsrDC1)
OFF
Switching device D1 (UsrDC1)
ON
Switching device D2 (UsrDC2)
OFF
Switching device D2 (UsrDC2)
ON

Comments

Internal
object no.

Double-point indication ON/OFF

Double-point indication ON/OFF

Double-point indication ON/OFF

3.1.2 Single commands status


Offset
1/6

Designation of the
SIPROTEC objects
Output channel E1 (UsrSC5)

Comments
Single-point indication ON/OFF

Internal
object no.

1/7

Output channel E2 (UsrSC6)

Single-point indication ON/OFF

2/0

Output channel E3 (UsrSC10)

Single-point indication ON/OFF

3.1.3 Input channels with allocation to the binary inputs and tagging
Offset
2/1

Designation of the
SIPROTEC objects
Input channel 1 (UsrSpO/C1)

Comments
Single-point indication OPEN/CLOSE

Internal
object no.

2/2

Input channel 2 (UsrSpO/C2)

Single-point indication OPEN/CLOSE

2/3

Input channel 3 (UsrSpO/O11)

Single-point indication ON/OFF

2/4

Input channel 4 (UsrSpO/O12)

Single-point indication ON/OFF

2/5

Input channel 5 (UsrSpO/O13)

Single-point indication ON/OFF

2/6

Input channel 6 (UsrSpO/O14)

Single-point indication ON/OFF

2/7

Input channel 7 (UsrSpO/O32)

Tagging / Internal single-point indication ON/OFF

3.1.4 Application logic CFC


Offset
3/0
3/1
3/2
3/3
3/4
3/5
3/6

3-2

Designation of the
SIPROTEC objects
CFC-Output indication 1
(UsCfcSpO1)
CFC-Output indication 2
(UsCfcSpO2)
CFC-Output indication 3
(UsCfcSpO3)
CFC-Output indication 4
(UsCfcSpO4)
CFC-Output indication 5
(UsCfcSpO5)
CFC-Output indication 6
(UsCfcSpO6)
CFC-Output indication 7
(UsCfcSpO7)

Comments
Single-point indication ON/OFF,
released as CFC output
Single-point indication ON/OFF,
released as CFC output
Single-point indication ON/OFF,
released as CFC output
Single-point indication ON/OFF,
released as CFC output
Single-point indication ON/OFF,
released as CFC output
Single-point indication ON/OFF,
released as CFC output
Single-point indication ON/OFF,
released as CFC output

Internal
object no.

7SJ62/63 PROFIBUS-DP Bus mapping


C53000-L1840-B003-01

Message in input direction: 7SJ62/63 to the PROFIBUS-DP master

Offset
3/7
4/0
4/1
4/2
4/3
4/4
4/5
4/6
4/7

Designation of the
SIPROTEC objects
CFC-Output indication 8
(UsCfcSpO8)
CFC-Output indication 9
(UsCfcSpO9)
CFC-Output indication 10
(UsCfcSpO10)
CFC-Output indication 11
(UsCfcSpO11)
CFC-Output indication 12
(UsCfcSpO12)
CFC-Output indication 13
(UsCfcSpO13)
CFC-Output indication 14
(UsCfcSpO14)
CFC-Output indication 15
(UsCfcSpO15)
CFC-Output indication 16
(UsCfcSpO16)

Comments
Single-point indication ON/OFF,
released as CFC output
Single-point indication ON/OFF,
released as CFC output
Single-point indication ON/OFF,
released as CFC output
Single-point indication ON/OFF,
released as CFC output
Single-point indication ON/OFF,
released as CFC output
Single-point indication ON/OFF,
released as CFC output
Single-point indication ON/OFF,
released as CFC output
Single-point indication ON/OFF,
released as CFC output
Single-point indication ON/OFF,
released as CFC output

Internal
object no.

Note
The CFC-Output indications allow configuration of further protection
annunciations with PROFIBUS-DP, which are not contained in the
standard mapping.

3.1.5 Diagnosis
Offset
5/0

Designation of the
SIPROTEC objects
Device OK

5/1

ProtActive

1 = Update of the device replica in the SIPROTEC


device completed after initial start or restart
1 = At least one protection function is active

5/2

Settings Calc.

1 = Setting calculation is running

70

5/3

Error Sum Alarm

1 = Error with a summary alarm ON

140

5/4

Alarm Sum Event

1 = Alarm summary event ON

160

5/5

Relay PICKUP

1 = Relay PICKUP (protection, summary alarm)

501

5/6

Relay TRIP

1 = Relay GENERAL TRIP command (common,


summary alarm)

511

5/7

<reserved>

7SJ62/63 PROFIBUS-DP Bus mapping


C53000-L1840-B003-01

Comments

Internal
object no.
51
52

3-3

Message in input direction: 7SJ62/63 to the PROFIBUS-DP master

Error with a summary alarm

7SJ62:
The "Error with a summary alarm" corresponds to the internal alarm
I/O-Board error in the 7SJ62.

7SJ63:
! The "Error with a summary alarm" is ON if at least one of the
following internal alarms assumes the value ON:
Error Board 1, Error Board 2, "Error Board 3, "Error
Board 4, "Error Board 5, Error Board 6, "Error Board 7,
I/O-Board error,
! additionally for the 7SJ631, 7SJ632, 7SJ633, 7SJ635 and
7SJ636:
Error 5V, Error 0V, Error -5V.

Alarm summary event


The "Alarm summary event" is indicated, if at least one of the following
internal alarms assumes the ON status:
"Failure: Current summation, "Failure: Current balance, "Failure:
Voltage balance, "Failure: Phase sequence current, "Failure: Phase
sequence voltage.

3.1.6 Automatic recloser status


Offset
6/0

Designation of the
SIPROTEC objects
>CB Ready

Comments

Internal
object no.
2730

1 = Binary input circuit breaker ready is active

6/1

79 OFF

1 = AR is switched OFF

2781

6/2

79 ON

1 = AR is switched ON

2782

6/3

79 Close

1 = AR close command

2851

6/4

79 Successful

1 = AR successfully completed

2862

6/5

79 Lockout

1 = AR definitive TRIP

2863

6/6

TRIP Gnd Fault

1 = AR TRIP ground fault

2869

6/7

TRIP Ph Fault

1 = AR TRIP phase fault

2870

3.1.7 Time overcurrent protection


Offset
7/0

Designation of the
SIPROTEC objects
50/51 PH OFF

1 = Time overcurrent phase is OFF

Internal
object no.
1751

7/1

50N/51N OFF

1 = Time overcurrent ground is OFF

1756

3-4

Comments

7SJ62/63 PROFIBUS-DP Bus mapping


C53000-L1840-B003-01

Message in input direction: 7SJ62/63 to the PROFIBUS-DP master

Offset
7/2

Designation of the
SIPROTEC objects
50(N)/51(N) PU

Comments

Internal
object no.
1761

1 = Time overcurrent PICKUP

7/3

50/51 Ph A PU

1 = Time overcurrent phase A picked up

1762

7/4

50/51 Ph B PU

1 = Time overcurrent phase B picked up

1763

7/5

50/51 Ph C PU

1 = Time overcurrent phase C picked up

1764

7/6

50/51N GND PU

1 = Time overcurrent ground picked up

1765

7/7

50(N)/51(N)TRIP

1 = Time overcurrent TRIP

1791

8/0

50-2 TRIP

1 = 50-2 TRIP

1805

8/1

50-1 TRIP

1 = 50-1 TRIP

1815

8/2

51 picked up

1 = 51 picked up

1820

8/3

51 TRIP

1 = 51 TRIP

1825

8/4

50N-2 TRIP

1 = 50N-2 TRIP

1833

8/5

50N-1 TimeOut

1 = 50N-1 TimeOut

1835

8/6

50N-1 TRIP

1 = 50N-1 TRIP

1836

8/7

51N TRIP

1 = 51N TRIP

1839

3.1.8 Directional time overcurrent protection


Offset
9/0

Designation of the
SIPROTEC objects
Phase A forward

1 = Phase A forward

Internal
object no.
2628

9/1

Phase B forward

1 = Phase B forward

2629

9/2

Phase C forward

1 = Phase C forward

2630

9/3

Phase A reverse

1 = Phase A reverse

2632

9/4

Phase B reverse

1 = Phase B reverse

2633

9/5

Phase C reverse

1 = Phase C reverse

2634

9/6

Ground forward

1 = Ground forward

2635

9/7

Ground reverse

1 = Ground reverse

2636

10/0

67-2 TRIP

1 = 67-2 TRIP

2649

10/1

67/67-TOC OFF

2651

10/2

67N OFF

10/3

67-1 TRIP

1 = Directional time overcurrent PHASE is switched


OFF
1 = Directional time overcurrent GROUND is
switched OFF
1 = 67-1 TRIP

2665

10/4

67-TOC TRIP

1 = 67-TOC TRIP

2675

10/5

67N-2 TRIP

1 = 67N-2 TRIP

2679

10/6

67N-1 TRIP

1 = 67N-1 TRIP

2683

7SJ62/63 PROFIBUS-DP Bus mapping


C53000-L1840-B003-01

Comments

2656

3-5

Message in input direction: 7SJ62/63 to the PROFIBUS-DP master

Offset
10/7

Designation of the
SIPROTEC objects
67N-TOC TRIP

Comments

Internal
object no.
2686

1 = 67N-TOC TRIP

11/0

67 A picked up

1 = Directional time overcurrent Phase A picked up

2692

11/1

67 B picked up

1 = Directional time overcurrent Phase B picked up

2693

11/2

67 C picked up

1 = Directional time overcurrent Phase C picked up

2694

11/3

67N picked up

1 = Directional time overcurrent GROUND picked up

2695

11/4

67/67N TRIP

1 = Directional time overcurrent TRIP

2696

3.1.9 Unbalanced load protection


Offset

Designation of the
SIPROTEC objects

Comments

11/5

46 OFF

1 = Unbalanced load protection is switched OFF

11/6

46 TRIP

1 = 46 TRIP

Internal
object no.
5151
5170

3.1.10 Frequency protection


Offset

Designation of the
SIPROTEC objects

Comments

Internal
object no.
5211

11/7

81 OFF

1 = Frequency protection is switched OFF

12/0

81-1 TRIP

1 = 81-1 TRIP

5236

12/1

81-2 TRIP

1 = 81-1 TRIP

5237

12/2

81-3 TRIP

1 = 81-1 TRIP

5238

12/3

81-4 TRIP

1 = 81-1 TRIP

5239

3.1.11 Undervoltage and overvoltage protection


Offset

Designation of the
SIPROTEC objects

Comments

Internal
object no.
6530

12/4

27 OFF

1 = 27 Undervoltage protection is switched OFF

12/5

27-1 TRIP

1 = 27-1 Undervoltage TRIP

6539

12/6

27-2 TRIP

1 = 27-2 Undervoltage TRIP

6540

12/7

59 OFF

1 = 59 Overvoltage protection is switched OFF

6565

13/0

59-1 TRIP

1 = 59 TRIP

6570

3-6

7SJ62/63 PROFIBUS-DP Bus mapping


C53000-L1840-B003-01

Message in input direction: 7SJ62/63 to the PROFIBUS-DP master

3.1.12 Sensitive ground fault protection


Offset
13/1

Designation of the
SIPROTEC objects
50Ns/67Ns OFF

Comments

Internal
object no.
1211

13/2

64 Pickup

1 = Sensitive ground fault protection is switched


OFF
1 = 64 displacement voltage pick up

13/3

64 TRIP

1 = 64 displacement voltage element TRIP

1217

13/4

50Ns-2 TRIP

1 = 50Ns-2 TRIP

1223

13/5

50Ns-1 TRIP

1 = 50Ns-1 TRIP

1226

13/6

51Ns TRIP

1 = 51Ns TRIP

1229

13/7

Sens.Gnd Pickup

1 = Sensitive ground fault pick up

1271

14/0

Sens. Gnd Ph A

1 = Sensitive ground fault picked up in phase A

1272

14/1

Sens. Gnd Ph B

1 = Sensitive ground fault picked up in phase B

1273

14/2

Sens. Gnd Ph C

1 = Sensitive ground fault picked up in phase C

1274

14/3

SensGnd Forward

1 = Sensitive GND fault in forward direction

1276

14/4

SensGnd Reverse

1 = Sensitive GND fault in reverse direction

1277

14/5

SensGnd undef.

1 = Sensitive GND fault direction undefined

1278

1215

3.1.13 Circuit breaker failure protection


Offset
14/6

Designation of the
SIPROTEC objects
50BF OFF

14/7

50BF TRIP

Comments
1 = Circuit breaker failure protection is switched
OFF
1 = Circuit breaker failure TRIP

Internal
object no.
1451
1471

3.1.14 Thermal overload protection


Offset
15/0

Designation of the
SIPROTEC objects
49 O/L OFF

1 = Thermal overload protection is switched OFF

15/1

49 O/L I Alarm

1 = 49 Overload current alarm (I alarm)

1515

15/2

49 O/L <Theta> Alarm

1 = 49 Overload alarm! Near thermal TRIP

1516

15/3

49 Windings O/L

1 = 49 Winding overload

1517

15/4

49 Th O/L TRIP

1 = 49 Thermal overload TRIP

1521

15/5

<reserved>

7SJ62/63 PROFIBUS-DP Bus mapping


C53000-L1840-B003-01

Comments

Internal
object no.
1511

3-7

Message in input direction: 7SJ62/63 to the PROFIBUS-DP master

3.1.15 Motor start protection


Offset
15/6

Designation of the
SIPROTEC objects
>66 emerg. start

Comments
1 = Binary input Emergency start is active

Internal
object no.
4823

15/7

66 OFF

1 = Motor start protection is switched OFF

4824

16/0

66 TRIP

1 = Motor start protection TRIP

4827

3.1.16 Startup supervision


Offset
16/1

Designation of the
SIPROTEC objects
START-SUP OFF

Comments

Internal
object no.
6811

1 = Startup supervision is switched OFF

16/2

START-SUP OFF

1 = Startup supervision TRIP

6821

16/3

Rotor locked

1 = Rotor locked

6822

16/4

START-SUP pu

1 = Startup supervision Pickup

6823

3.1.17 Trip coil monitor


Offset
16/5

Designation of the
SIPROTEC objects
FAIL: Trip cir.

Comments
1 = 74TC Failure trip circuit

Internal
object no.
6865

3.1.18 Cold load pickup setup


Offset
16/6

Designation of the
SIPROTEC objects
CLP OFF

Comments

Internal
object no.
1994

1 = Cold-load-pickup is switched OFF

16/7

CLP BLOCKED

1 = Cold-load-pickup is BLOCKED

1995

17/0

CLP running

1 = Cold-load-pickup is RUNNING

1996

17/1

Dyn set. ACTIVE

1 = Dynamic settings are ACTIVE

1997

3.1.19 Measurement supervision


Offset
17/2

Designation of the
SIPROTEC objects
Fail I Superv.

1 = Failure: General current supervision

17/3

Failure <Sum>I

1 = Failure: Current summation

162

17/4

Fail Ph. Seq.

1 = Failure: Phase sequence

171

17/5

MeasSup OFF

1 = Measurement supervision is switched OFF

197

3-8

Comments

Internal
object no.
161

7SJ62/63 PROFIBUS-DP Bus mapping


C53000-L1840-B003-01

Message in input direction: 7SJ62/63 to the PROFIBUS-DP master

3.1.20 Set point alarms


Offset
17/6

Designation of the
SIPROTEC objects
SP. Op Hours>

Comments
1 = Set point operating hours

Internal
object no.
272

17/7

SP. IA dmd>

1 = Set point phase A dmd>

273

18/0

SP. IB dmd>

1 = Set point phase B dmd>

274

18/1

SP. IC dmd>

1 = Set point phase C dmd>

275

18/2

SP. I1 dmd>

1 = Set point positive sequence I1 dmd>

276

18/3

SP. |Pdmd|>

1 = Set point |Pdmd|>

277

18/4

SP. |Qdmd|>

1 = Set point |Qdmd|>

278

18/5

SP. |Sdmd|>

1 = Set point |Sdmd|>

279

18/6

SP. 37-1 alarm

1 = Set point 37-1 undercurrent alarm

284

18/7

SP. PF(55)alarm

1 = Set point 55 power factor alarm

285

3.1.21 Status annunciations


Offset

Designation of the
SIPROTEC objects

Comments

Internal
object no.

19/0

>No Volt

1 = Binary input No voltage (fuse blown)" is active

19/1

DataStop

1 = "Stop data transmssion" is active

19/2

Test mode

1 = Test mode is active

Control authority
(0 = REMOTE, 1 = LOCAL)
Control mode LOCAL
(0 = LOCKED, 1 = UNLOCKED)
Control mode REMOTE
(0 = LOCKED , 1 = UNLOCKED)
Control authority
(0 = REMOTE, 1 = LOCAL)
Control mode LOCAL
(0 = LOCKED, 1 = UNLOCKED)

19/3

Cntrl Auth (device 7SJ63)

19/4

ModeLOCAL (device 7SJ63)

19/5

ModeREMOTE

19/6

Cntrl Auth (device 7SJ62)

19/7

ModeLOCAL (device 7SJ62)

Stop data transmission


The functionality "Stop data transmission" is not supported via
PROFIBUS-DP communication. If "Stop data transmission" is active
nevertheless data via PROFIBUS-DP will be transmitted furthermore.
The annunciation "DataStop" signals the activation of "Stop data
transmission" however and can be evaluated correspondingly in the
PROFIBUS-DP master.

1
2

Not used in the 7SJ62.


Not used in the 7SJ63.

7SJ62/63 PROFIBUS-DP Bus mapping


C53000-L1840-B003-01

3-9

Message in input direction: 7SJ62/63 to the PROFIBUS-DP master

3.2

Measured values
Note
Depending on the device composition not all of the indicated analog
inputs (and corresponding PROFIBUS-DP message positions) may be
available in the SIPROTEC device.

Standard mapping

By selecting the standard mappings (standard mapping 1 to standard


mapping 4) the measured values can be scaled in accordance with the
operational values of the primary equipment.
For each measured value the table in chap. 3.2.2 shows in the column
Scaling the scaling values defined in standard mappings 1 to 4, e.g.
(for "IA =):
1: 3276.7 A

- applies to standard mapping 1

2: 3276.7 A

- applies to standard mapping 2

3: 32.767 kA

- applies to standard mapping 3

4: 3276.7 A

- applies to standard mapping 4

3.2.1 Reference values for selecting a standard mapping in accordance with


the operating values of the primary equipment
Note
All conditions in the table below to the selected standard mapping must
be fulfilled so that the measured values are transferred correctly via
PROFIBUS-DP.
Dependent on the SIPROTEC device either parameter address 207 or
parameter address 208 is adjustably.

Standard
mapping
no.
1
2
3
4

Parameter address 1101


Primary operating voltage
Vprim
1,0 kV ... 32.76 kV
1,0 kV ... 327.67 kV
1,0 kV ... 32.76 kV
1,0 kV ... 32.76 kV

Parameter address 1102


Primary operating current
Iprim
10 A ... 999 A
10 A ... 999 A
1 kA ... 32 kA
10 A ... 999 A

Energy values of the


primary equipment
Iprim * Vprim * 3 >= 1 MW
Iprim * Vprim * 3 >= 1 MW
1 MW <= Iprim * Vprim * 3 < 1 GW
Iprim * Vprim * 3 < 1 MW

Standard
mapping
no.
1
2
3
4

Parameter address 206


Ratio factor
Vph / Vdelta
Vprim * Vph / Vdelta < 32.76 kV
Vprim * Vph / Vdelta < 327.67 kV
Vprim * Vph / Vdelta < 32.76 kV
Vprim * Vph / Vdelta < 32.76 kV

Parameter address 207


Ratio factor
IN / Iph
Iprim * IN / Iph < 1 kA
Iprim * IN / Iph < 1 kA
Iprim * IN / Iph >= 1 kA
Iprim * IN / Iph < 1 kA

Parameter address 208


Ratio factor
INs / Iph
Iprim * INs / Iph < 1 kA
Iprim * INs / Iph < 1 kA
Iprim * INs / Iph < 1 kA
Iprim * INs / Iph < 1 kA

3-10

7SJ62/63 PROFIBUS-DP Bus mapping


C53000-L1840-B003-01

Message in input direction: 7SJ62/63 to the PROFIBUS-DP master

3.2.2 Recorded measured values


Offset

Designation of the
SIPROTEC objects

Comments

20

Ia =

Ia

22

Ib =

Ib

24

Ic =

Ic

26

In =

In

28

Va-b =

Va-b

30

Vb-c =

Vb-c

32

Vc-a =

Vc-a

34

VN =

VN

36

P=

P (active power)

38

Q=

Q (reactive power)

40

S=

S (apparent power)

42

Freq =

Frequency

Scaling
(32767 corresponds to ...)
1: 3276.7 A
2: 3276.7 A
3: 32.767 kA
4: 3276.7 A
1: 3276.7 A
2: 3276.7 A
3: 32.767 kA
4: 3276.7 A
1: 3276.7 A
2: 3276.7 A
3: 32.767 kA
4: 3276.7 A
1: 3276.7 A
2: 3276.7 A
3: 32.767 kA
4: 3276.7 A
1: 32.767 kV
2: 327.67 kV
3: 32.767 kV
4: 32.767 kV
1: 32.767 kV
2: 327.67 kV
3: 32.767 kV
4: 32.767 kV
1: 32.767 kV
2: 327.67 kV
3: 32.767 kV
4: 32.767 kV
1: 32.767 kV
2: 327.67 kV
3: 32.767 kV
4: 32.767 kV
1: 32.767 MW
2: 327.67 MW
3: 327.67 MW
4: 3276.7 kW
1: 32.767 MVAR
2: 327.67 MVAR
3: 327.67 MVAR
4: 3276.7 kVAR
1: 32.767 MVAR
2: 327.67 MVAR
3: 327.67 MVAR
4: 3276.7 kVAR

Internal
object no.
601

602

603

604

624

625

626

627

641

642

645

644
327.67 Hz

44

46

48

INs Real =

INs Reac =

PF =

Resistive ground current in isol.


systems

3276.7 A

701

Reactive ground current in isol.


systems

3276.7 A

702

Power Factor

901
3.2767

50

I1 =

I1 (positive sequence)

52

I2 =

I2 (negative sequence)

7SJ62/63 PROFIBUS-DP Bus mapping


C53000-L1840-B003-01

1: 3276.7 A
2: 3276.7 A
3: 32.767 kA
4: 3276.7 A
1: 3276.7 A
2: 3276.7 A
3: 32.767 kA
4: 3276.7 A

605

606

3-11

Message in input direction: 7SJ62/63 to the PROFIBUS-DP master

Offset
54

Designation of the
SIPROTEC objects
V1 =

Comments
V1 (positive sequence)

56

V2 =

V2 (negative sequence)

58

<Theta> Rotor

Temperature of rotor

Scaling
(32767 corresponds to ...)
1: 32.767 kV
2: 327.67 kV
3: 32.767 kV
4: 32.767 kV
1: 32.767 kV
2: 327.67 kV
3: 32.767 kV
4: 32.767 kV

Internal
object no.
629

630

805
327.67 %

60

<Theta> Stator

Temperature of stator

806
327.67 %

62

Td1=

Transducer 1

996
32.767 mA

64

Td2=

Transducer 2

997
32.767 mA

3.2.3 Measured values mean values


Offset
66

Designation of the
SIPROTEC objects
I1 dmd =

I1 (positive sequence) demand

68

P dmd =

Active power demand

3.3

Comments

Scaling
(32767 corresponds to ...)
1: 3276.7 A
2: 3276.7 A
3: 32.767 kA
4: 3276.7 A
1: 32.767 MW
2: 327.67 MW
3: 327.67 MW
4: 3276.7 kW

Internal
object no.
833

834

Fault locator
Note
Always the latest fault location is stored.
In the event of a fault, reading out of the fault record protocol from the
SIPROTEC device is necessary for an exact diagnosis.

Offset
70

3-12

Designation of the
SIPROTEC objects
dist =

Comments
Fault locator:
Distance to fault (Fault location)

Scaling
(32767 corresponds to ...)
3276.7 km/miles

Internal
object no.
1119

7SJ62/63 PROFIBUS-DP Bus mapping


C53000-L1840-B003-01

Message in input direction: 7SJ62/63 to the PROFIBUS-DP master

3.4

Metered measurands

The scaling of the metered measurands, which are derived from


measured values, refers to:

Scaling

60000 impulses per hour for V = Vprim and I = Iprim


Vprim = PRIMARY OPERATING VOLTAGE
(parameter address = 1101)
Iprim =

PRIMARY OPERATING CURRENT


(parameter address = 1102)

In the parameter set is configured:

Example

Iprim = 100 A und Vprim = 12 kV,


60000 impulses correspond so that:
1 h * 100 A * 12 kV * 3 = 2078.46 kWh

Note
The type of the update (cyclic, with or without deletion) and the update
interval must be programmed for the metered measurands (except for
the operating hours meter) with the parameterization software DIGSI.

Offset

72

Designation of the
SIPROTEC objects
Wp(puls) =

76

Wq(puls) =

80

WpForward=

84

WqForward=

88

WpReverse =

92

WqReverse =

96

Comments

Pulsed Energy Wp (active)


(metering impulses at binary input)
Pulsed Energy Wq (reactive)
(metering impulses at binary input)
Wp Forward (metered measurand
derived from measured value)
Wq Forward (metered measurand
derived from measured value )
Wp Reverse (metered measurand
derived from measured value)
Wq Reverse (metered measurand
derived fom measured value)
Counter of operating hours of the
primary equipment

Op.Hours=

Scaling
(231-1 of the unsigned longvalue corresponds to...)
31
2 -1 impulses

Internal
object no.
888

31

889

31

924

31

925

31

928

31

929

2 -1 impulses
2 - 1 impulses
2 -1 impulses
2 -1 impulses
2 -1 impulses
31

2 -1 hours

1020

Note
The scaling of the metered measurands at binary inputs ("Wp(puls)" and
"Wq(puls)") depends on the externally connected pulse generator.

7SJ62/63 PROFIBUS-DP Bus mapping


C53000-L1840-B003-01

3-13

Message in input direction: 7SJ62/63 to the PROFIBUS-DP master

3-14

7SJ62/63 PROFIBUS-DP Bus mapping


C53000-L1840-B003-01

Glossary

Glossary
AR

Automatic Recloser

CFC

Continuous Function Chart

DC

Double Command

DDB file /
GSD file

The DDB file contains the Device Data Base (technical characteristics) of the
PROFIBUS-DP communication module (PROFIBUS-DP slave).
This file is required for configuration and is supplied together with the
SIPROTEC device.

DIGSI

Parameterization system for SIPROTEC devices

DP

Double-point Indication

Input data/
input direction

Data from the PROFIBUS-DP slave to the PROFIBUS-DP master.

Mapping

Allocation of the SIPROTEC data objects to the positions in the PROFIBUS-DP


messages.

Octet

Term from EN 50170, one octet corresponds to 8 bits.

OLM

Optical Link Module

Output data/
output direction

Data from the PROFIBUS-DP master to the PROFIBUS-DP slave.

PNO

PROFIBUS Nutzerorganisation

PROFIBUS-DP

PROFIBUS - Decentralized Peripherals

PSE

PROFIBUS interface module with (electrical) isolated RS485 interface for the
SIPROTEC devices from Siemens.

PSO

PROFIBUS interface module with optical interface for the SIPROTEC devices
from Siemens.

SC

Single Command

SP

Single-point Indication

7SJ62/63 PROFIBUS-DP Bus mapping


C53000-L1840-B003-01

4-1

Glossary

4-2

7SJ62/63 PROFIBUS-DP Bus mapping


C53000-L1840-B003-01

Index

Index
Numerics

27 ..............................................................3-6
46 ..............................................................3-6
49 ..............................................................3-7
50/51 .........................................................3-4
50BF .........................................................3-7
50Ns..........................................................3-7
51Ns..........................................................3-7
59 ..............................................................3-6
64 ..............................................................3-7
66 ..............................................................3-8
67 ..............................................................3-5
79 ..............................................................3-4
81 ..............................................................3-6

Measured values .................................... 3-10


Measurement supervision ........................ 3-8
Metered measurands.............................. 3-13
Motor start protection................................ 3-8

A
Alarm summary event...............................3-4
additional manuals ........................................ i
annunciations............................................3-1
Automatic recloser status .........................3-4
B

O
operating hours meter ............................ 3-13
Overvoltage protection.............................. 3-6
S
Sensitive ground fault protection .............. 3-7
Set point.................................................... 3-9
setting group ............................................. 2-4
standard mapping ............................1-3, 3-10
standard parameter set ............................ 1-2
Startup supervision ................................... 3-8
Stop data transmission ............................. 3-9
switching devices status .......................... 3-1
T

binary inputs.......................................1-2, 3-1


Binary outputs ...........................................1-2

Thermal overload protection..................... 3-7


Time overcurrent protection...................... 3-4
Trip coil monitor ........................................ 3-8

CFC-Incoming annunciations ...................2-5


change of the setting group ......................2-4
Circuit breaker failure protection...............3-7
Cold-load-pickup .......................................3-8
configuration data .....................................1-3
control authority .................................2-3, 3-9
Control mode ....................................2-3, 3-9

Unbalanced load protection ...................... 3-6


Undervoltage protection............................ 3-6
user-definable objects .............................. 1-2
V
Validity ..........................................................ii

D
Directional time overcurrent protection .....3-5
Double-point indication .............................3-1
E
Error with a summary alarm......................3-4
F
Fault locator ............................................3-12
Frequency protection ................................3-6

7SJ62/63 PROFIBUS-DP - Busmapping


C53000-L1840-B003-01

5-1

Index

5-2

7SJ62/63 PROFIBUS-DP Bus mapping


C53000-L1840-B003-01

You might also like