You are on page 1of 1

41-11

07-09-10 -R6
2

CERTIFIED

610mm TO FIN. GRD.

TIE
6

WRAP

50(2")
AMP WEDGE
CONNECTOR
(C116)

2/0 STR. CU
BARE GRD.

OR

WIRE

AMP WRENCH-LOK
(G044)

1.0m

DETAIL A

8
7

1.0m
SEE DETAIL A FOR
GRD. ROD CONNECTION

NOTE :

1. GROUNDING SHALL COMPLY WITH ELECTRICAL SAFETY AUTHORITY


SAFETY ELECTRICAL CODE - LATEST REVISION .
2. LEAVE 2.4 METRES OF GROUND CONDUCTOR WIRE COILED
IN TRANSFORMER BASE .

2/0 CU. STRANDED BARE, GROUND GRID (610mm BELOW GRADE).

PRECAST CONCRETE FOUNDATION FOR 3 PHASE PADMOUNT TRANSFORMER AS PER

HYDRO ONE BRAMPTON STD. 37-114 .

TYPICAL WALL OPENING FOR DUCT/CABLE INSTALLATION .

OUTLINE OF PROPOSED TRANSFORMER .

TRANSFORMER H0 / X0 GROUNDING .

CONNECTION TO GROUNDING BAR IN TRANSFORMER .

GROUND ROD 20mm(3/4") x 3.0m (10 ) LONG (610 mm BELOW GRADE) .

SUITAB
AMPACT WEDGE CONNECTOR
AMP WRENCH-LOK
CONCENTRIC NEUTRAL

TO TX NEUTRAL

TO GROUNDING GRID

GROUNDING SCHEMATIC

APPROVED IN ACCORDANCE WITH REGULATION 22/04

DATE

R E V I S I O N

APPVD

CHGD FDN BASE CABLE ENTRY OPENINGS

CHECKED:

07-09-10

----------------------

APPROVED:

---------------------

ORIGINAL ISSUE:

OCTOBER 6, 1989

CHGD GROUNDING WIRE LAYOUT

3 PHASE PADMOUNT TRANSFORMER


GROUNDING DETAIL