Professional Documents
Culture Documents
4
214
13 14
A
Status DI 1
Status DI 2
13 14
Data contacts
5
DI 1
DI 1
DI 2
L
DI 2
DI
100nF
DI
230 V
230 V
230 V
N N
7
750-405
750-405
The digital input module receives control signal from the digital field devices
(sensors, etc.).
Field and system levels are electrically isolated.
Notice:
An additional supply module must be added for operation with 230VAC!
Description
Item No.
Pack.
Unit
Technical Data
2DI 230V AC
2DI 230V AC (without connector)
750-405
753-405
1
1
Number of inputs
Current consumption (internal)
Voltage via power jumper contacts
Accessories
753 Series Connectors
Coding elements
Item No.
Pack.
Unit
753-110
753-150
25
100
Approvals
Conformity marking
Korea Certification
Marine applications
r UL 508
r ANSI/ISA 12.12.01
4 TV 07 ATEX 554086 X
1
ABS, BV, DNV, GL, KR, LR, NKK, PRS, RINA
Isolation
Internal bit width
Wire connection
Cross sections
Strip lengths, 750/753 Series
Width
Weight
EMC immunity of interference
EMC emission of interference
2
2 mA
230 V AC (-15 % ... +20 %);
( 20 % 1.5 s)
0 V ... 40 V AC
164 V AC ... 1.1 VN
10 ms
6.5 mA
f (nominal) 10 %
50 Hz 10 %
60 Hz 10 %
1.5 kV eff. (field/system)*;
* 2.5 kV rated surge voltage
2 bits
CAGE CLAMP
0.08 mm ... 2.5 mm / AWG 28 ... 14
8 ... 9 mm / 0.33 in
9 ... 10 mm / 0.37 in
12 mm
48.7 g
acc. to EN 61000-6-2, marine applications
acc. to EN 61000-6-4, marine applications
26.01.2016
Tel.: +49(0)571/887-0
E-Mail: info@wago.com
Fax: +49(0)571/887-169