You are on page 1of 5

Cv From d, qm, rho, dP

Area = (pi/4) x d^2


diameter
Area
Area
Volumetric vol flow rate = area x vel
Area
Vel
vel
vol flow

14 in
153.93804 in^2
1.069014167 ft^2
1.069014167 ft^2
4209.485842 ft/min
70.15809736 ft/sec
75 ft^3/sec

vol flow
4500 ft^3/min
Mass flow rw = vol flow x density
vol flow
75 ft^3/sec
density (rho)
0.075 lb/ft^3
w
5.625 lb/sec
W=w * 3600
20250 lb/hr
Pressure drConvert in wc to psi ( 1 psi = 27.58" wc)
dp
0.15 in wc
dp
0.005438724 psi
Cv calculatCv = W / (63.3 Fp Y sqrt (dp x rho))
Equation 3-15 in TP-410
W
20250 lb/hr
Fp
1 unitless
Y
1 estimated (range 0.667 to 1.0)
dp
0.005438724 psi
rho
0.075 lb/ft^3
Cv
15,840
Resistance Resistance Coefficient K = 891 d^4 / Cv^2
d
14 in
Cv
15839.52622
K
0.136428616

15 in TP-410

14" End of Lateral Balancing Damper


Area = (pi/4) x d^2
diameter
14 in
Area
153.93804 in^2
Area
1.069014167 ft^2
vol flow rate = area x vel
Area
1.069014167 ft^2
Vel
2000 ft/min
vel
33.33333333 ft/sec
vol flow
35.63380556 ft^3/sec
w = vol flow x density
vol flow
35.63380556 ft^3/sec
density (rho)
0.075 lb/ft^3
w
2.672535417 lb/sec
W=w * 3600
9621.127502 lb/hr
Convert in wc to psi ( 1 psi = 27.58" wc)
dp
0.028 in wc
dp
0.001015228 psi
Cv = W / (63.3 Fp Y sqrt (dp x rho))
Equation 3-15 in TP-410
W
9621.127502 lb/hr
Fp
1 unitless
Y
1 estimated (range 0.667 to 1.0)
dp
0.001015228 psi
rho
0.075 lb/ft^3
Cv
17,418
Resistance Coefficient K = 891 d^4 / Cv^2
d
14 in
Cv
17418.45952
K
0.112815912

15 in TP-410