Professional Documents
Culture Documents
Table of contents
Introduction
10
10
Entry box
Micro ODF
10
Entry pipes
11
15
Telecommunication cabling
15
Telecommunication socket
15
Accessories
16
Flat distribution
16
Villa distribution
Labeling
19
Under-floor systems
19
Mobile requirements
19
20
FTTH Requirements
Fiber distribution hub at main telecom room
11
15
21
Important notes
23
List of annexures
26
Introduction
A raised floor of minimum 300mm should be provided if required, depending on the telecom room usage.
The room must be provided with a good earth set with resistance of less than 1 ohms.
The door opening for the room should swing outwards.
The floor, roof and surrounding wall of the telecom room, should be free of any concealed water/drainage
pipes and air-conditioning ducts passing through.
The room must be provided with an emergency light, a smoke detector and a fire alarm including two hand
held CO2 fire extinguishers of minimum 10KG capacity.
If the telecom room is proposed in the basement, an automatic sump draining system must be provided to
handle water seepages.
The duct entry to building must be sealed air and water tight.
For the main telecom room size, please refer Table No. 1
The room must be free from any water pipes to prevent equipment damage in case of water leakage
The room must readily be accessible to Etisalat personnel and equipment 24 hr every day, all the days, round
the clock and the room must be clean, dry and free from dust
Flat distribution
All UTP cables inside the flat must be through a PVC conduit from indoor equipment cabinet to individual
telecom socket.
Internal conduit must run from indoor equipment cabinet up to individual socket in each room
7
All internal conduits should meet at the cabinet where the SCS on a star topology can be installed
The farthest socket must not exceed 90m from the cabinet
All internal conduits should be of a diameter not less than 25mm
Villa distribution
Indoor equipment cabinet must be installed at ground floor of the villa for distributing internal cables
A secured floor distribution box of size 300mm (L) X 300mm (H) X 150mm (W) flush mounted on wall is
required in every floor of the villa, for distributing SCS, from the indoor equipment cabinet
The distribution box should be kept at a convenient and easily accessible location where the floor distribution
conduits are terminated. It should be installed at a height between 600mm and 1200mm above the finished
floor level
The distribution boxes on different floors of a villa should be connected through a 1 X 50mm black PVC conduit. If
the conduit space will exceed the standard fill-in capacity, then additional conduit of same size may be provided
The distribution box should have 1 X 50mm (2 inch) conduit to the roof-top of the villa, from the cabinet or
from the telephone entry duct location, in order to provide access to cables from the antenna Installation of
in-building fibre drop cables
Mobile requirements
A number of telecom mobile rooms will be required in a development depending on the characteristic of the
buildings. During NOC issuance, Etisalat Mobile Development team shall determine the need for mobile telecom
rooms in the building.
Details and requirements are provided in separate document FTTH Network Installation Guide and Mobile
Requirements.
Direct Fibre
A minimum of 1 core fibre drop cable (2 cores fibre, optional) or as approved design shall be pulled from the
main telecom room FDH location up to indoor equipment cabinet in each flats/offices, with no cut and splice in
between and where both ends must be terminated using SC/APC connector or through fusion splicing.
Multicore Fibre
In multicore fibre system, the cable must be installed from FDH up to mini ODF which is strategically located in
floor telecom room. The cable must be terminated on both ends using SC/APC connector. Multicore riser must
be planned with 25% spare fibers in each riser cable for future service.
In addition, a minimum of 1 core fibre drop cable (2 cores fibre, optional) shall be pulled from the mini ODF up to
indoor equipment cabinet in each flats/offices.
Optical fibre cable details and specifications are provided in Annexure 5.
For single villa, Etisalat to provide the fibre drop cable. However, in case of complex of villas, building owner/
developer must provide, install and terminate outdoor fibre distribution cables & drop closures if required,
including 1 core fibre drop cable (2 cores fibre, optional).
Low-rise buildings including complex of villas may use wall-mount FDH cabinet. This cabinet is recommended for
less than 100 tenancies.
For more details of FDH requirements for various types of buildings, you may refer to Table-1. Also, FDH details &
requirements, specifications are provided in Annexure 4.
For buildings with mobile service rooms, multicore fibre optic cable must be provided by the building owner/
developer. It must be installed from the main telecom room and must be terminated on both ends in a mini-ODF.
Number of fiber cores and termination point to be determine during planning stage. Details and requirements are
provided in separate doucments FTTH network installation guide and mobile requirements.
Micro ODF
Inside the customer premises, termination of fibre drop cable must be through micro ODF also known as Rosette
and it must be installed inside the indoor equipment cabinet.
Specifications for micro ODF are provided in Annexure 5.
10
The Table No. 1 below, details the different requirements for the various types of buildings and types.
Entry Box*
Entry Pipes/
Ducts
11
Single Villa
Complex of Villas
Buildings up to (B+G+5)
floors or building area up to
3000m2
Size: 600mmX600mmX800mm
Location: Within the
compound
Notes: Entry box must have
grade A cover
Size: JRC-4/JRC-12
(Etisalat standard) for plot entry,
and 600mm X 600mm X 800mm
per Villa
Location: Plot entry box must be
within the compound
Notes: Size of joint box is based
on number of villas, blocks and
position Entry box for each villa
must have grade A cover
Size: JRC-4/JRC-12
(Etisalat standard)**
Location: Within the plot
Notes: Additional boxes must be
provided at all turning points of
lead-in, if necessary
Size: JRC-12
(Etisalat standard)**
Location: Within the plot
Notes: Additional boxes must be
provided at all turning points of
lead-in, if necessary
Shopping Mall
Size: JRC-12
(Etisalat standard)
Location: Depending on
the layout
Size: JRC-12
(Etisalat standard)
Location: Depending on
the layout
Size: 3mX4mX3m
(LxWxH) or as per
approval
Location: In the ground
floor common area
To be determined during
design stage
Size: 2m X 3m X 3m (LxWxH) or
as per approval.
Location: every 10 floors starting
from the lowest basement.
To be determined during
design stage
To be determined during
design stage
No Requirements
No Requirements
To be determined during
design stage
To be determined during
design stage
No Requirements
No Requirements
Main Telecom
Room
No Requirements
No Requirements
No Requirements
Size: 3m X 3m X 3m
Size: 3m X 3m X 3m
Mobile Service
Room
No Requirements
No Requirements
No Requirements
No Requirements
Size:1mX2mX3m(LxWxH)
or as per approval
Notes: Dedicated floor
telecom room to be
provided or as per advise
Location: In common area
Size:1mX2mX3m(LxWxH)
or as per approval
Notes: Dedicated floor
telecom room to be
provided or as per advise
Location: In common area
To be determined during
design stage
No Requirements
No Requirements
No Requirements
Floor Telecom
Space
No Requirements
No Requirements
Riser Cable
Containment
Type: Pipe/duct
Qty. & Size: 1X50mm
Remarks: To be provided
between distribution boxes
12
Shopping Mall
Factories
and Warehouses
Size: 300mmX300mmX150mm
Notes: To be provided in
each floor telecom room,
flush to wall
Size: 300mmX300mm
X150mm
Notes: To be provided in
each floor telecom room,
flush to wall
Size:
300mmX300mmX150mm
Notes: To be provided for
remote buildings, flush to
wall
Size: 300mmX300mmX150mm
Notes: To be provided in each floor
telecom room, flush to wall
Single Villa
Complex of Villas
Buildings up to (B+G+5)
floors or building area up to
3000m2
Floor
Distribution Box
Size: 300mmX300mmX150mm
Location: convenient location
with 1 meter free wall space
around
Notes: The box must be
recessed inside the wall
for each floor, and must be
installed at a height between
600-1200mm above finished
floor level.
Size: 300mmX300mmX150mm
Notes: To be provided in each
floor telecom room, flush to wall
Size: 300mmX300mmX150mm
Indoor
Equipment Cabinet
Size: 600mm(H)X425mm(W)
X120mm(D)
Location: Common and
accessible areas
Size: 600mm(H)X425mm(W)
X120mm(D)
Location: Common and
accessible areas in each flat
Size: 600mm(H)X425mm(W)
X120mm(D)
Location: Common and accessible
areas in each flat
Size: 600mm(H)X425mm(W)
X120mm(D)
Location: Common and accessible
areas in each flat
To be determined during
design stage
To be determined during
design stage
Size: 600mm(H)X425mm(W)
X 120mm(D)
Location: Common and
accessible areas in each
factory/warehouse
Size: 600mm(H)X425mm(W)
X120mm(D)
Location: Common and accessible
areas in each Shop/Sheds
No Requirements
To be determined during
design stage
No Requirements
Direct fibre
To be determined during
design stage
To be determined during
design stage
Fibre Distribution
Hub
Fibre Network
Architecture
No Requirements
Direct fibre
*Entry box size and location may vary depending on area Engineer/Planner assessment.
**If proposed Entry Box (EB) location cannot accomodate the standard EB size, 600mm x 600mm x 800mm EB maybe considered, subject to Etisalat approval
13
14
equipment cabinet.
Every socket must be connected with a minimum of four pair SCS CAT 6 cable, following star topology. In case
of hotel buildings, the provision of telecommunication socket should also be extended to the bathrooms.
Telecommunication sockets, cables and associated facilities within the various rooms and premises are to be
provided by the building owner.
However, the following are the general minimum requirements of structured cabling systems for provision of service.
Accessories
All accessory plates should be dual or quad white PVC plated. The use of any special faceplate, which may be
specific to any other manufacturers product range, such as brass finish, etc. should be reviewed.
Telecommunication cabling
The cables used for these wiring must comply with minimum CAT 6 standards.
The planned SCS cable should meet the designed service requirements within the particular flat level and
should have built-in flexibility, to meet growing needs of the tenants.
All SCS cables are to be properly labeled and terminated, in the RJ45 sockets and in patch panel or in CAT 6
compliant Insulation Displacement Connector (IDC) modules by the owners/building contractor.
Building owner is responsible for replacement of in-building cables and other fixtures, if these become faulty.
Cable diagrams must be submitted to Etisalat for approval at the design stage and as-built is required
on completion.
Cables and other accessories required for block wiring may be purchased from any reputable source provided
that the material meets standards.
The name and contact telephone numbers of the SCS installer should be labeled at appropriate location.
Completed SCS should be subject to acceptance by Etisalat. However, the design and performance of the SCS
system should be the responsibility of the installer/owner.
Any upgrading required in the inbuilding facility, telecommunication cables, due to either enhanced demand,
change in building status or damage should be provided by building owner.
The supply and termination of UTP cables on patch panel or IDC modules and sockets locations should be the
responsibility of the installers/owners.
The choice of outlets distribution, location and type, either it is single, dual, or quad, the optimum requirements
in each area, ultimate number of outlets in every locations, flexibility and maximum usage, should be the
responsibility of consultants.
Tip
White
White
White
White
Ring
Blue
Orange
Green
Brown
Telecommunication socket
All outlets should be Category 6 performance, outlets mounted in shutters, typically in dual, triple or quad
formation in a single or double gang white faceplate. All RJ45 outlets should be fitted with spring loaded sliding
shutters to prevent the ingress of dirt and dust.
Provision for at least one dual socket for telecommunication services should be made in every room including
kitchen. Conduit with not less than 25mm should be connected between the socket locations and indoor
15
16
Horizontal cabling
The physical topology of the horizontal cabling should be configured as a star with each outlet connected
directly to a flat/apartment distribution box inside the flat or apartment. No looping of cables from outlet to
outlet is permitted
The horizontal cabling is to be provided to single, dual, triple and quad outlets throughout
The length of cable between the farthest telecommunications outlet and the indoor equipment cabinet should
not exceed 90m (295ft.). Etisalat must be notified in case the cable will exceed allowable length for further advice
A minimum of two telecommunications outlets should be provided for each individual work area. The outlets
may be located with one or more faceplates in the work area.
Spare conduit capacity is important for the removal and replacement of cables if became faulty. The maximum
number of UTP cables inside a conduit recommended for the installation of a Structured Cabling System is shown
below. However, the number of cables may be adjusted if cable pulling difficulties may be encountered
Horizontal pathways
Horizontal pathways (conduits, sleeves, cable trays, etc.) are used for taking the cables from the floor
telecommunications room to the telecommunications outlets in the same floor
A variety of methods are available and the choice of selection of method should depend on the purpose of the
floor area to be served (i.e. general office spaces, apartment dwellings, etc.)
Conduits
The use of conduits as a horizontal raceway system should only be considered when the outlet locations are
permanent, the device densities are low and flexibility is not required
The minimum size of a conduit pipe used as a horizontal pathway from the distribution box to the
telecommunications outlet should be 25mm (1 inch)
For the conduits, the inside bending radius should always be at least 10 times the internal diameter
Minimum of one nylon draw wire must be installed in a conduit
Pull boxes should be located such that they are readily accessible at all times. Pull boxes to be spaced at a
maximum of 15m apart to minimize cable stress during installation and to provide serviceability in the future
Conduits must be free from sharp edges, to prevent cable damage during and subsequent to pulling
Conduits protruding through a floor should be terminated; a minimum of 50mm from the floor to
prevent water or other liquids from flowing into the conduits
17
18
Patching
The design of patch frame layouts is critical to create a high level of manageability within a compact cabinet,
while maintaining effective operations when used by the customer.
We recommend all horizontal UTP cabling should be terminated in a 12 or 24 port patch panel, placed inside
indoor equipment cabinet. Alternatively, CAT6 compliant IDC modules can also be used. Voice services can be
fed from the services patch panel directly to the user outlet using standard 1 pair patch cords.
Feeder raceway
Feeder raceway provides a pathway for the cables from the distribution box in the floor telecommunications
room to the distribution raceways. The minimum size of the feeder raceway should be 40mm (H) X 200mm (W) of
cross-sectional area. The same size must be used for every (multi-channel) layout
The feeder raceways starting point in the floor telecommunications room must be adjacent to the distribution
box. The Feeder raceway should end at the last distribution raceway it is serving.
Labeling
Label elements
Access unit
All fibre optic and SCS infrastructure including floor outlets, patch frames and horizontal cables should be
labeled. A typewritten standard labeling system is recommended. The labeling scheme shall be agreed on with the
clients telecom team. Labeling guide for fiber optic infrastructure is provided in Annexure 7.
Cable trays
Under-floor systems
For general office spaces, an under-floor raceway system should be used for maximum flexibility
In multi-channel layouts, separate raceways must be used for telecommunications and electrical power to
reduce electromagnetic interference. The dividers for separation of compartments in the raceway should be
bonded to ground Main elements of under-floor raceway systems
19
The access unit provides access at the point of intersection of the feeder and the distribution raceways
Cable trays are mostly used for floors with raised tiles or floorings
As a general guideline, cable trays that intersect must be provided with a transitional bend radius of 150mm
in all directions.
Exposed sheet metal edges must be provided with bushings or other means of protection such that cables will
not be damaged during or after installation. Since cable trays are usually metallic, all sharp edges, burrs and
screw tips that may come into contact with cabling should be removed.
The minimum access space between the sub-floor and the underside of the floor tile should be minimum
150mm (6 in). Etisalat should be consulted in the initial design stage to decide on the requirements if the
building is designed for office use.
20
To avoid EMI, the telecommunications pathways, spaces and metallic cables should be installed with the following
clearances:
1200mm from large motors or transformers
300mm from conduit and cables used for electrical power distribution
120mm from fluorescent lighting
Pathways and metallic cables should cross perpendicular to fluorescent lighting and electrical power cables
or conduits.
Equipment room
A room for exclusive use of Etisalat is needed for the telephone equipment. The room should be accessed by the
underground cables, fibre optic cables, patch panel and the distribution to the floor cables. The main telecom
room can be considered for PABX installation in case of commercial single owner building.
Room size
For up to 100 extensions, the minimum floor space required is 2m X 3m
For up to 400 extensions, the floor space required is 4m X 4m
For large systems Etisalat must be consulted at the planning stage
The room should have a minimum height of 3m, be air-conditioned, clean, and dry and free from dust
Condition
<2KVA
2-5KVA
>5KVA
130mm
300mm
600mm
65mm
155mm
300mm
50mm
155mm
300mm
1000mm
1000mm
1000mm
Fluorescent lighting
300mm
300mm
300mm
The room should be far away from high voltage plant. Other services/utility ducts should not run through this
room and it should not be directly under a toilet or bathroom, kitchen and electrical rooms
The room should provide ready access to Etisalat personnel or Etisalats authorized personnel and equipment
but must be secured from unauthorized entry
The room must be properly protected from the risk of flooding if provided in the basement
In multi-PBX user building, each PBX to have its own room
Raised flooring should be provided when required depending on the PBX type
For large PBX installations, air-conditioned battery room adjacent to the equipment room will be required.
Etisalat will supply details at the design stage. The battery room should be provided with an exhaust fan.
Conduit or tray is required between the equipment room and the battery room
Direct sunlight should not fall in the PBX room. Curtains/screens are to be provided for the windows if any
Power conduit and telecom cable conduit must be separate
Electrical requirements
A minimum of two 13 amp 240 v A/C main outlets (via) UPS system should be provided. The actual mains
power requirements will depend on the size and type of the PBX
The room should be provided with an earth not more than 5 ohms
Anti-static flooring should be provided, including the battery room
The rooms must be provided with an emergency light, a smoke detector and a fire alarm
PABX can be installed in the main telecom room in the case of a single owner.
21
22
Important notes
1) This design guide explains in general, all Etisalat requirements that will facilitate the provision of
telecommunication services to new buildings, yet the requirements indicated in the No Objection Certificate
(NOC)/approved building drawing should be fully complied.
9) The building owner/developer may choose to buy these FTTH components from Etisalat if available, or
from any reputable source. However, if the building owner/developer wishes to use different brands other
than recommended, Product Approval Product Registration and Certificate number must be obtained
from the Vendor.
2) Architects/consultants/designers must liaise with Etisalat at the design stage and obtain Etisalat approval on
the final design drawings.
10) FTTH components that are not in Etisalat recommended brand must be certified through Product Approval
process. Sample component and specification sheet must be submitted by the Vendor prior to building
owner/developer purchase.
3) Minimum two sets of telephone design drawings must be submitted for study and approval, before tendering.
For projects located in Dubai Region, design drawings must be uploaded to eNOC portal in PDF format.
11) Building owners/developers are responsible for the maintenance and repair of FTTH in-building network and
SCS installations including replacement of faulty components.
4) Where deviations/comments/amendments are advised on the design, drawings must be corrected and resubmitted for approval.
12) The indoor drop 1F fibre cables (2F, optional) should be from a popular brand and make, conforming to ITU-T
standard G.657A1/A2 single mode fibre standards.
5) One set of approved As-Built drawings, fibre test results and fibre connection details must be submitted
along with the building completion certificate request, which will be certified by Etisalat.
13) The owners must ensure all fibre optic installations and terminations including the Structured Cabling System
(SCS) are installed with utmost quality according to but not limited to the checklist provided in Annexure 8.
14) On completion of the requirements, any comments and snags advised by Etisalat building inspector must be
attended to by the contractor or owner of the building soon, to avoid delays in the issuance of the building
completion certificate.
Also, in case outdoor fibre distribution is required for complex villas, group of shops & sheds. The building
owner shall be responsible for the supply including accessories, installation and termination of outdoor
distribution cable and fibre drop closures.
8) FTTH components recommended brand or make must be acquired from Etisalat prior to purchase and
installation by the building owner/developer. This is to ensure in-building network performance meets
Etisalat standard.
23
24
List of Annexures
25
26
27
b) JRC-12
28
29
30
120 mm
Cross-drilled back
plate
(min 3mm thickness)
ONU
6 0 0mm
5 60 mm
Power socket
Conduits to individual
Conduit from
Floor Distribution Box telecom socket
4 00 mm
Note: Indoor equipment cabinet door can be Right or Left opening as per site convenience.
Specifications
31
32
60 0mm
a) Specifications
3 00 mm
Power socket
Micro-ODF
ONU
60 0mm
Rack shelf
RJ45 Patch panel
Conduit from
Floor Distribution Box
Specifications
Conduits to individual
telecom socket
Note: This type of cabinet is applicable for commercial building with pre-defined offices and for big palaces.
For commercial building with open-floor, Etisalat must be consulted.
33
34
Telcordia qualified
RoHS Complaint
Return loss of 50dB
SC/APC connectivity
Operating temperature of -5C to +60C
All fibers are single mode (ITU-T-G.652D or G.657A1/A2)
d)To determine the quantity of Optical Splitter module and Optical Patch
Panel module
To find the Optical splitter quantity
Number of Tenants/32
(where splitter has 32 output ports)
Note: Etisalat must be consulted for splitter quantity in case of
commercial buildings.
Minimum
distance
Minimum
distance
1.0m
Wall
0.5m
FDH Cabinet
(Free standing type)
Front Side
Wall
35
36
Single mode
Indoor drop fibers
Cable to be of flat cross-section
Suitable for SC/APC connectors
Low friction
Compliant with ITU-T G.652D or G.657A1/A2
Flame Retardant Low Smoke Zero Halogen (LSZH)
37
Maximum attenuation,
@1310nm 0.36dB/km
@1550nm 0.22dB/km
8F, 16F or 24F core
Central strength member, steel stranded wire
38
Shall be wall-mountable
Shall be compact in size and durable
Shall have two lockable compartments
Riser cable pass-through feature
To determine mini ODF location, multicore cable size including required number of SC/APC adaptors and
connectors
The major aspects of Multi-core riser systems are the Fiber selection and mini ODF port capacity are mostly
dependent on the number of flats in each floor.
number of fibers to be used and the number of ports
for mini ODF and its location.
39
Mini ODF location, fiber size, required number of connectors and SC/APC adaptors can be determine as shown in
the matrix.
Tenants Per Floor
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
Cable Size
Every 3 Floors
1X16F
Every 3 Floors
1X24F
Every 3 Floors
2X16F
Every 3 Floors
1X16F
&
1X24F
Every 3 Floors
2X24F
Every 2 Floors
1X16F
&
1X24F
Every 2 Floors
2X24F
Every 1 Floors
2X16F
Number Of
SC/APC Adaptor
3
6
9
12
15
18
21
24
27
30
33
36
39
42
45
48
34
36
38
40
42
44
46
48
25
26
27
28
29
30
SC/APC Connector
(FDH To Mini ODF)
6
12
18
24
30
36
42
48
54
60
66
72
78
84
90
96
68
72
76
80
84
88
92
96
50
52
54
56
58
60
40
6
Typical Multicore riser
cabling system
Description
Value
Unit
1
2
3
4
17.2
0.35
0.25
0.4
dB
dB/Km
dB/km
dB
Splitter No.
Building Number/Name
Splitter Ports
4
5
-
30
31
32
Remarks
Splitter 1
Splitter 2
Splitter 3
Splitter 4
Splitter 5
Measurement Setting
41
1310nm/1550nm
Date
42
Building Number/Name
SN
Mini ODF
No.
1
2
3
4
5
1 / 16F
2 / 24F
3 / 24F
4 / 24F
5 / 24F
1
2
3
4
5
Measurement Setting
Cable length
(meters)
1310nm/1550nm
Measured
Cable Loss
(db)
Emirates
Remarks
Date
1F
Flat Number
Building Number/Name
Cable length (meters)
Shop 1
Shop 2
101
102
103
104
10F
1001
1002
1003
1004
Measurement Setting
43
1310nm/1550nm
Sector/block Number
Date
Remarks
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
Building Number/Name
SPLITTER 1
Patch Panel
No.
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
Port
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
1
2
3
4
5
6
7
8
Flat No.
Notes
Shop 1
Shop 2
Shop 3
Shop 4
MZ01
MZ02
MZ03
MZ04
101
102
103
104
201
202
203
204
301
302
303
304
401
402
403
404
501
502
503
504
601
602
603
604
Modern Bakery
German Rent-A-Car
The Textile Co.
Clock Grocery
44
45
No.
Port
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
1
2
3
4
5
6
7
8
a) Label legends
Building
Number/Name
SPLITTER 1
No.
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
2
2
2
2
3
3
3
3
Mini ODF
Port Location
1
2
3
4
5
6
7
8
9
10
11
12
1
2
3
4
5
6
7
8
9
10
11
12
1
2
3
4
1F
1F
1F
1F
1F
1F
1F
1F
1F
1F
1F
1F
4F
4F
4F
4F
4F
4F
4F
4F
4F
4F
4F
4F
7F
7F
7F
7F
Flat No.
Notes
Shop 1
Shop 2
Shop 3
Shop 4
MZ01
MZ02
MZ03
MZ04
101
102
103
104
201
202
203
204
301
302
303
304
401
402
403
404
501
502
503
504
601
602
603
604
b) Label size
SP1/P1 - ODF1/P1
Label size 9mm
Font size 5mm, black color and all capital
MODF1/P1/3F - ODF1/P1
TO Patch panel 1/Port 1
FROM Mini ODF number 1/Port 1 - Mini ODF location 3rd floor
SP1/P2 - ODF1/P2
TO Patch panel 1/Port 2
FROM Splitter 1/Port 2
F101
TO Flat Number 101
ODF1/P2 - SP1/P2
TO Splitter 1/Port 2
FROM Patch panel 1/Port 2
46
E. Multicore Riser
Descriptions
Remarks
1
2
3
4
1
2
Is the total length of the CAT 6 cables including any patch cords or drop cables at
each end below 100 meters?
Are the cables do not have kinks and bends that exceed its minimum bending radius?
Are the UTP CAT 6 cables are kept a safe 12 inch separation from power cables and
other potential sources of EMI (electrical cables, transformers, light fixtures, etc.) ?
Are all the communication sockets firmly fixed in the wall?
Does all the connection points and cables are properly labelled.
2
3
Descriptions
C. Patch Cord
1
2
3
4
Is the patch cord linking the splitter and patch panel (drop module) properly routed?
Is the patch cord arranged and properly secured?
Is patch cord bending does not exceeds maximum bending radius?
Is patch cord properly labeled?
SN
Remarks
9
Annexure 9 Structure Identification Plate
47
Is it made sure that cables are not in contact with any heating pipes located above
the ceiling?
Are the drop cables from each floor bunched together for easy identification?
Is fibre cable fitted with the right connector?
Is fibre cable properly labeled?
48