You are on page 1of 1

Roof/Ceiling

Components
Asphalt shingles
Asphalt roll roofing
Insulation
Gypsum board
Air film interior
Air film exterior

Area (sq/ft)
1380
1380
1380
1380
1380
1380

R-value
0.44
0.15
8
0.45
0.68
0.17

Thickness

1/2"

Notes
Table A.4 (pg 493)
Table A.4 (pg 493)
Given
Table A.4 (pg 491)
Table A.5 veritcal (pg 494)
Table A.5 15 mph winter (pg 494)

Total R-value
9.89
U-value
0.10
Area - surface area through which heat flows, ft^2

Sum of all R-values


U-value = reciprocal of R-value (1/R)

Exterior Walls (north, south, east, west)


Components
Wood siding
Ashpalt roll siding
Wood sheathing
Insulation
Gypsum board
Air film interior
Air film exterior

Area (sq/ft)
1359
1359
1359
1359
1359
1359
1359

R-value
0.81
0.15
1.14
4
0.32
0.68
0.17

Thickness
Notes
1/2"
Table A.4 (wood, bevel, .5" X 8" lapped)
Table A.4 (pg 494)
1/2"
Table A.4 (pg491) Nail-based sheathing
Given
3/8"
Table A.4 (pg 491)
Table A.5 veritcal (pg 494)
Table A.5 15 mph winter (pg 494)

Total R-value
7.27
Sum of all R-values
U-value
0.14
U-value = reciprocal of R-value (1/R)
Wall height = 9'-0"
Exterior Wall area is determined by total calculated outside dimensions X wall height reference Figure
3.16 (pg 69)

Windows
Location
Area (sq/ft) # Wind.
U-value
Reception Room
14
3
0.98
Office No. 1
14
1
0.98
Office No. 2
14
2
0.98
Office No. 3
14
2
0.98
Open Office
14
1
0.98
Storage
14
1
0.98
Restroom Room
14
1
0.98
*Calculated (window area X number of windows per room)
Window dimensions for all windows = 4'-0" X 3'-6"
U-values - Table A.7 - A.8 assumed winter conditions (pg 500)

*Total Area per Room (sq/ft)


42
14
28
28
14
14
14

Exterior Doors
Location
Area (sq/ft) # Doors
U-value
Reception Room
21
1
0.49
Restroom Room
21
1
0.49
Door dimensions for all exterior doors = 7'-0" X 3'-0"
R-value - thermal resistance of a material, hr-ft^2-F/Btu

Total Area per Room (sq/ft)


21
21

You might also like