You are on page 1of 8

E-Stop with monitored start, protective door monitoring with

automatic start and service mode,


Category 2 according to EN 954-1
with a SIRIUS 3TK2845 safety relay

Functional examples CD-FE-I-023-V01-EN

Safety-related controls
SIRIUS Safety Integrated

E-Stop with monitored start, protective door monitoring with automatic start and
service mode, Category 2 according to EN 954-1

Preliminary comment
Safety Functional Examples are functional and tested automation circuits based on
standard A&D products. They can be used to simply, quickly and cost-effectively
implement applications in safety technology. Each of the Safety Functional
Examples covers a sub-task of a typical customer application involving safety
technology that is frequently encountered.

Function ........................................................................................ 2

1.1

Description of the functionality ....................................................... 2

1.2

Advantages/customer benefits....................................................... 3

Components required.................................................................. 4

Structure and wiring .................................................................... 5

3.1

An overview of the hardware structure........................................... 5

3.2

Connecting-up the hardware components ..................................... 5

Contact partners .......................................................................... 6

Warranty, liability and support ................................................... 6

Evaluation/feedback ....................................................................................... 7

Note
The Safety Functional Examples are not binding and do not claim to be
complete regarding the circuits shown, equipping and any eventuality. The
Safety Functional Examples do not represent customer-specific solutions.
They are only intended to provide support for typical applications. You are
responsible in ensuring that the described products are correctly used. These
Safety Functional Examples do not relieve you of the responsibility in safely
and professionally using, installing, operating and servicing equipment. When
using these Safety Functional Examples, you recognize that Siemens cannot
be made liable for any damage/claims beyond the liability clause described
above. We reserve the right to make changes to these Safety Functional
Examples at any time without prior notice. If there are any deviations between
the recommendations provided in these Safety Functional Examples and other
Siemens publications - e.g. Catalogs - then the contents of the other
documents have priority.

A&D Safety Integrated

Page 1/7

CD-FE-I-023-V01-EN

E-Stop with monitored start, protective door monitoring with automatic start and
service mode, Category 2 according to EN 954-1

Function

1.1

Description of the functionality


If people (in production technology) are close to machines, then they must be
protected using the appropriate equipment.
This Safety Functional example describes how an E-Stop command device
and a guard in the form of a protective door are monitored. The E-Stop
command device represents a widely established component that protects
people, plants/systems and the environment against potential hazards. An
additional solution for plants and machines to secure hazardous areas is
mechanically isolating protective equipment (guards) or access hatches. In
this case, the function is to monitor unauthorized entry into plant and system
areas as well as to prevent potentially hazardous machine functions if the
protective equipment - in this case protective door - is opened.

Actuator

Position switch with


separate actuator

Protective door closed


Protective door opened
In this Safety Functional Example, the E-Stop command device with a positivelyopening contact is monitored by a SIRIUS 3TK2845 safety relay according to
Category 2 in compliance with EN 954-1. If the E-Stop button is pressed, the
safety-relay opens, via safety outputs, the downstream contactors K1 and K2 with
positively driven contacts according to stop Category 0 in compliance with EN
60204-1.
Before powering-up again and acknowledging the E-Stop device using the start
button, a check is made as to whether the contact of the E-Stop command device
is closed and both contactors have been de-energized (i.e. the contactors have
dropped-out).
The protective with a SIRIUS position switch with positively-opening contact door is
also monitored by the 3TK2845 safety relay according to Category 2 in compliance
with EN 954-1. If this protective door is opened, the safety relay also opens the
downstream contactors K1 and K2 via the positively driven safety-related outputs
according to stop Category 0 in compliance with EN 60204-1. If the protective door
is closed and after the position switch and downstream contactor have been
checked, then the drive automatically starts.
If the "Service mode" key-operated switch is actuated, then contactor K2 drops-out
and the protective door can be opened without contactor K1 dropping-out. After the
"Service mode" has been completed, when the key-operated switch is re-actuated,
contactor K2 is automatically closed again. K1 and K2 switch two separate drives.

A&D Safety Integrated

Page 2/7

CD-FE-I-023-V01-EN

E-Stop with monitored start, protective door monitoring with automatic start and
service mode, Category 2 according to EN 954-1

Cascading input
(1)

Relay output,
instantaneous
(13 / 14)

EMERGENCY
STOP
(Y42)

Electronic output,
instantaneous
contactor K1
(24)

Protective door
(Y42)

Relay output,
instantaneous
(33 / 34)
Electronic output,
instantaneous
contactor K2
(44)

Key-operated
switch "service
mode"
(Y72 / Y82)

Safety logic 3TK2845-1BB40 Stop Category 0


Note
Using this circuit example, Category 2 according to EN 954-1 can only be fulfilled if, when
the actuator fails, an alarm is automatically output or the machine control initiates a safety
condition. If this is not the case, a second shutdown path is required.
Equipment, functional aspects and Design Guidelines for E-Stop command devices are
provided in EN 418.(EN ISO 13850 being prepared)
The position switches must be arranged so that they are not damaged when they are
approached and passed. This is the reason that they may not be used as mechanical
endstop.

1.2

Advantages/customer benefits
Pure hardware engineering without having to configure/program
software
Little wiring is required and it is simple
Space-saving design using our compact safety relay
Can be simply expanded using expansion devices

A&D Safety Integrated

Page 3/7

CD-FE-I-023-V01-EN

E-Stop with monitored start, protective door monitoring with automatic start and
service mode, Category 2 according to EN 954-1

Components required

Hardware components

Type

MRPD / Ordering data

Position switch with


separate actuator
Radius actuator
Mushroom head
pushbutton, 1 NC, 40
mm, with yellow upper
section without protective
collar
Empty enclosure of two
command points
1NO contact for basemounting
Pushbutton, black with
flat actuator, 22 mm
nominal diameter
Key-operated switch CES
3TK2845
Contactor, AC-3,
3KW/400V, 1NC, 24V
DC, 3-pole, Size S00,
screw connection

3SE2 243-0XX40

Component
SIRIUS position switch
Actuator for position switch

E-Stop

Start button and service mode

safety relay
Contactors K1 / K2

3SX3 228
3SB3 801-0DG3

Qty.

Manufacturer

1
1

3SB3 802-0AA3
3SB3 420-OB

1
2

Siemens AG

3SB3 000-0AA11
1
3SB3000-4LD01
3TK2845-1BB40
3RT1015-1BB42

1
1
2

Note
The functionality was tested using the specified hardware components. Products that are similar
but deviate from the list above can be used (e.g. a different 3TK28 safety relay). However, in
this case, please carefully note that it may be necessary to make modifications as to how the
hardware components are connected-up (e.g. another connection assignment).

A&D Safety Integrated

Page 4/7

CD-FE-I-023-V01-EN

E-Stop with monitored start, protective door monitoring with automatic start and
service mode, Category 2 according to EN 954-1

Structure and wiring

3.1

An overview of the hardware structure


SIRIUS
position switch

Protective
door

E-Stop
Start
mode

3TK2845 safety relay

L1 L2 L3

L1 L2 L3

K2

K1

3.2

Connecting-up the hardware components


L+(24V DC)

Protective
door

E-Stop

Y11 Y12 Y35 Y21 Y22

3TK2845-1BB40

A1 Y41 Y42 Y65 Y51 Y52

Service
mode
13

14

24

Y72 Y82 A2

33

34

44

Y34 Y64 32

Start

K1

M1

A&D Safety Integrated

K1
M

Page 5/7

K2

K1
K2

K2

M2

CD-FE-I-023-V01-EN

E-Stop with monitored start, protective door monitoring with automatic start and
service mode, Category 2 according to EN 954-1

Contact partners
Technical Assistance for low-voltage switchgear
In person from Mon. - Fri. 8.00 to 17.00 (CET)
Telephone: +49 (911)-895-5900
E-Mail: technical-assistance@siemens.com
Internet: http://www.siemens.de/lowvoltage
By fax, 24 hours a day
Fax: +49 (911)-895-5907

Warranty, liability and support


We do not accept any liability for the information contained in this document.
Any claims against us based on whatever legal reason - resulting from the
use of the examples, information, programs, engineering and performance
data etc., described in this Safety Functional Example shall be excluded. Such
an exclusion shall not apply in the case of mandatory liability, e.g. under the
German Product Liability Act (Produkthaftungsgesetz) in case of intent,
gross negligence, or injury of life, body or health, guarantee for the quality of a
product, fraudulent concealment of a deficiency or breach of a condition which
goes to the root of the contract (wesentliche Vertragspflichten). However,
claims arising from a breach of a condition which goes to the root of the
contract shall be limited to the foreseeable damage which is intrinsic to the
contract , unless caused by intent or gross negligence or based on mandatory
liability for injury of life, body or health. The above provisions does not imply a
change in the burden of proof to your detriment.
Copyright 2004 Siemens A&D. It is not permissible to transfer or copy
these Safety Functional Examples or excerpts of them without first having
prior authorization from Siemens A&D in writing.

A&D Safety Integrated

Page 6/7

CD-FE-I-023-V01-EN

E-Stop with monitored start, protective door monitoring with automatic start and
service mode, Category 2 according to EN 954-1

Evaluation/feedback
Technical Assistance
A&D CD MM1

D-90327 Nrnberg-Moorenbrunn
Fax.: +49 (911) 895-5907
From

Should you come across any printing


errors when reading this publication,
please notify us on this sheet. We would
also be grateful for any suggestions and
recommendations for improvement.

Name:
Department
Location:
Telephone:
Internet address

Evaluation of the Safety Functional Example

very good

good

poor

Because:

Time saving by using the Safety Functional Examples:


No saving

approx. 5%

approx. 10%

other...........%

Suggestions/recommendations:

A&D Safety Integrated

Page 7/7

CD-FE-I-023-V01-EN