Professional Documents
Culture Documents
org). Reprinted by permission from ASHRAE Journal, (Vol. 47, No. 7, July 2005). This article may not be
copied nor distributed in either paper or digital form without ASHRAEs permission.
Designing
Exhaust Systems
to minimize energy costs
By John J. Carter, Member ASHRAE, Ronald L. Petersen, Ph.D., Member ASHRAE, Brad C. Cochran, Member ASHRAE
he usual focus of indoor air quality has been emission sources for 15 minutes or more. The 15-minute
period is important for two reasons. First,
emanating from within the building. However, another critical exposure limits for many chemicals are
ASHRAE Journal
July 2005
Figure 1: Nearby diesel generator exhaust entering a building through an air intake.
19
140
40
120
Fan Power
30
20
10
0
100
Power, bhp
50
80
60
40
20
60
100
140
180
220
Distance from Stack, ft
m3/s)
260
300
20
0
10
20
30
40
50
60
70
80
Design Q (in thousands of cfm)
90
100
Figure 2 (left): Stack height above top of intake required to meet a specied design criterion for various exhaust volume ow rates at a
range of downwind distances. Figure 3 (right): Required fan power vs. design exhaust volume ow rate, Q.
ASHRAE Journal
ashrae.org
July 2005
hausts are operating at the same time, such as in a system that uses real-time input from a local meteorological data station (met
one or more backup exhaust stacks, or a system where fans are station), is developed based on the dispersion analysis. This
staged on/off depending on building ventilation demand, the tight algorithm will allow the exhaust system to run at the lowest
placement of stacks may be detrimental to their performance.
possible ow rate, thus using the minimum amount of energy
ASHRAE is sponsoring a research project (RP-1167, The Effect while still maintaining acceptable air quality. This ow setting
of Ganging on Pollutant Dispersion from Building Exhaust Stacks) would increase as required based on building demand. A simplito quantify this effect so that it may be accurately accounted for ed version of such a system might allow for turndown to the
when using the mathematical dispersion analysis techniques. It is minimum allowable setting based on time of day.
expected that this project will be completed in 2006. The benet
of ganged stacks can be assessed using wind tunnel modeling.
Case Study
Manifolded Exhaust Systems. This method consists of comDuring the design of a recent research laboratory, the design
bining several exhaust streams internally (i.e., upstream of the team was specically interested in determining the relationship
exhaust fan) to dilute intermittent bursts of contamination from between the exhaust system exit velocity and the appropriate
a single source, as well as producing an exhaust with greater stack height along with the associated cost implications. The
plume rise. Additional air volume also may be added to the project plan called for four 40,000 cfm (18 880 L/s) exhaust
exhaust at the fan to achieve the same end.
systems, with two systems on each of two building wings, as
The most recent version of the International Mechanical Code shown in Figure 5. The gure also lists the exit velocities evalu(IMC) states hazardous exhaust systems shall be independent ated (2,862 fpm [14.5 m/s] for the 15 ft [4.6 m] tall stacks and
of other types of exhaust systems. This may preclude manifold- 1,916 fpm [9.7 m/s] for the 20 ft [6 m] tall stacks) as well as the
ing laboratory fume hood and laboratory room exhaust with resulting predicted concentrations (295 g/m3 per g/s and 391
general building exhaust. However, the 2004 2005 proposed g/m3 per g/s). Both exhaust designs proved sufcient to meet
modif ications to the IMC
the established design criterion
may result in exclusion of
of 400 g/m3 per g/s.
On-Site
Chemical Use &
laboratory exhaust systems
The gure also shows the
Met Station
Design Criteria
from this requirement. The
difference in annual energy
energy-use advantage of a
cost, assuming $0.06 per
manifolded system, assuming
kWh, to be approximately
more than one exhaust fan
$1,800 annually per system.
exhausting from a common
This may not be signicant for
Wind Tunnel Test
Building
C/m = f(WD, WS)
plenum, is that the fans may
a single system, but assumAutomation
Fume Hood
System
be controlled so that only the
Control
ing four exhaust systems, the
System
minimum number of fans
energy cost savings is $7,200
operate to satisfy building
per year. Other recent projects
ventilation demand. In this
have shown a range of anVAV Exhaust
case, each exhaust fan/stack
nual savings from $1,500 per
Fans
would need to be designed to
exhaust system to $6,000 per
achieve the design criterion in
exhaust system.
the absence of the other fans Figure 4: Complex integrated control system.
These energy savings are
in the system.
in addition to any rst cost
Emission Controls. This technique may include installing savings that may be achieved through conducting a detailed
restrictive ow orices on compressed gas cylinders, scrubber analysis of the exhaust system. Cost savings for items such as
systems for chemical specic releases, low NOx units for combus- shorter stacks and smaller exhaust fans, in addition to the antion equipment such as boilers and emergency generators, and nual energy savings, can easily add up to the cost required to
oxidizing lters or catalytic converters for emergency generators. conduct the analysistypically $10,000 to $40,000 depending
Reducing the emissions results in a lower dispersion requirement on complexity of the design and analysis required.
for the exhaust system. For a given stack height, this technique
saves energy because less plume rise (i.e., volume ow/exit Conclusions
velocity) is required than for a full-emission exhaust.
An accurate assessment of exhaust dispersion can be used to
Integrated Control Systems. Figure 4 illustrates this concept produce exhaust/intake designs optimized for energy consumpschematically. In this type of system, a dispersion analysis is tion. Key factors affecting exhaust system energy consumption
conducted (typically through use of wind tunnel modeling to can be identied, including 1) the design and operation of the
ensure the most accurate results) to dene the relationship building; 2) the environment surrounding the building; and 3)
among wind direction, wind speed, and the minimum exhaust the local meteorology.
design parameters required to maintain acceptable air quality.
Exhaust systems can and should be designed and operated to
An algorithm for an automatic building control system, using optimize energy requirements. This may be achieved by approJuly 2005
ASHRAE Journal
21
$16
$14
$12
$10
$8
$6
$4
$2
$0
2,862 fpm, 15 ft
1,916 fpm, 20 ft
Difference
priately sizing equipment and stack heights, using simple control techniques such as staged exhaust fan operation, or through
complex control with integrated weather information.
References
3. Petersen, R.L., B.C. Cochran, and J.J. Carter. 2002. Specifying exhaust
and intake systems. ASHRAE Journal 44(8):30 35.
4. Petersen, R.L., J.J. Carter and B.C. Cochran. Best PracticesModeling Exhaust Dispersion for Specifying Acceptable Exhaust/Intake Designs.
Currently in review. Labs for the 21st Century (EPA/DOE sponsors). www.
labs21century.gov.
5. ACGIH. 2004. Guide to Occupational Exposure Values. American
Conference of Governmental Industrial Hygienists.
6. ANSI/AIHA Standard Z9.5-2003, American National Standard: Laboratory Ventilation. American Industrial Hygiene Association.
22
ASHRAE Journal
ashrae.org
July 2005