Professional Documents
Culture Documents
K Kauhaniemi, L Knmpnlained
University of Vaasa, Finland, *VTT Technical Research Centre of Finland, Finland
INTRODUCTION
Traditionally distribution networks have been designed
to operate radially so that the power flows from upper
voltage levels down-to customers situated along the
radial feeders. This has enabled also quite
straightforward protection concept. Especially when
applying overcurrent protection it bas been possible to
assume that the fault current can have only one
direction. This is not always true if there are distributed
generation (DG) units in the network. As the share of
distributed generation increases, distribution networks
are becoming more like transmission networks where
generation and load nodes are mixed, and more complex
protection system design is unavoidable.
Basic Theory
Theoretically the problem can be explained as follows.
A situation, where a production unit is connected in a
medium voltage (MV) feeder close to a primary
substation, is studied. When a fault occurs at the end of
the feeder the fault current consists of contributions both
from the grid (I,) and from the generator (I,) as shown
316
I1
ZL
Fault
Figure 1. Short-circuit fault in MV network and the
corresponding single phase Thtvenin equivalent circuit.
Lets assume that the feeder relay sees a current Ik when
there is no production unit. For the ratio between the
feeder relay current 1, in the situation shown in Figure I
and the current 1, the following formula can he derived
0 0
1 2 k m o 2 0 km
0.5 I
Figure 2 presents the impact of the coefficients a and b
on the ratio l,llk.In all practical cases the impact is such
that the ratio is less than one, which means that the
contribution from the generator reduces the current seen
by the feeder relay. We can also conclude that the
impact of the production unit increases with the size of
the unit (larger unit 3 lower coefficient a ) and with the
length of the line section between the production unit
and the fault (larger coefficient b).
If the production unit is not located at the beginning of
the feeder but along the feeder, Figure 1 can be changed
so that the impedance of the feeder, ZL, is divided into
two parts,
, , ,Z
ja Zlend. When Z,,
is combined with
Z,: Z, = Z,+ Z
,
,
, we can write Z, = aZ, and ZL.,~
= bZ, and repeat the procedure above to find out the
ratio of the feeder relay currents.
* 24 km
I
Ik
Current
(W
12
15
18
21
t /Time (s)
317
FALSE TRIPPINGS
The basic principle of false tripping is shown in Figure
4. The short-circuit fault occurs on feeder 2, but also
feeder 1 is tripped because of overcunent fed by the DG
unit. False tripping (sympathetic tripping) is typically
caused by synchronous generators, which are capable of
feeding sustained short-circuit current.
LOSS-OF-MAINS PROTECTION
4
Figure 4. Principle of false tripping.
False tripping of healthy feeder was verified by
simulations with a diesel power plant model. Figure 5
presents an example, where a 3-phase short-circuit fault
on adjacent feeder causes false tripping of feeder 1,
because the diesel power plant on feeder 1 feeds shortcircuit current to the fault.
x Feeder 1 0 Feeder 2
4.2 I
HI, if2
Current
t / Time
(s)
318
AUTORECLOSING
In overhead medium voltage networks, automatic
reclosing is a very effective mean to clear faults. E.g. in
Finland, ca. 80% of faults can be cleared with highspeed autoreclosing and 15% with time-delayed
autoreclosing. The impact of autoreclosing is based on
extinction of arc during the dead time of the reclosing
sequence. In the Nordic countries, dead time is typically
only 0.3 s.
Distributed generation seems to be rather incompatible
with current reclosing practices as noted, e.g., in Dugan
and McDermott (6). In suitable conditions DG may
prevent the arc extinction and the momentary fault
becomes permanent. During the dead time of the
reclosing sequence the generators in the network usually
tend to drift away from the synchronism with respect to
the grid. Thus the reconnection made without any
synchronization, which is the usual way, may cause
serious damages to the generators, as well as high
currents and voltages in the neighboring network.
Simulation studies have confirmed the high risk of outof-phase reclosing. As a conclusion to this it can be
stated that rapid and reliable loss-of-mains protection is
needed. DG units must be disconnected very fast during
the dead time of autoreclosing sequence.
REFERENCES
1. Brahma, S.M., Girgis, A.A., 2002, IEEE PES Winter
5. D E W , 1995, Relaebeskvttelse
ved decentrale
produktionsanlaeg
med
synkrongeneratorer.
Teknisk rapport 293,2. udgave
CONCLUSIONS
6. Dugan, R.C., McDermott, T.E., 2002, IEEE Ind.
Appl. Mag., MadApr. 2002, 19 - 25
According to the simulation studies proper coordination
of the protection of network and DG units is important
in order to avoid false tripping. In certain cases also
directional protection is necessary to guarantee
selectivity. DG units that are capable of providing large
short-circuit current may prevent the operation of feeder
relays. On the other hand, overcurrent relays cannot be
applied with inverter based DG units that do not feed
any significant short-circuit current.