User Manual: Alc700 Series
User Manual: Alc700 Series
USER MANUAL
Smartgen Technology
Chinese trademark
English trademark
Version
1.0
1.1
Contents
Original release
Modify some functions.
CONTENTS
1 OVERVIEW ..................................................................................................... 5
2 MODULES COMPARISON ............................................................................. 6
3 PERFORMANCE AND CHARACTERISTICS ................................................ 7
4 SPECIFICATION ............................................................................................. 9
5 OPERATION ................................................................................................. 10
5.1
PUSHBUTTONS ....................................................................................................... 10
5.2
5.3
5.4
5.5
5.6
5.7
5.8
6 PROTECTIONS............................................................................................. 25
6.1
6.2
SHUTDOWN ALARMS.............................................................................................. 27
6.3
8.2
8.3
8.4
8.5
8.6
8.7
8.8
8.9
8.10
2013-12-06
Version 1.1
Page 3 of 54
8.12
8.13
SUNRISE/SET SET................................................................................................... 45
13.2
13.3
13.4
AC INPUT .................................................................................................................. 52
13.5
13.6
2013-12-06
Version 1.1
Page 4 of 54
1 OVERVIEW
ALC700 series controllers are used for automation and monitor control systems of single light
tower unit to achieve scheduled start/stop, sunrise and sunset start/stop, SMS message
remote start/stop as well as start/stop genset via remote input port.
ALC700 series controllers can be used for turning on and off the flashlights of the light tower in
proper order and is compatible with both AC and DC light tower sets. The modules are digital,
smart and networked and enjoy precise data measurement, alarm protection as well as remote
control, remote measuring and remote communication functions.
ALC700 series controllers adopt micro-processor technology and combine automation control
function with flashlights control function into one product. They have LCD display, selectable
Chinese/English languages interface, modular design, compact structure and simple
connections. They can be widely used in all types of automatic light tower set with compact
structure, advanced circuits, and high reliability.
2013-12-06
Version 1.1
Page 5 of 54
2 MODULES COMPARISON
Items
Total Number of
Controlled Light Tower
DC Detection
AC Detection
Digital Input
Relay Output
Scheduled Start
Auto SMS Mode
Auto SMS Sunrise/Sunset
Mode
Remote Start
Event log
USB
RS485
High-precision Clock
ALC704
ALC708
Yes
Yes
8
10
Yes
No
Yes
Yes
12
14
Yes
Yes
No
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
NOTE:
The user manual takes ALC708 as its template while ALC704 has relatively simple features.
You can get all information about ALC704 just reference this document.
2013-12-06
Version 1.1
Page 6 of 54
Based
on microprocessor, fitted with LCD screen with graphic icons and backlight,
Real-time
sunrise and sunset start/stop light tower set; moreover, scheduled start time, running
duration time, sunrise time and sunset time can be set by users as their wish.
SMS message function (GSM modem must be fitted). When failure occurs, controller will
send short messages automatically to max. 5 telephone numbers. Besides, users can
remote start/stop light tower set via SMS message.
Remote start function. Set arbitrary input port as Remote Start Input and controller enters
into remote start mode, then users can remote start/stop light tower set by remote
close/open input port.
Manual start/stop control of light tower set and manual on/off control of flashlight.
Standard RS485 communication port enables remote control, remote measuring,
and
Standard USB communication port makes it easier to communicate with PC and faster to
be programmed.
2013-12-06
Version 1.1
Page 7 of 54
Accumulative total run time and total electric energy functions make convenient for users
to regular maintain and survey fuel consumption;
Scheduled start time, SMS telephone number and various delays can be set on the spot
and also comes with password protection in case of laypeople misoperation.
ALC708 controller can control up to 8 flashlights and the feedback indicator were be fitted
on the panel. In addition, the turn on interval time between two lights can be set by users.
99 pieces of event logs can be circularly stored and inquired on the spot; also can be print
or be inquired via PC.
More kinds of curves of temperature, oil pressure, fuel level can be used directly and users
can select User Configured sensor curves for unknown engine sensor
Widely
environment;
Modular
installation;
2013-12-06
Version 1.1
Page 8 of 54
4 SPECIFICATION
Parameter
Working Voltage
Overall Consumption
Voltage Input:
3 Phase 4 Wire
3 Phase 3 Wire
Single Phase 2 Wire
2 Phase 3 Wire
DC
Alternator Frequency
Speed Sensor Voltage
Speed Sensor Frequency
Start Relay Output
Fuel Relay Output
Configurable Relay Output 1
Configurable Relay Output 2
Configurable Relay Output 3
Configurable Relay Output 4
Light Control Relay Output
1~8
Case Dimensions
Panel Cutout
CT Secondary Current
DC Current Input
Working Conditions
Storage Conditions
Protection Level
Insulation Intensity
Weight
Details
DC8. 0V to 35. 0V, uninterruptible power supply
<5W (Standby mode: 2W)
AC 20V - 360V (ph-N)
AC 30V - 600V (ph-ph)
AC 20V - 360V (ph-N)
AC 20V - 360V (ph-N)
DC 0V - 75V (ph-N)
50Hz/60Hz
1. 0 V to 24 V (RMS)
Maximum 10,000 Hz
8A DC28V power supply output
8A DC28V power supply output
8A DC28V power supply output
8A DC28V power supply output
8A DC28V power supply output
8A AC250V passive output
8A AC250V passive output
197 mm x 152 mm x 47 mm
186mm x 141mm
Rated: 5A
Hall sensors secondary side current: 4~20mA
Temperature: (-25~+70)C
Humidity: (20~93)%RH
Temperature:(-25~+70)C
IP55 Gasket
Apply AC2.2kV voltage between high voltage terminal and
low voltage terminal;
The leakage current is not more than 3mA within 1min.
0.71kg
2013-12-06
Version 1.1
Page 9 of 54
5 OPERATION
5.1
PUSHBUTTONS
Stop running light tower set;
Stop/Reset
Manual Mode
Auto Mode
Mute
Flashlight
Start
Light Off
Light On
MenuConfirm
Down/Config. -
1) Screen scroll;
2) Down cursor and decrease value in setting menu.
UpConfig. +
1) Screen scroll;
2) Up cursor and increase value in setting menu.
2013-12-06
Version 1.1
Page 10 of 54
5.2
LCD DISPLAY
U = 220V
F = 50.0Hz
MANUAL MODE
MANUAL START
CURRENT TIME
12:05:18
GENERATOR NORMAL RUNNING
GENERATOR
UL-L 381 381 381 V
UL-N 220 220 220 V
F =50.0 Hz 1500RPM
FUEL LEVEL
ENGINE TEMP.
OIL PRESSURE
16.0 PSI
80 %
80176
110 KPa
1.10Bar
Light On
Light Off
Press
button
The
screen
display
generator
line
voltage(L1-L2,
L2-L3,
L3-L1),
phase
voltage(L1L2L3), frequency and engine
speed.
DC light tower set without this page.
Press
button
The screen display generator fuel level,
engine temperature, oil pressure, flexible
sensor information.
There is no sensor information when flexible
sensor select Not used or Digital closed or
Digital open.
The screen display ++++ when sensor is
open circuit.
PLANT BATTERY
24.1 V
D+ VOLTAGE
18.1 V
Engine Speed 1500 RPM
05-06-16 (4) 08:16:01
Press
button
The screen display battery voltage, charger
voltage, engine speed and current time (the
number in the parentheses is week
information).
GENERATOR
STARTS
88888 times
HOURS RUN 009999:05:30
ENERGY
0003561.6 kWh
Press
button
The screen display accumulated start times,
accumulated energy, accumulated run time
(HH: MM: SS).
2013-12-06
Version 1.1
Page 11 of 54
NOTE:
Pressing
Press
button
The screen display load current, total active
power, total apparent power, total reactive
power and power factor
The screen display voltage, current and
power when DC current is fitted.
2013-12-06
Version 1.1
Page 12 of 54
5.3
SCHEDULED START/STOP
A. Press
its indicator light on, and controller enters Auto mode. Meanwhile, the panel
or
and
to select 01 Timer
Fig 1
Fig 2
Fig 3
B. When there are 10s left from start time, audible alarm relay is active (if configured). When
start time is up and start remaining time is more than 0s, light tower set begin cranking and
flashlight is twinkling (if configured). Stop delay time will be displayed on the first line
(Picture 4).
Fig 4
STOP DELAY
START TIME
CURRENT TIME
CRANKING
10:10:59
16:28:00
16:28:00
5s
STOP DELAY
START TIME
CURRENT TIME
2# LIGHT ON
10:07:42
16:28:00
16:32:18
09s
2013-12-06
Version 1.1
Page 13 of 54
STOP DELAY
09:06:02
START TIME
16:28:00
CURRENT TIME
16:33:58
GENERATOR NORMAL RUNNING
needed) then 1#8# lights will off in proper order and the extinguishing interval delay
can be set as 1s300s. The light tower set begin stopping when all the lights off. (Picture
7,8)
Fig 7
Fig 8
STOP DELAY
START TIME
CURRENT TIME
7# LIGHT OFF
00:00:00
16:28:00
23:32:18
09s
16:28:00
23:33:58
29s
NOTE: The auto timer mode will be canceled automatically when select other auto start
mode
2013-12-06
Version 1.1
Page 14 of 54
5.4
SUNRISE/SUNSET MODE
If the city information havent been set when select this mode, users should connect PC and
ALC700 controller using USB or RS485 communication line and set the city information first.
The procedures as following:
Open test softwareedit configurationset sunrise/sunsetselect city/user-defined city
(longitude, latitude and time zone) download the configuration
A. Press
its indicator light on, and controller enters Auto mode. Meanwhile, the panel
or
and
to select 03 Sunrise/Sunset
and
to select 01
Fig 1
Fig 2
SUNRISE/SET ACTION
01 SUNRISE/SUNSET START
02 SUNRISE/SUNSET STOP
Fig 3
SUNRISE/SET ACTION
START TIME
17:26:00
CURRENT TIME
12:05:18
GENERATOR AT REST
B. When there are 10s left from start time (controllers current time can be set via utility
computer software), audible alarm relay is active (if configured). When start time is up, light
tower set begin cranking and flashlight is twinkling (if configured). Stop delay will be
displayed on the first line (Picture 4).
Fig 4
STOP DELAY
07:25:00
START TIME
17:26:00
CURRENT TIME
17:26:02
CRANKING
5s
2013-12-06
Version 1.1
Page 15 of 54
STOP DELAY
START TIME
CURRENT TIME
2# OUTPUT DELAY
07:25:00
17:26:00
17:26:15
09s
Fig 6
STOP DELAY
07:25:00
START TIME
17:26:00
CURRENT TIME
17:27:20
GENERATOR NORMAL RUNNING
D. When Current Time is 07:25:00(controllers current time can be set via upper computer
software), then 1#8# lights will off in proper order and the extinguishing interval delay
can be set as 1s300s. The light tower set begin stopping when all the lights off. (Picture
7,8)
Fig 7
STOP DELAY
START TIME
CURRENT TIME
7# OFF DELAY
Fig 8
SUNRISE/SET ACTION
START TIME
17:26:00
CURRENT TIME
07:27:00
COOLING TIME
29s
07:25:00
17:26:00
07:25:00
09s
NOTE: The Sunrise/Sunset mode will be canceled automatically when select other auto
start mode
2013-12-06
Version 1.1
Page 16 of 54
5.5
A. Press
its indicator light on, and controller enters Auto mode. Meanwhile, the panel
or
and
Fig 1
Fig 2
B. When SMS message module receives the start command, light tower set begin cranking
and flashlight is twinkling (if configured). Stop delay will be displayed twinklingly on the first
line of the second screen. (Picture 3).
Fig 3
C. If generator voltage and frequency has reached on-load requirements (Voltage on-load
voltage and frequency on-load frequency), all the lights will illuminate in proper order and
the illumination interval delay is 2s (can be set as 1~300s). (Picture 4,5)
Fig 4
Fig 5
2013-12-06
Version 1.1
Page 17 of 54
Fig 7
NOTE: The auto SMS mode will be canceled automatically when select other auto start
mode
2013-12-06
Version 1.1
Page 18 of 54
5.6
A. Press
its indicator light on, and controller enters Auto mode. Meanwhile, the panel
or
and
Fig 2
B. When controller receives start order (SMS SUNRISE/SET START) correctly (Picture 3), it
will reply message: SMS SUNRISE/SET START OK. The telephone number which sends
start order message should be set via test software and downloaded into controller.
Fig 3
SUNRISE/SET ACTION
START TIME
17:26:00
CURRENT TIME
12:05:18
GENERATOR AT REST
C. When there are 10s left from start time (controllers current time can be set via utility
computer software), audible alarm relay is active (if configured). When start time is up, light
tower set begin cranking and flashlight is twinkling (if configured). Stop delay will be
displayed on the first line of the second screen (Picture 4).
Fig 4
STOP TIME
START TIME
CURRENT TIME
CRANKING
07:25:00
17:26:00
16:28:00
5s
2013-12-06
Version 1.1
Page 19 of 54
Fig 6
STOP TIME
07:25:00
START TIME
17:26:00
CURRENT TIME
17:26:00
2# OUTPUT DELAY
09s
STOP TIME
07:25:00
START TIME
17:26:00
CURRENT TIME
17:27:20
GENERATOR NORMAL RUNNING
E. When Current Time is 07:25:00(controllers current time can be set via utility computer
software), then 1#8# lights will off in proper order and the extinguishing interval delay
can be set as 1s300s. The light tower set begin stopping when all the lights off. (Picture
7,8)
Fig 7
STOP TIME
START TIME
CURRENT TIME
7# OFF DELAY
07:25:00
17:26:00
07:25:00
09s
Fig 8
SUNRISE/SET ACTION
START TIME
17:26:00
CURRENT TIME
07:27:00
COOLING TIME
29s
NOTE: The auto SMS sunrise/sunset mode will be canceled automatically when select
other auto start mode
2013-12-06
Version 1.1
Page 20 of 54
5.7
enters Auto Mode. Meanwhile, the panel display Auto Mode Select (Picture 1); Press
and
Fig 1
Fig 2
or
B. When remote start input port is active (input port can be set via utility computer software),
remote start delay begins and audible alarm relay is active (if configured). When remote
start delay is over and remote start signal is active, light tower set begin cranking and
flashlight is twinkling (if configured). (Picture 3, 4).
Fig 3
Fig 4
C. If generator voltage and frequency has reached on-load requirements (Voltage on-load
voltage and frequency on-load frequency), all the lights will illuminate in proper order and
the illumination interval delay is 2s (can be set as 1~300s). (Picture 5)
Fig 5
2013-12-06
Version 1.1
Page 21 of 54
Fig 7
Fig 8
2013-12-06
Version 1.1
Page 22 of 54
5.8
MANUAL START/STOP
A. Press
its indicator light on, and controller enters Manual Mode (Picture 1). Press
MANUAL MODE
WAIT MANUAL START
CURRENT TIME
12:05:18
GENERATOR AT REST
Fig 2
MANUAL MODE
MANUAL START
CURRENT TIME
CRANKING
B. Press
12:05:18
5s
, the light relay will activate (if configured) while deactivate by pressing
again.
C. When warming up delay is over, in addition, generator voltage and frequency has reached
on-load requirements(Voltageon-load voltage and frequencyon-load frequency), 1#8#
lights will illuminate in proper order by pressing
pressing
Fig 3
CURRENT TIME
16:32:18
GENERATOR NORMAL
RUNNING
Fig 4
MANUAL MODE
MANUAL START
CURRENT TIME
16:33:58
1# OFF
2013-12-06
Version 1.1
Page 23 of 54
, 1#8# lights will off in proper order and the extinguishing interval delay can
be set as 1s300s. The light tower set begin stopping when all the lights off. Press
again during this procedure will lead to all lights off at the same time and ETS status of
controller (Picture 5,6)
Fig 5
MANUAL MODE
MANUAL STOP
CURRENT TIME
23:32:18
8# OFF
Fig 6
MANUAL MODE
MANUAL STOP
CURRENT TIME
COOLING
23:33:58
29s
2013-12-06
Version 1.1
Page 24 of 54
6 PROTECTIONS
6.1
WARNING ALARMS
Warnings are not shutdown alarms and do not affect the operation of the genset. Alarm
information will be displayed on the LCD.
Warning alarms types are as follows:
No.
Type
Description
When controller detects the temperature is higher than the
1
High Temp. Warn
set value, it will send warning signal and the corresponding
alarm information will be displayed on the LCD.
When controller detects the oil pressure is lower than the set
2
Low OP Warn
value, it will send warning signal and the corresponding
alarm information will be displayed on the LCD.
When controller detects the speed is higher than the set
3
Over Speed
value, it will send warning signal and the corresponding
alarm information will be displayed on the LCD.
When controller detects the speed is lower than the set
4
Under Speed
value, it will send warning signal and the corresponding
alarm information will be displayed on the LCD.
When controller detects the speed is 0, it will send warning
5
Loss of Speed Signal signal and the corresponding alarm information will be
displayed on the LCD.
When controller detects the generator frequency is higher
than the set value, it will send warning signal and the
6
Over Frequency
corresponding alarm information will be displayed on the
LCD.
When controller detects the generator frequency is lower
than the set value, it will send warning signal and the
7
Under Frequency
corresponding alarm information will be displayed on the
LCD.
When controller detects the generator voltage is higher than
the set value, it will send warning signal and the
8
Over Voltage
corresponding alarm information will be displayed on the
LCD.
When controller detects the generator voltage is lower than
the set value, it will send warning signal and the
9
Under Voltage
corresponding alarm information will be displayed on the
LCD.
When controller detects the generator current is higher than
the set value, it will send warning signal and the
10
Over Current
corresponding alarm information will be displayed on the
LCD.
ALC700 Series Light Tower Set Controller
2013-12-06
Version 1.1
Page 25 of 54
11
12
13
14
15
17
18
16
NOTE: The warning types of Aux. input are active only when they are configured by
users.
2013-12-06
Version 1.1
Page 26 of 54
6.2
SHUTDOWN ALARMS
When controller detects shutdown alarm, it will send signal to turn off #1#8 lights and shuts
down generator.
Shutdown alarms as following:
No.
Type
Description
When controller detects emergency stop signal, it will send a
1
Emergency Stop
shutdown signal and the corresponding alarm information will
be displayed on the LCD.
When controller detects the temperature is higher than the set
High Temp.
2
value, it will send a shutdown signal and the corresponding
Shutdown
alarm information will be displayed on the LCD.
When controller detects the oil pressure is lower than the set
3
Low OP Shutdown value, it will send a shutdown signal and the corresponding
alarm information will be displayed on the LCD.
When controller detects the generator speed is higher than the
4
Over Speed
set value, it will send a shutdown signal and the corresponding
alarm information will be displayed on the LCD.
When controller detects the generator speed is lower than the
5
Under Speed
set value, it will send a shutdown signal and the corresponding
alarm information will be displayed on the LCD.
When controller detects the generator speed is 0, it will send a
Loss of Speed
6
shutdown signal and the corresponding alarm information will
Signal
be displayed on the LCD.
When controller detects the generator frequency is higher than
7
Over Frequency
the set value, it will send a shutdown signal and the
corresponding alarm information will be displayed on the LCD.
When controller detects the generator frequency is lower than
8
Under Frequency
the set value, it will send a shutdown signal and the
corresponding alarm information will be displayed on the LCD.
When controller detects the generator voltage is higher than
9
Over Voltage
the set value, it will send a shutdown signal and the
corresponding alarm information will be displayed on the LCD.
When controller detects the generator voltage is lower than the
10
Under Voltage
set value, it will send a shutdown signal and the corresponding
alarm information will be displayed on the LCD.
When controller detects the current is higher than the set
11
Over Current
value, it will send a shutdown signal and the corresponding
alarm information will be displayed on the LCD.
If genset start failure within setting of start times, it will send a
12
Fail To Start
shutdown signal and the corresponding alarm information will
be displayed on the LCD.
2013-12-06
Version 1.1
Page 27 of 54
Type
13
Pressure Sensor
Open
14
Temp. Sensor
Open
15
16
Flexible Sensor
Open
17
Flexible Sensor
High
18
Flexible Sensor
Low
19
Description
When controller detects the oil pressure sensor is open circuit,
it will send shutdown signal and the corresponding alarm
information will be displayed on the LCD.
When controller detects the temperature sensor is open circuit,
it will send a shutdown signal and the corresponding alarm
information will be displayed on the LCD.
When controller detects the fuel lever is lower than the set
value, it will send shutdown signal and the corresponding
alarm information will be displayed on the LCD.
When controller detects the sensor is open circuit, it will send a
shutdown signal and the corresponding alarm information will
be displayed on the LCD. If the sensor name is configured by
users as xxx, then xxx open will be displayed on the LCD.
When controller detects the sensor value is higher than the
maximum set value, it will send shutdown signal and the
corresponding alarm information will be displayed on the LCD.
If the sensor name is configured by users as xxx, then xxx
high will be displayed on the LCD.
When controller detects the sensor value is lower than the
minimum set value, it will send shutdown signal and the
corresponding alarm information will be displayed on the LCD.
If the sensor name is configured by users as xxx, then xxx
low will be displayed on the LCD.
When the controller detects auxiliary input ports 1-4 shutdown
alarms, it will send shutdown alarm signal and the
corresponding alarm information will be displayed on the LCD.
If the input port name is configured by users as xxx, then xxx
shutdown will be displayed on the LCD.
NOTE: The shutdown alarm types of Aux. input are active only when they are configured
by users.
2013-12-06
Version 1.1
Page 28 of 54
6.3
When the controller detects trip and stop signal, it will send signal to turn off #1#8 lights and
then generator is cooling down and stopped.
Shutdown alarms as following:
NO.
Type
Detection range
Over
Current
Always active
Aux. input
1-4
User-defined
Description
When controller detects the current is higher than
the set value, it will send a trip and stop signal and
the corresponding alarm information will be
displayed on the LCD.
When the controller detects auxiliary input ports 1-4
trip alarms, it will send a trip and stop alarm signal
and the corresponding alarm information will be
displayed on the LCD. If the input port name is
configured by users as xxx, then xxx trip and stop
will be displayed on the LCD.
NOTE: The trip and stop alarm types of Aux. input are active only when they are
configured by users.
2013-12-06
Version 1.1
Page 29 of 54
7 WIRING CONNECTION
ALC700 controllers rear as following:
Functions
Cable Size
DC input B-
2.5 mm2
DC input B+
2.5 mm2
Emergency stop
1.5 mm2
Fuel relay
1.5 mm2
Start Relay
1.5 mm2
6
7
8
Aux. output 1
Aux. output 2
Aux. output 3
1.5 mm2
1.5 mm2
1.5 mm2
1.0 mm2
9
10
11
12
13
Charger (D+)
Aux. output 4
1#-4# COM
1# Light Output
1.5 mm2
1.5 mm2
2.5 mm2
1.5 mm2
Remark
Connected with negative of starter
battery.
Connected with positive of starter battery.
20A fuse is recommended.
Connected with DC voltage via
emergency stop button. Max. 30A fuse is
recommended.
DC voltage is supplied by 3 point, rated
8A.
DC voltage is supplied by 3 point, rated
8A.
B+ outputrated 8A.
Connected with chargers D+ (WL)
terminals. Ground connection is not
allowed.
Normally open voltage free outputs, rated
8A.
Light control output port, rated 8A.
2013-12-06
Version 1.1
Page 30 of 54
Functions
2# Light Output
3# Light Output
4# Light Output
Cable Size
1.5 mm2
1.5 mm2
1.5 mm2
17
5#-8# COM
2.5 mm2
18
5# Light Output
1.5 mm2
19
20
21
22
23
24
6# Light Output
7# Light Output
8# Light Output
RS485 SCR
RS485 A
RS485 B
Light tower set
A-phase voltage
sensing input
Light tower set
B-phase voltage
sensing input
Light tower set
C-phase voltage
sensing input
Light tower set
N-wire input
1.5 mm2
1.5 mm2
1.5 mm2
0.5 mm2
0.5 mm2
0.5 mm2
29
Remark
1.0 mm2
1.0 mm2
1.0 mm2
1.0 mm2
Engine Temp.
1.0 mm2
30
Oil pressure
1.0 mm2
31
Fuel level
1.0 mm2
32
Aux. Sensor
1.0 mm2
33
Sensor COM
1.0 mm2
34
MP+
1.0 mm2
25
26
27
28
35
MP-
36
37
38
39
Aux. input 1
Aux. input 2
Aux. input 3
Aux. input 4
40
1# Light Input
41
2# Light Input
1.0 mm2
1.0 mm2
1.0 mm2
1.0 mm2
1.0 mm2
1.0 mm2
1.0 mm2
2013-12-06
Version 1.1
Page 31 of 54
Functions
3# Light Input
4# Light Input
Cable Size
1.0 mm2
1.0 mm2
1.0 mm2
Remark
B- is active.
3# light control feedback input; connect
B- is active.
4# light control feedback input; connect
B- is active.
5# light control feedback input; connect
B- is active.
6# light control feedback input; connect
B- is active.
7# light control feedback input; connect
B- is active.
8# light control feedback input; connect
B- is active.
Connect to the output port of Hall DC
4-20mA sensor(DC Generator current)
Connect to the voltage output port of DC
Generator
Externally connected to secondary coil of
current transformer (rated 5A).
Externally connected to secondary coil of
current transformer (rated 5A).
Externally connected to secondary coil of
current transformer (rated 5A).
Current transformers common port
Connected with negative of starter
battery.
44
5# Light Input
45
6# Light Input
46
7# Light Input
47
8# Light Input
48
49
50
51
DC Current DC Current +
DC Voltage DC Voltage +
CT A-phase
sensing input
CT B-phase
sensing input
CT C-phase
sensing input
1.0 mm2
1.0 mm2
1.0 mm2
1.0 mm2
55
CT COM
2.5 mm2
56
57
58
Controller GND
Controller RXD
Controller TXD
0.5 mm2
0.5 mm2
0.5 mm2
USB
USB Port
0.5 mm2
Communicate
software of PC.
52
53
54
1.0 mm2
1.0 mm2
1.0 mm2
2.5 mm2
2.5 mm2
2.5 mm2
2013-12-06
with
Version 1.1
communication
Page 32 of 54
Form 1
Parameters
DET Range
Default
0-3
Daily
Weekly
02 START DAY
Monthly
Custom Week
Start Time
03 Timer Start
Run Duration
04
CUSTOM Start Time
SUNDAY
Run Duration
05
CUSTOM Start Time
MONDAY
Run Duration
06
CUSTOM Start Time
TUESDAY
Run Duration
07
CUSTOM Start Time
WEDNESDAY
Run Duration
08
CUSTOM Start Time
THURSDAY
Run Duration
09
CUSTOM Start Time
FRIDAY
Run Duration
10
CUSTOM Start Time
SATURDAY
Run Duration
11 Telephone Number 1
12 Telephone Number 2
Null
Monday ~Sunday
1-31
Null
00:00-23:59
00:00-23:59
00:00-23:59
00:00-23:59
00:00-23:59
00:00-23:59
00:00-23:59
00:00-23:59
00:00-23:59
00:00-23:59
00:00-23:59
00:00-23:59
00:00-23:59
00:00-23:59
00:00-23:59
00:00-23:59
0
18:30
12:00
18:30
12:00
18:30
12:00
18:30
12:00
18:30
12:00
18:30
12:00
18:30
12:00
18:30
12:00
maximum 16 bits
13 Telephone Number 3
14 Language
(0-1)
(-60)-(+60)min
(-60)-(+60)min
2013-12-06
Remarks
0 Daily
1 Weekly
2 Monthly
3 Custom Week
Version 1.1
Page 33 of 54
Parameters
Start Delay
Pre-heat Delay
Cranking Time
Crank Rest Time
Safety On Delay
Start Idle Time
Warming Up Time
Cooling Time
Stop Idle Time
ETS Solenoid Hold
Fail to Stop Delay
Over Speed Time
Light Output Interval Time
Total Number of Controlled
Light Tower
Audible Alarm Output Delay
AC Generator Select
Poles
Magnetic Pickup
AC System
Fast Onload
Start Attempts
PT
Fuel Pump Control
Engine Temperature Sensor
Oil Pressure Sensor
Fuel Level Sensor
Flexible Sensor
Low Oil Pressure Shutdown
High Temperature
Shutdown
Low Fuel Level Warn
Input Port 1
Input Port 2
Input Port 3
Default
5s
0s
5s
10s
10s
10s
30s
60s
10s
20s
30s
2s
2s
8
30s
Yes
4
Yes
3 Phase 4 Wire
No
3
No
No
VDO 120 degrees C
VDO 10 bar
VDO ohm range (10-180)
Not Used
103Kpa
95C
10%
Remote start input
Content: High Temperature;
Active Type: Closed to active;
Active Action: Shutdown;
Arming: From safety on
Content: Low Fuel Level;
Active Type: Closed to active;
Active Action: Shutdown;
Arming: From safety on
2013-12-06
Version 1.1
Page 34 of 54
Input Port 4
Output Port 1
Output Port 2
Output Port 3
Output Port 4
Input Port 1 Custom Delay
Input Port 2 Custom Delay
Input Port 3 Custom Delay
Input Port 4 Custom Delay
Generator Under Frequency
Warn
Generator Under Frequency
Shut
Generator Onload
Frequency
Generator Over Frequency
Warn
Generator Over Frequency
Return
Generator Over Frequency
Shut
Generator Under Voltage
Warn
Generator Under Voltage
Shut
Generator Onload Voltage
Generator Over Voltage
Warn
Generator Over Voltage
Return
Generator Over Voltage
Shut
Over Current Percentage
Delay Ratio
Over Current Action
Crank Disconnect Generator
Frequency
Crank Disconnect Engine
Speed
Crank Disconnect Oil
Pressure
Oil Pressure Detection
During Cranking
2013-12-06
Version 1.1
Page 35 of 54
No
80%
40min
Feedback input
2013-12-06
Version 1.1
Page 36 of 54
8.2
No.
0
Description
Not Used
Air Flap
Audible Alarm
3
4
5
6
7
Start Relay
Fuel Relay
10
11
12
13
14
15
16
17
18
19
20
Common Alarm
21
22
23
24
25
26
27
28
29
30
2013-12-06
Version 1.1
Page 37 of 54
Type
Aux Input 4 Active
Reserved
Reserved
Emergency Stop
ETS Control
Failed To Start
37
38
Generator Available
39
40
41
42
43
44
45
46
47
Louver Control
48
49
54
Flexible
Sensor
Low
Shutdown
Flexible Sensor Low Warn
Flexible Sensor High Warn
Flexible
Sensor
High
Shutdown
Flexible Sensor Open
55
Low OP Warn
56
Low OP Shutdown
57
58
59
60
61
62
63
OP Sensor Open
Reserved
Reserved
Reserved
Reserved
Over Current Warn
Over Current Trip
50
51
52
53
Description
Action when input port 4 is active
2013-12-06
Version 1.1
Page 38 of 54
83
84
Type
Description
Over Speed Warn
Action when over speed warns.
Over Speed Shutdown
Action when over speed shutdown alarm.
Preheat (during preheat Action in period of preheat delay to cranking.
timer)
Action in period of preheat delay to the end of cranking
Preheat (until end of crank)
delay.
Preheat (until end of warm Action in period of preheat delay to the end of warming
timer)
up delay.
Preheat (until end of safety Action in period of preheat delay to the end of safety
on)
on delay.
Reserved
Reserved
Auto Mode
Action in Auto mode.
Manual Mode
Action in Manual mode.
Stop Mode
Action in stop mode.
Under Speed Warn
Action when over speed warns.
Under Speed Shutdown
Action when over speed shutdown alarm.
Reserved
Action during cranking---start idle period and stop
Idle/High Speed Control
idle --- fail to stop period.
Oil Pre-supply
Actions in period of cranking to safety on.
Raise Speed
Action in warming up delay.
Output in start period. If there is no generator
Excite Generator
frequency during hi-speed running, output for 2
seconds.
Action between the period from stop idle to failed to
Drop Speed
stop.
Pre-Lubricate
Actions in period of pre-heat to safety on.
Reserved
85
Flashlight Output
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
Press
button, control output.
Action when there are 10s left from start time in auto
86
Audible Alarm
start mode.
Control genset via utility software or remote
87
Remote Control
communication.
88
SMS Power
Control the power supply of GSM modem.
NOTE: The contents of output port 1~4 can be set only via PC software.
2013-12-06
Version 1.1
Page 39 of 54
8.3
No.
8.4
No.
0
1
2
3
Description
Including following functions,
Indication: indicate only, not warning or shutdown.
Warning: warn only, not shutdown.
Shutdown: alarm and shutdown immediately
Users
Configured
Trip and stop: alarm, generator unloads and shutdown after
(See the form below
hi-speed cooling
for more details)
Never: input inactive.
Always: input is active all the time.
From crank: detecting as soon as start.
From safety on: detecting after safety run delay.
Remote Start
Lamp Test
Panel Lock
7
8
9
10
11
12
13
14
15
Description
HIGH WATER TEMP will be displayed on the panel when
the input is active.
Alarm types can be set by users.
Alarm will be displayed on the panel when the input is active.
HIGH OIL TEMP will be displayed on the panel when the
input is active.
HIGH CANOPY TEMP will be displayed on the panel when
the input is active.
LOW WATER LEVEL will be displayed on the panel when
the input is active.
LOW OIL LEVEL will be displayed on the panel when the
input is active.
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
NOTE: The contents of input port 1~4 can be set only via PC software.
2013-12-06
Version 1.1
Page 40 of 54
8.5
No.
SENSOR SELECTION
Items
Temperature
Sensor
Oil pressure
Sensor
Fuel Level
Sensor
Contents
Remark
1 Not used
2 Digital closed
3 Digital open
4 VDO 120 degrees C
5 Datcon high
6 Datcon low
7 SGX 120 degrees C
8 Cummins
9 SGH 120 degrees C
10 Curtis
11 SGD 120 degrees C
12 Pt100
13 User defined
1 Not used
2 Digital closed
3 Digital open
4 VDO 5 bar
5 VDO 10 bar
6 Datcon 5 bar
7 Datcon 10 bar
8 Datcon 7 bar
9 SGX 10 bar
10 CMB812
11 SGH 10 bar
12 Curtis
13 SGD 10 bar
14 User defined
1 Not used
2 Digital closed
3 Digital open
4 VDO Ohm range (10-180)
5 VDO Tube type (90-0)
6 US Ohm range (240-33)
7 GM Ohm range (0-90)
8 GM Ohm range Ohm range (0-30)
9 Ford (73-10)
10 NKZR12/24-1-04 Ohm range (100-0)
11 User defined
2013-12-06
Version 1.1
Page 41 of 54
8.6
SENSORS SETTING
1. When reselect sensors, the sensor curve will be transferred into the standard value. For
example, if temperature sensor is SGX (120C resistor type), its sensor curve is SGX
(120C resistor type); if select the SGD (120C resistor type), the temperature sensor
curve is SGD curve.
2. When there is difference between standard sensor curves and using sensor, user can
adjust it in curve type.
3. When input the sensor curve, X value (resistor) must be input from small to large, otherwise,
mistake occurs.
4. If select sensor type as None, sensor curve is not working.
5. If corresponding sensor has alarm switch only, user must set this sensor as None,
otherwise, maybe there is shutdown or warning.
6. The headmost or backmost values in the vertical coordinates can be set as same as below,
1Pa
1kgf/cm2
1bar
1psi
pa
1
9.8x104
1x105
6.89x103
kgf/cm2
1.02x10 5
1
1.02
7.03x10 2
2013-12-06
bar
1x10 5
0.98
1
6.89x10 2
Version 1.1
psi
1.45x10 4
14.2
14.5
1
Page 42 of 54
8.7
T = 900s(15 minutes)
8.8
No.
0
1
2
3
4
5
6
Contents
Gen frequency (It is DC voltage when fitted with DC generator)
Speed sensor
Speed sensor + Gen frequency
Oil pressure
Oil pressure + Gen frequency
Oil pressure + Speed sensor
Oil pressure + Speed sensor + Gen frequency
2013-12-06
Version 1.1
Page 43 of 54
8.9
Work mode can be set asFeedback input, Control input, Invalid. The control logic is as
following:
System Mode
Light Inputs
Setting
Feedback Input
Manuel Mode
Control Input
Invalid
Feedback Input
Auto Mode
Control Input
Invalid
Feedback Input
Stop Mode
Control Input
Invalid
TFT Light
Status
Light
Input
Status
Light
Input
Status
Relay
Output
Status
Light
Input
Status
Relay
Output
Status
Relay
Output
Status
Light
Input
Status
Invalid
Invalid
Light Relay
Panel Light
Output Status
Switch
Light
Input
Valid
Status
Light
Input
Invalid
Status
Panel Switch
Valid
System Control
Invalid
System Control
Invalid
System Control
Invalid
Invalid
Invalid
Invalid
Invalid
Invalid
Invalid
start time, run duration, scheduled start or scheduled not start function. If the run duration is
set as 00:00, then the unit will not be start.
2013-12-06
Version 1.1
Page 44 of 54
SMS Code
SMS STOP
SMS START
SMS SUNRISE/SET
START
SMS GENSET
SMS ENGINE
SMS OPS
SMS WTP
SMS FLE
Description
Stop mode order; set controller into stop mode; Stop
running light tower set;
ReplySMS STOP OK
Start order; can control light tower set to start;
ReplySMS START OK
Sunrise/sunset mode order
ReplySMS SUNRISE/SET START OK
Set the time of controller;
Set formYY-MM-DD HH:MM:SS
ReplyTIME SET OK YY-MM-DD HH:MM:SS
Inquiry order; inquiry the current status of controller.
ReplyGENSET AT REST or
GENSET IS RUNNING
YY-MM-DD HH:MM:SS
Inquiry all sensors information
Replyall sensors information and the real time
Inquiry oil pressure sensors information
Replyoil pressure
Inquiry temperature sensors information
Replyengine temperature
Inquiry fuel level sensors information
Replyfuel level sensors information
NOTE: Its national and areas cods must be added, e.g. Chinese number should be set as
+8613666666666 or 008613666666666.
NOTEThe SMS orders are active only when GSM modem is enabled. In addition, the
1~3 SMS orders are active only in AUTO DIAL-UP MODE.
NOTEThe controller will send alarm information to preset telephone automatically when
shutdown alarm or trip alarm occur.
2013-12-06
Version 1.1
Page 45 of 54
9 PARAMETERS SETTING
1) Parameters SettingAfter controller power on, press
and
password 0~9; press key to right move the bit, in fourth bit press key to check
password. If password is correct, enter into advanced parameter setting interface,
otherwise, exit directly. (Factory default password is 1234 and users can modify it.)
Press + key and - key to scroll screen; select parameter you want to configure and press
key (the parameter will highlight with black), press+
key or - key to change parameter value, press key to
move the bit, in fourth bit press key to confirm setting
and the set value will be saved into internal FLASH (picture
Parameter Setting
01 Timer Start
Start Time
Duration
18:50
08:30
on the right).
2) Date and Time Setting: After controller power on, press
and , then select 3 Time Calibration, press
again to the Date and Time Setting interface. The first line
is current date and time and the second line is the time
information of users modification. The digital which highlight with black is currently
adaptable for user by pressing + key and - key to increase and decrease the value.
Press key to confirm setting and the bit will right move automatically. Number 5 in the
parenthesis is the week information. It is set by the microprocessor based on current date,
so the user does not need to modify it. (picture on the right)
NOTEPressing
2013-12-06
Version 1.1
Page 46 of 54
10
EVENT LOG
Maximum 99 pieces of event logs can be circularly stored into controller. Shutdown alarms and
real time information will be record but warning alarms. If the alarm records are more than 99
pieces, then the latest record will replace the oldest one.
Press
and , then select 2 Event Log, press again to inquiry the event log (See
and
to exit directly;
2013-12-06
Version 1.1
Page 47 of 54
11
COMMISSIONING
2013-12-06
Version 1.1
Page 48 of 54
12
2013-12-06
Version 1.1
Page 49 of 54
NOTE: Users should select suitable Hall DC sensor according to the output power and
current of the light tower set.
2013-12-06
Version 1.1
Page 50 of 54
13
INSTALLATION
Controller is panel built-in design; it is fixed by clips when installed. The controllers overall
dimensions and cutout dimensions for panel, please refers to as following,
2013-12-06
Version 1.1
Page 51 of 54
13.4 AC INPUT
Current input of ALC700 controller must be connected to outside current transformer. And the
current transformers secondary side current must be 5A. At the same time, the phases of
current transformer and input voltage must correct. Otherwise, the current of collecting and
active power maybe not correct.
NOTE: ICOM port must be connected to negative pole of battery.
WARNING! When there is load current, transformers secondary side prohibit open
circuit.
2013-12-06
Version 1.1
Page 52 of 54
14
FAULT FINDING
Here are the common faults and troubleshooting. If there is any other problem, please feel free
to contact Smartgens service.
Symptoms
Controller no response with
power.
Light tower set shutdown
Possible Solutions
Check starting batteries;
Check controller connection wirings;
Check DC fuse.
Check the water/cylinder temperature is too high or not;
Check the generator AC voltage;
Check DC fuse.
Check emergence stop button is correct or not;
Check whether the starting battery positive be connected with
the emergency stop input;
Check whether the circuit is open.
Check the oil pressure sensor and its connections.