You are on page 1of 27

MAHARASHTRA STATE ELECTRICITY TRANSMISSION CO. LTD.

OFFICE OF THE CHIEF ENGINEER, DESIGN, C & M DEPTT.


' PRAKASHQANGA ', PLOT C-19, E-BLOCK, BANDRA-KURLA COMPLEX,
BANDRA (EAST), MUMBAI - 400051
TEL.: 022 - 26595125 (0), 26595124 (P), FAX: 022 - 26598587
EMAIL: cec.m._(gmahatransco.in, WEBSITE: www.mahatransco.iq
CIN NO. U40109MH2005SGC153646

MSETCL/CO/Proj. & Des./D&E-S2/TKC/Shah Constn./Nimboni (Bhalawani)/

Date:

NoO 98 56

T9/

.2 4 JUL 2015

~s

Shah Construction
Engineers & Contractors,
'PARAG', 286/2, Station Road,
Karad - 415110.
Sub:

Establishment of 132/33kV Substation at Nimboni (Bhalawani), Dist. Solapur on


Turnkey basis against Tender T-13 31 .
Approval of GTP & Drawing of Fire Fighting equipments thereof.

Ref:

1) LOA No. MSETCL/CO/C&M/Contract/TKC-IIl/T-1331 /S/S/Shah/2107, 2108 &


2109 Dtd. 18.02.2012.
2) Your letter No. SECIPL/DA/NIM/23 Dtd.17.07.2015.

Dear Sirs,
We refer to the documents submitted by you vide letter under reference (2) in respect of Fire
Fighting equipments (of Kanadia Fyr Fyter make) for subject project. The same have been
scrutinized and are found to be generally in order and hence approved. One set of the approved
documents as per Annexure 'A' is enclosed. You are requested to furnish the copies of approved
documents to our concerned field offices.
This approval is given without prejudice to the terms. and conditions of the Turnkey contract
and does not absolve you of your responsibility of meeting all applicable statutory and technical
requirements for executing the works.
Yours faithfully,

Encl: As above

Supe~~neer
Copy f.w.cs.to:
1) The Superintending Engineer, EHV Const. Circle, MSETCL, Pune.

(D&T)

ANNEXURE-A

Fire Fighting Equipments for 132133kV Nimboni substation

Description

Sr.No

Document

.
1

Type
Trolley mounted DCP type Fire

01

Drawing

KFPL/OADIH/CPIP17 5

00

QAP

KFPL/QPIH/CP/P/75

00

OTP

KFPL/OTPIHICPIM/50

01

Drawing

KFPL/OADIHICP/M/50

00

Ltr. capacity

QAP

KFPL/QPIHISLP/M/50

00

C02 type Fire Extinguisher 22.5

OTP

K.FPLIOTPIPISHPICl 22.5

01

Drawing

K.FPLIOADIHISHPICl 22.5

00

QAP

K.FPLIQPIPISHPICl22.5

00

Powder (Stored Pressure) type

OTP

KFPLIOTPIPISLPIPl9

01

Fire Extinguisher 9 kg capacity

Drawing

KFPL/OADIP/SLP/P19

00

QAP

KFPL/OADIPISLPIP19

00

OTP

KFPL/OTP/P/CP/M/9

01

Drawing

KFPL/OADIPISLPICPIM/9

00

QAP

----

00

OTP

KFPL/OTP/PISHP/Cl6.5

01

Drawing

KFPLIOADIHISHPICl 6.5

00

QAP

KFPLIQPIPISHPICl 6.5

00

Drawing

KFPL/BSTI009

00

Trolley

mounted

Mechanical

kg capacity

(ABC Type)
5

Mechanical

Foam

type

Fire

Extinguisher 9 Ltr. capacity

C02 type Fire Extinguisher 6.5


kg capacity

Sheets No.
KFPL/OTP/H/CPIP/75

Foam type Fire Extinguisher 50

No. of Rev.

OTP

Extinguisher 75 kg. capacity

Drg./Document No.

9 Ltr. Buckets with Stand

TECHNICAL DATASHEET FOR


POWDER(TROLLEY MOUNTED) TYPE
FIRE EXTINGUISHER OF CAPACITY
75KG

K NEX

KAN EX DOC NO.: KFPL/GTP /H/CP /P /7 5

REV.

PROJECT

132/33 KV Nimboni Substation

CLIENT

MSETCL

CONTRACTOR

M/s SHAH CONSTRUCTIONS

KAN AD IA FYR FYTER PVT LTD


I

(An ISO 9001:2008 Certified Company)

01

DATE: 01.09.2014

SHEET 1 OF

1.00

General

1.01
1.02

Manufacturer
Trade Mark

Kanadia Fyr Fyter Pvt Ltd


"KAN EX"

1.03

Standard Code

IS:10658:1999

1.04

Type

Trolley Mounted Type

1.05

Yes

1.06

Whether Seal is provided to indicate


that Extinguisher has not been used
Quantity

2.00

Materials of Construction

2.01

Extinguishing Medium

Sodium Bi-Carbonate Powder-IS:4308

2.02

Body

M.S Sheet of IS:2062

2.03

Neck Ring

M.S Pipe of IS:1239

2.04

Cap

Brass IS:319

2.05

Cap Washer

Rubber

2.06

Siphon Tube(Inlet)

M.S. Pipe

2.07

Siphon Tube(Outlet)

M.S. Pipe of!S :3601

2.08

C02 gas Cylinder(2 kg)

As per IS:7285

2.09

C02 gas

As per IS:15222

2.10

Discharge Hose

PVC Braided (Burst pressure

2.11

Discharge Nozzle

Aluminium alloy (IS:617)

2.12

Discharge Valve

IS:3224 (Wheel Type)

2.13

Trolley Wheel

Solid Rubber

2.14

Pressure Guage

Range: 0-28kg/cm2

2.15

Carrying Handle

Mild steel Pipe

3.00

Guaranteed Performance

3.01

Capacity

75 kg (By weight of extinguishing charge)

3.02

Discharge Time

50 to 60 sec. (Actual:56 sec approx)

3.03

Range or Throw of Jet

10 meter min. (Actual:ll meter approx)

3.04

Percentage of Discharge

Not Less than 85 %. (Actual:92% approx)

3.05

Hydraulic Pressure Test

30 kg/cm2 for 2.5 minutes

3.06

Burst Test

45 kg/cm2

3.07

Service Pressure/Expansion Space

Not to exceed 15 kg/cm2

3.08

Construction
Features
.,

"

~1

01 No.

"

50 kg/cm2)

/\

As per IS:10658:1999
,,
r.o

/,

,,,,

I/
~

I ,Al;
PROV~D
_____

=...,..

Proj ~ct~

/3..

~-

D~sigo

,---

~ L)

Section

M.S.E.T.C.L. "Prakashganga "


BKC, Sandra (East),Mumbai - 5 1

K NEX

TECHNICAL DATASHEET FOR


POWDER(TROLLEY MOUNTED) TYPE
FIRE EXTINGUISHER OF CAPACITY
75KG

KANADIA FYR FYTER PVT. LTD


(An ISO 9001:2008 Certified Company)

3.09

Supplied First Charge Of Extinguisher


A ent

4.00

Dimensions

4.01

Maximum Diameter of Fire


Extinguisher

40010 mm O/D approx

4.02

Overall Height of Extinguisher

4.03
4.04
4.05
4.06

Shell thickness
Filler Opening
Discharge Hose
Full Weight

1030 mm (Approx.)
4 mm (Approx.)
7Smm
L=S meter 1.0=19 mm
146 kg approx

5.00

Anti-Corrosive Treatment

6.00

Accessories

6.01
6.02
6.03

Carrying Handle
Wheels
All other Accessories as per IS:10658

7.00

Miscellaneous

7.01

Inspection & Testing

As per approved GTP

7.02

Finish

PO Red as per IS : 5 (Shade 538)

7.03

Marking

As Per IS:10658:1999

7.04

Maintenance, Care and Refilling

As per IS 2190

8.00

Approvals

BIS

9.00

Packing

Suitable Jute Bags

Yes

Phosphate Treatment Followed by Epoxy Powder Coating of


body OFT not less than SO micron
Provided
Provided
Provided

10

DES IGN DATA :

STANDARD CODE

IS 10658: 1999

TYP E OF EXTINGU ISHER

TROLLEY MOUNTED TYPE

EXTING UI SHI NG MEDI UM

SOD IUM Bl CARBONATE POWDERIS:4308

CLASS OF FIRE

B& C

CAPA CITY

75 KG.(BY WE IGHT OF
EXT INGU ISH I NG CHARGE)

DI SHCHllRGE T IM E

MIN IM UM 50 SEC.. &


MAX IMlJM60
SEC.(Actual:56 sec approx]

RANG E OF THROW OF JET

NOT LESS THAN 10 METERS.


(Actual:l l meter s approx)
30 kg/.cm 2 FOR 2.5 MINUTES.

HYDRAULI C PR ESSURE
T EST
BURST PRESS UR E

AI

1030mm (APPROX)
PO RED /IS PER IS:5 (SHAD E - 538)

MARKING

AS PER IS: 10658 - 1999

NOT TO EXCEED 15 kg/.cm

TROL LEY WHEEL

SOLID RUBBER

19.

TROLLEY HANDLE

M.S.PIPE

18.

DRA IN PLUG NECK RIN G:

M.S.

17.

DRA IN PLUG WASHER

RUBBER

16.

DRA IN PLUG

15.

PR ESS URE GAUGE

'--

<(
.._...

E
E

0
C'0
0

...-

BRASS
: 0 TO 28 kg/cm 2

DISC HARG E NOZZLE

ALUM INIUM ALLOY IS:6 17

13.

DISC HARGE HOSE

PVC BRAIDED
(BURST PRESSURE 2:5 0kg/ cm 2 )
Lenglh: 5 meter s l.D:19 mm

12.

C02 CONNECT ION HOSE:

W I RE BRAIDED

11.

C02 SYPHONE TUBE


DISCHARGE VALVE

ALUM INIUM
CONF IRM TO IS: 3224

C02 GllS CYL INDER


( 2 KG)

AS PER IS:7285

SYPHONE TUBE
ADAPTOR

M.S.

07.

DI SC HARGE LBOW

M.S.

06.

SI PHONE TUBE
(INL ET)
SI PHONE TUBE
(OUTLET)

M.S.

CA P

03.

WASHER

RUBBER

02.

NECKRING (G 3)

M.S.P IPE OF IS: 1239

0 1.

BODY

M.S. SH EET OF IS:2062

CLIENT

CONTRACTOR
M/ s SHAH CON STRUCTION S
PO.No.

Qty. 01 Nos.
oo.oo.001r o.oo.001
oo.oo.ooJ Q.01~ .

Date

Rev.Dt

Os.08.14

Sandra (East),

eJ

Kfrl'i.N Ex

ame 1Si gn. I

Dte .. m . . . ..-

.. . . ... -

'"'""'"

PROJ ECT

132/33kV

~5.08.14 .~Ji.~?L~ ..~.r,~ FYTER PVT.LTD DRG.No.


IXXX

D escripti o n

J-

l"~ '"''"''"' ""''~""". "'"'""' "' "'~

05.08.14

SEC/P0 / 15-16/04

TITLE
HIGHER CAPAC ITY DRY POWDER FI RE
EXTINGU ISH ER 75 KG CA PACITY.(TROLLEY MOUNTED)

Projects & D~ign Section

~.qw~ .E.T.C . L -"Pra

M a ter i a l s of Con struction s

MSETCL

BRASS TO IS : 3 19

Ite m D escription

'

040010mm

M.S. PIPE TO IS:3601

04.

Sr.No

0...
0...

20.

05.

E
...-

FIN ISH

o0.

'

Q)

400 lOmm.0 /D.(APPROX)

09.

J.

45 kg/.cm 2

TOTAL HE IGHT

10.

1' ~

~r a~~

SE RV ICE
PRESSU RE/EXPA NSION
SP/ICE
Diii. OF BODY

c I 14.

BI

N IM BONI SUB STAT ION

Project

KFPL GAD H CP P/ 75

Sheet

I I

,,J
Scale

NTS

o~

IA

REV.
00

10 SIZE - i\4

KANADIA FYR FYTER PVT. LTD.

F/QAC/01
QUALITY PLAN FOR INSPECTION (IS 10658-1999)

MANUFACTURERS NAME AND ADDRESS

CLIE NT: MSETCL

ITEM: DCP TYPE FIRE EXTINGUISHER OF CAPACITY 75 KG

Kanadia Fyr Fyter Pvt. Ltd.,

PROJECT: 132/33kV NIMBONI SUBSTATION

Plot No. 8 Paras Industrial estate

QP NO. :KFPL/QP / H/CP /P /75

PO.NO: SEC/ P0/15-16/04

Near Garib sha Pir.

REV.: 00

CONTRACTOR: M/s SHAH CONSTRUCTIONS

District: Bhavnagar

Page: 1of1

Sihor(Guj arat) -364 240


SR. NO.

MOC&TESTS

CHARACTERISTICS

EXTE NT OF CHECK
INTERNAL

1
A

Materials of Co nstruction

Body

Che mica l

RV/ MTC

REF. DOCS

IS:2 062

ACCEPTANCE
NORMS

FORMATS OF
RECORDS

AGENCY

RV

IS:2062

MTC

--

Neck Ring

Chemical

RV/ MTC

IS:l239 (P l-1)

1$:1239 (Pl-1)

MTC

--

Cap

Chemica l

RV/ MTC

Type 1 of IS : 319

Type 1 of IS: 319

MTC

Sypho n tube

Chemical

RV/ MTC

IS 3601

IS 3601

MTC

---

CoZ Cyli nder

Visual

RV/ MTC

CCE Approva l

CCE Approva l

CCE Certificates

--

Discharge Hose

Burst Pressure

1 Per Lot

As per 1$: 10658

As pe r IS:l0658

MTC/ ll R

--

Discharge No zzle

Chemical

RV/ MTC

IS 617

IS 617

MTC

--

Dry Powder

Chemical

RV/ MTC

IS:4308

IS:4308

ISi Certificate

--

Hydraulic Test

Hydro Test

100%

IS: 10658 Cl.9.2

IS:10658 Cl.9.2

llR

--

Burst Pressure test

Hydro Test

1 pe r lot

IS:l0658

llR

--

Anti-Corros ive Treatment

Anti - Corros ive


Treatme nt

10% Per Lot

IS: 10658/99 Cl.7.1

IS: 10658 Cl.7.1

ll R

--

Performance Test

Duration. Ra nge &


Discharge

1 Per Lot

IIS: 10658/99 Cl.9.1

IS: 10658 Cl.9.1

ll R

--

Painting

Painting

1 Per Lot

IS: 10658/99 Cl.8.1

IS: 10658 Cl.8.1

llR

Marking

Marking

1 Pe r Lot

IS: 10658/99 Cl.12.1 IS: 10658 Cl.12.1

ll R

---

BIS Approva l

Statutory Requirement Valid BIS Approva l Ce rtificate w ill provided at th e time of Ins pection

--

MFGR:

ISURESH CHAKRASA LI Engg. (Prod.&QC)

1 per order quantity


for witness

1 pe r order quantity
for witness

1. Client/TP I

P : PERFORM ING IMTC : MATERIAL TEST CERT IFICATES

2. Kanadia

W: WITNESS ING l ll R : INTERNAL INSPECTION REPORT


RV: REVIEW ING

LEGEND FOR INSPECTION

!APPROVED BY:

/\

SIGN:

REMARKS

Its: 10658

SIGN:

Projects

t Design Section

M.S.E.T.C.L. "Prakashganga"
BKC, Bandra (East),Mumbai - 51

K' NEX

KANADIA FYR FYTER PVT. LTD

TECHNICAL DATASHEET FOR FOAM


(TROLLEY MOUNTED)TYPE FIRE
EXTINGUISHER OF CAPACITY 50 LTR

KANEX DOC NO.: KFPL/GTP /H/CP /M/50

REV.

(An ISO 9001:2008 Certified Company)

01

PROJECT

132/33 KV Nimboni Substation

.l

CLIENT

MSETCL

CONTRACTOR

M/s SHAH CONSTRUCTIONS

DATE: 01.09.2014

SHEET 1 OF

1.00

General

1.01
1.02
1.03
1.04

Manufacturer
Trade Mark
Standard Code
Type

1.0S
1.06

Whether Seal is provided to indicate


that Extinguisher has not been used
Quantity

2.00

Materials of Construction

2.01
2.02

Extinguishing Medium
Body

AFFF Foam 6 % concentrate confirms to IS:4989


M.S Sheet of IS:1079

2.03
2.04
2.0S

Neck Ring
Cap
Cap Washer

M.S Pipe of!S:1239


LTB2 of JS:318
Rubber

2.06
2.07

2.10
2.11
2.12
2.13

Siphon Tube
C02 gas cartridge(300 gm)
Discharge Hose
Discharge Nozzle
Drain Plug
Snifter Valve
Trolley Wheel
Carrying Handle

M.S. Pipe (IS:3601)


As per JS:494 7
PVC Braided (Burst pressure~ SO kg/cm2)
Aluminium alloy (IS:617)
Brass
Brass IS:319
Solid Rubber
Mild steel Pipe

3.00

Guaranteed Performance

3.01

Capacity

SO Ltr (By volume of extinguishing charge)

3.02

Discharge Time

40 to 180 sec (Actual : 130 sec approx)

3.03

Range or Throw of Jet

Not less than 10 meter (Actual: 11 meter approx)

3.04

Percentage of Discharge

Not Less than 90 % (Actual : 94% approx)

3.05

Hydraulic Pressure Test

30 kg/cm2 for 2 minutes

3.06

Burst Test

45 kg/cm2

3.07

Service Pressure/Expansion Space

Not to exceed 1S kg/cm2

3.08

Construction Features
Supplied First Charge Of Extinguisher
Agent
,
"'

As per IS:13386:1992

2.08
2.09

3.09

2-1

Kanadia Fyr Fyter Pvt Ltd


"KAN EX"
JS 13386:1992
Trolley Mounted Type
Yes
01 No.

I
,.v
'

Yes
,,,,,

I\

,,,,,,,

;b- --------'!:!"

\ ~. -

c:ci
u:::<::r (U&l:::-S2
Proje ts & Design Section
......
aKasnganga "
., "" '"-IL- '-'L
BKC, Sandra (East),Mumba i - 5 1

"'

L ~PPROVED

K NEX

TECHNICAL DATASHEET FOR FOAM


(TROLLEY MOUNTED)TYPE FIRE
EXTINGUISHER OF CAPACITY 50 LTR

KANADIA FYR FYTER PVT. LTD


(An ISO 9001:2008 Certified Company)

4.00

Dimensions

4.01

Maximum Diameter of Fire


Extinguisher

30010 mm.0/D

4.02
4.03
4.04
4.05

Overall Height of Extinguisher


Shell thickness
Filler Opening
Discharge Hose

1285 mm (Approx.)
3.15 mm (Approx.)
75mm
L=3 meter l.D =12.5 mm

5.00

Anti-Corrosive Treatment

Phosphate Treatment Followed by Epoxy Powder Coating of


body DFT not less than 50 micron

6.00

Accessories

6.01
6.02

Carrying Handle
Wheels
All other Accessories as per
1S:13386:1992

6.03

Provided
Provided
Provided

7.00

Miscellaneous

7.01

Inspection & Testing

As per approved GTP

7.02

Finish

PO Red as per IS: 5 (Shade 538)

7.03

Marking

As per IS 13386:1992

7.04

Maintenance, Care and Refilling

As per IS 2190

8.00

Approvals

BIS

9.00

Packing

Suitable Jute Bags

10

_(
I ..
\

J)

DESIGN DATA:
STJ\NDJ\RD CODE

IS 13386: 1992

TYPE OF EXTINGll lSHER

TROLLEY MOUNTED TYPE

EXTINGU ISH ING MEDIUM

J\Fr-F, FOJ\M 6%
CONCENTRATE CONF IRM S TO
IS:4989
A&B

CLASS OF FIRE
CAPAC ITY

El

DI

DISHCHJ\RGE TIME

M INIMUM 40 SEC &


MAX IMUM 180 SEC.

RANGE OF THROW OF JET

NOT LE SS THAN 10 METERS.

PERCENTAGE OF DISCHARGE:

NOT LESS THAN 90%

HYDRAULIC PR ESSURE
TEST

30 kg/.cm 2 FOR 2.0 M INUTES.

BURST PRESSURE

45 kg/.cm

SERV ICE
PRESSURE/EXPANSION
SPACE

NOT TO EXCEED 15 kg/.cm 2

DI/\. OF BODY

300 lOmm.0/D.(APPROX)

TOTAL HEIGHT

1285mm (APPROX)

FINISH

PO RED SHADE 538 OF IS:5- 1994.

MARKING

AS PER IS:13386,CL.12.0

(1 3)

<f:

H2 )

'

;[

Bl

14.

CARRY IN G HANDLE

M.S.PIPE

13.

DISC HARGE ELBOW

M.S.

12.

SNI FTER VJ\LVE

BRJ\SS, TP.-1 Of IS:

11.

DRA I N NECK RING

M.S.

10.

DRAIN PLUG WASHER :

RUBBER

DRAIN PLUG

BRASS

08.

DISCHARGE NOZZLE

ALUMIN IU M J\LLO

07.

DISC HARGE HOSE

PVC BRAID ED
BURST PRESSURE <: 50kg/cm 2
ID: 12.S mm, Length: 3 mtr.

05.

I CO,

GAS CARTRIDGE,:
300 Gms.

I SI PHONE TUBE

<(
...._..

E
E
l()
N

~~")!

~--(1&1)

@-Q_l )
'k _,

Al

03.

CAP

LTB2 TO IS:318

NECK RI NG (G 3)

M.S. PI PE OF IS: 1239

01.

Sr.No

oo.oo.~
0 .00.00.00[

Item Description

Materia ls of Co nstructions

M/s SHAH CONSTRUCTIONS

- - . - I-

-- l
WK~
_ .. N EX

23.08.14

:23.08.14!
23.08.14

-I_

i,

SEC/P0/15-16/04

ITITLE HIGHER CAPACITY MECHAN ICAL FOAM TYPE


FIRE EXT IN GUISHER SO LTR. (TROLLEY MOUNTED)

Sca le

132/33kV NIMBONI SUBSTATION

PROJECT
DRG

,~.,_N..,':'.1,~ ..!;,Y~. FYTER PVTLTD1

XXX Name I Si bon. Date 111.m NO-fo:. l'A RAS No i:srATf. NtARGAX111S11A 1'11t

De scription

Date Rev.Dt

Qty. 01 No.

GIK'Dt SNC
OR'N
RNG
_
_

.No.

KFPL/GAD/H/CP/M/ 5 0

MHOK-JtHHO .tt1Ul)<"nl.:ul 1cdL?~ l:anc.1.firc.co1n

<[o)
PO.No.

J\PP'D /\.Shah

00.00.00 00.00.0 ~
00.00.00 00.00.00J

M.S.SHEET OF IS:1079

BODY

CONTRACTOR

(OUTLET)

02.

MSETCL

M.S. Pl PE TO IS:3601
RUBBER

CL I ENT

(:_.,.)_

WASHER

ID

co

;~

( Ill ~ -@

IS:4947

04.

{oy

09.

06.

IE

"-Q_
Q_

It
~
r

SOLID RUBBER

1
I

I
I

@--~ I

l
\1\
j'

))

)~

TROLLEY WHEEL

lx

!'( ~. ~/)
- (---,

----_4)

50 LTR.(BY VOLUME OF
EXT INGU ISHING CHARGE)

15.

IF

-(6 3)

'---

C1

NTS

Projec

CJ[) I

Sheet

REV.

1ofl

00

10 SIZE - A4

KANADIA FYR FYTER PVT. LTD.

F/QAC/01
QUALITY PLAN FOR INSPECTION (IS 13386)

MANUFACTURERS NAME AND ADDRESS


Kanadia Fyr Fyter Pvt. Ltd.,

ITEM: MFOAM TYPE FIRE EXTINGUISHER OF CAPACITY 50 LTR.

CLIENT: MSETCL
PRO JECT: 132/33kV NIMBONI SUBSTATION

Plot No. 8 Paras In d ustria l estate

QP NO. :KFPL/QP/ H/ SLP / M/ 50

PO.NO: SEC/P0/15-16/04

Near Garibsha Pir.

REV.: 00

CONTRACTOR: M/s SHAH CONSTRUCTIONS

Distr ict: Bhavnagar

Page:lofl

Sih or(G uj arat)-364 240


SR.NO.

MOC & TESTS

CHARACTERISTICS

EXTENT OF CHECK
(INTERNAL)

REF. DOCS

ACCEPTANCE
NORMS

FORMATS OF
RECORDS

AGENCY
p

I wI

RV

REMARKS
9

Materials of Construction

Body

Chemical

RV/MTC

IS: 1079

IS: 1079

MTC

--

Neck Ring

Chem ical

RV/MTC

IS 1239 (Part I)

IS 1239 (Part I)

MTC

Cap

Chem ical

RV/MTC

IS 318 {L TB 2)

IS 318 (LTB 2)

MTC

---

Spri ng

Chemical

RV/MTC

GR. I of IS: 4454

GR. I of IS: 4454

MTC

--

Piercer

Chem ical

RV/MTC

Steel to IS : 65 28

Steel to IS: 6528

MTC

--

Hose

Burst Pressure

1 Per Lot

IS: 13386

As per IS: 13386

MTC/ l! R

--

Foam making Nozzle

Chemical

RV/MTC

IS 617

IS 617

MTC

--

Syphon Tube

Chem ical

RV/MTC

IS 3601

IS 3601

MTC

--

Cartridge

Chemical

RV/ MTC

IS: 4947

IS: 4947

!SI copy

--

Hydraulic Test

Hydro Test

100%

IS: 13386 Cl. 11.3

IS: 13386 Cl. 11.3

l! R

__ 11 Per order quantity

--

Burst Pressure test

1 Per Lot

IS: 13386 Cl. 11.3

IS: 13386 Cl. 11.3

UR

10% Per Lot

IS: 13386 Cl.9.1

IS: 13386 Cl. 9.1

II R

--

1 Per Lot

IS: 13386 Cl.11.1

IS: 13386 Cl.11.1

IIR

Pa inting

10% Per Lot

IS: 13386 Cl. 10.1

IS: 13386 Cl. 10.1

l! R

--

10% Per Lot

IS: 13386 Cl. 13.1

IS: 13386 Cl. 13.1

ll R

--

--

Hydro Test
Anti-Corrosive
Treatment
Duration, Range &
Discharge

Anti-Corrosive Treatment

Performance Test

Painting

Marking

Marking

BIS Approval

Statutory Requirement Va lid BIS Approval Certificate wi ll provided at the time of Inspection

SURESH CHAKRASALI Engg. (Prod.&QC)

APPROVED BY:

F\OVED

SIGN:

1 Per order quantity


for witness

LEGEND FOR INSPECTION

/\

SIGN:

for witness

MFGR:

J:: SJ~

veE gine

&E-S2)

Proiects , _D esign S ec ti on

M.S.E.T.C.L. "Prakashganga "

iKC, Sandra (East),Mumbai - 51

1. CLIENT /TP I

P : PERFORMING IMTC: MATERIAL TEST CERTIFICATES

2. KANADIA

W: W ITNESS ING lll R : INTERNAL INSPECTION REPORT

RV: REVIEWING

K NEX

KANADIA FYR FYTER PVT. LTD

TECHNICAL DATASHEET FOR C02


TYPE FIRE EXTINGUISHER OF
CAPACITY 22.5 KG

KANEX DOC NO.: KFPL/GTP /P /SHP /C/22.5

REV.

PROJECT

132/33 KV Nimboni Substation

CLIENT

MSETCL

CONTRACTOR

M/s SHAH CONSTRUCTIONS

(An ISO 9001:2008 Certified Company)

01

DATE: 01.09.2014

SHEET 1 OF

a.I

1.00
1.01
1.02

Kanadia F r F er Pvt Ltd


"KAN EX"

1.03

Standard Code

IS 2878:2004

1.04

Type

Trolley Mounted Type

1.05

Yes

1.06

Whether Seal is provided to indicate


that Extin uisher has not been used
Quantity

2.00

Materials of Construction

2.01

Extinguishing Medium

C02 Ofpurity-99.5% As per IS:15222

2.02

Body

Seamless Manganese Steel-IS! marked confirms to IS:7285

2.03

Discharge Valve(Wheel Type)

Confirms to IS:3224

2.04
2.05

Discharge Horn
Discharge Hose

Non-Conductor Of Electricity-Polyethylene
Wire Braided Rubber L=5m ID =lOmm

2.06

Siphon Tube

Aluminium confirms to IS:738

2.07

Trolley

Mild steel (Powder Coated)

2.08

Trolley Wheel

Solid Rubber

3.00

Guaranteed Performance

3.01

Capacity

22.5 kg (Tolerance 0 to -5% by mass)

3.02

Filling Ratio

Not to exceed 0.667 percent

3.03

Discharge Duration

20 to 60 sec (Actual: 47 sec approx)

3.04

Percentage of Discharge

Not Less than 95 % (Actual: 97.5% approx)

3.05

Temperature Range

-30 C to +55 C

3.06
3.07

Hydrostatic Stretch Test


Leakage test

At 250kgf/cm2
By Dipping in water for 2 min. leakage to checked

3.08

Discharge Hose Test

3.09

Intermittent Discharge test

Burst pressure of 275 kgf/cm2 in controlled discharge and 140


kgf/cm2 without controlled discharge
Discharge not less than 95%

4.00

Dimensions

4.01

Maximum Diameter of Fire


Extinguisher

0232+10 mm.

4.02

Overall Height of Extinguisher

1155 mm (Approx.)

4.03
4.04

Shell thickness
Full weight of cylinder

5.5mm
66 to 69 kg (Approx)
.,__

- .,_

r,

04 Nos.

/\

/ AP

.,

---

,.

...

---

I
I

--

ROVED

.~ ,,..-.- ~~
--

Y"'"u" _;;,,
. '

tn&l= -S2)

---=~--~ ~oction

"PrakashQanga"
.
. -
-
t) Mumbai - 51
BKC, Sandra (Eas
.... - r - - r r l

.....

K NEX

TECHNICAL DATASHEET FOR C02


TYPE FIRE EXTINGUISHER OF
CAPACITY 22.5 KG

KANADIA FYR FYTER PVT. LTD


(An ISO 9001:2008 Certified Company)

5.00

Color Of Extin2uisher body

Painted With Durable Enamel PO red shade No.538 of JS:5

6.00

Accessories (brackets & screws)

Provided

7.00
7.01

Miscellaneous
Inspection & Testing

As per approved GTP

7.02

Finish

PO Red as per IS: 5 (Shade 538)

7.03

Marking

As per IS 2878 :2004

7.04

Approvals

BIS & CCOE (PESO)

7.05

Maintenance, Care and Refilling

As per IS 2190

8.00

Packing

Suitable Jute Bags

~~~~~~2~~~~3-

10

.l

07

rI

06

DESIGN DATA

f- I

01.

STANDARD CODE

02.

TY PE 01' EXTINGU ISI IER

TROLLEY MOUNTED TYPE

EXTINGU ISHING MED IUM

CO, - OF PUR ITY 99. 5%


AS PER IS: 15222

04.

CAPAC ITY

22.5 KG (BY WEIG ll TOI'


EXTINGU ISI JI NG Cl IARGE)

o5.

FILLING RATIO

NOT TO EXCEED 0.667

06.

DISCHA RGE DURATION

20 - 60 SEC.

07.

PERCENTAGE OF
DISCHARGE

NOT LESS THAN 95%

TEMPERATURE RANGE

-30C TO +55C

cl

I
05

Lr

AT 250 KGF/CM'

10.

DI AOF BODY

0232 10M M O D (AP PROX)

II.

TOT AL HE IGHT

I 155MM (A PPROX)

12.

FIN ISH

P.O. RED TO SHADE


N0. 538 OF IS : 5

13.

MARKING

AS PER IS:2R78,CL.IO.O

t-rrL~
r

~I

d1

11

~~:;;!

~f 1

'--

0.
Q_

<(

E
E

ID

04 - -

01

c
12.

COTTER PIN

M.S

I I.

NUT/BOLT

ACCESSORIES

10.

TROLLEY Wll EEL

SO LID RU BBER

09.

TROLLEY

M.S.POWDER COATED

08.

SEAL

LEAD

07.

SAFETY PIN HOLDER

PVC

06.

SAFETY PIN

S.S.

05.

SI PHONE TUBE

AL UM INU M CONF IRM TO IS:738

04.

DISC HARGE HOSE

WIRE BRA IDED 5 MTR. ID- 10 MM.


I-I A YING BURSTING PRESSURE
SHALL 275 KGF/CM' IN CONTROL
DISCHARGE AND 140 KGF/CM'
WIT HOUT CONTROL DISCHA RGE

03.

Al

L()
L()

I-

'i'

!
09

l-IYDROSTA TIC STRETCH


TEST

09.

08

02 -

IS 2878 : 2004

03.

08.

ra-

DISC! IARGE I JORN

.i'':.! 3L J Q
1

10 ,~~~~-r--ir-~~~~~--.

CLIENT

DISCHARGE VALVE
(WHEEL TYPE)

CON FI RMS TO

01.

BODY

SEAMLESS MANGANESE
STEEL - rsr 1..: YIARKED
CONFTR~ I S TO TS:7285

Materials o f Co nstructions
j

MS ET CL
CONTRACTOR

Design Section

M/s SHAH CONSTRUCTIONS

M.S.E.T.c.l. "Prakashganga "

PO.No.

BKC, Sandra (East), Mumbai - ~.104 Nos.

T ITLE

rs: 3224

02 .

~ "'

prr I

12

NON CONDUCTOR OF
ELECTRICITY POL YETI IYLENE

Sr.No Item Description

- - 03

APP'D A.Shah
Cl-IK'D SNC
DR'N RNG

00.00.00 00.00.00
00 .00.00 00.00.00
00.00.00 00.00.00

Date Rev.Dt

~ K NEX

XXX Name Sign. Date

--6

C0 2 TYPE FIRE EXTINGUISHER


OF CAPACITY 22.5 KG .

PROJECT
13 .08. 14
I 32/33kV
13.08. 14 KANADlA FYR FYTER PVT.LTD DRG .No.
(A N I S0-~1 -l(loH(ll( l l fll O C01

Descri ption

13.08. 14

SEC/PO/ 15- 16/04

PLOT NO 8. !'Alt.AS !NO FSTATE. /\'f.All.GAR.IOSllA


~ 111011. -364 HO (GUI ) <>-nml: 1ccti2~la....,>.fir~.coo1

l~ll

NfMBON1 SUBST ATTON


KFPL/GAD/ H/S HP/C/22.5

cJ@

Sheet
or }

.--

Sca le NTS
Proj ect

'.::l

IA

REV.
00

1 n s 1zE-M

Kanadia Fyr Fyter Pvt. Ltd.

F/QAC/01

QUALITY PLAN FOR INSPECTION (AS PER IS 2878 : 2004)


ITEM : 22.5 KG CAPACITY C02 TYPE FIRE EXTINGUISHER

MANUFACTURERS NAM E & ADDRESS


Kanadia Fyr Fyter Pvt Ltd.,
Plot No. 8 Paras Ind ustria l estate
Near Garibs ha Pir.
District Bhavnagar

t-c_
u _EN_T_:_Ms_E_Tc_L_ _ _ _ _ _ _ _ _ _ _ _ _ __
PROJECT: 132/33kV NIMBON! SUBSTATION

QP. NO.: KFPL/ QP /P / SHP /C/ 22.5


REV.: 00
Page: 1of1

PO.NO: SEC/P0/15- 16/04


CONTRACTOR: M/s SHAH CONSTRUCTIONS

Sihor(G ujarat)-364 240


SR NO
.
.

MOC & TESTS

CHARACTERISTICS

EXTENT OF CHECK
(INTERNAL)

REF DOCS
.

ACCEPTANCE
NORMS

FORMATS OF
RECORDS

AGENCY
W

RV

S
EMARK
10

Raw Material

Body

Vis ua l and Dime nsiona l

R / MTC

IS : 7285

IS: 7285

MTC

--

Valve

Vis ua l and Dimensiona l

R / MTC

IS : 3224

IS: 3224

MTC

--

Hose

Burst Pressu re

1 Per Lot

IS : 2878

As per IS: 2878

MTC/ II R

--

C02 Gas

.
Qua lity of Gas

R / MTC

IS: 2878

Purity as per IS :
15222

MTC

--

Syphon Tube

Chem ical

R / MTC

IS: 738

IS : 738

MTC

--

Hydro Test

Hydro Test

R / MTC

IS: 7285

IS : 7285

MTC

--

IS:2878/20 04 CI.9.1 II R

--

1 Per order q uantity


for Witness
1 Per order quantity
for Witness

Performance Test

Duration,% discharge

1 Per Lot

IS:2878/2004
Cl. .
91

Leakage Test

Leakage Test

1 Per Lot

IS:2878/2004
CI. .3
9

!S:2878/2004 CI.9.3 !I R

--

Visual Inspection

Painting

Visual

1 Per Lot

IS:2878/2004
Cl _
81

IS:2878/2004
_
81

!I R

--

.
Markmg

.
Marking

1 Per Lot

IS: 2878/2004
CI
11

!S:2878/2004
CI
11

llR

--

Accessories

Wh ee l Carriage

1 Per Lot

Mfrs. Sta ndard

Mfrs. Standard

--

BIS Approval

Statutory requirement

Valid BIS Approval Certificate w ill provided at the t ime of Inspection

--

C.C.E Nagpur Approval

Statutory req uirement

The C.C.E. Nagpur approval Certificate wi ll be provided a long with supp ly

--

MFGR: SURESH CHAKRASALI Engg. (Prod.&QC)

SIGN

/
C'

APPROVED BY:

SIGN

---

,....

'.

Ex

~,..

Cl

L -~
r p~

' A\)

ut1ve

o~-:---

R.

LEGEND FOR INSPECTION

VED
__ r (D&E-82)

\ ~ac-i,-,n

c-

M.S.E.T.C.L. "Prakashganga"
I BKC, Sandra (East),Mumbai - 51

1. Client/TPI

P: PERFORMING

MTC: MATERIAL TEST CERT IFICATES

2. Kanadia

W: WITNESS ING

ll R: INTERNAL INSPECTION REPORTS

RV: REVIEWING

TECHNICAL DATASHEET FOR


POWDER(STORED PRESSURE) TYPE
FIRE EXTINGUISHER OF CAPACITY
9KG

KANEX DOC NO.: KFPL/GTP /P /SLP /P /9

REV.

PROJECT

132/33 KV Nimboni Substation

CLIENT

MSETCL

CONTRACTOR

M/s SHAH CONSTRUCTIONS

01

KANADIA FYR FYTER PVT. LTD


(An ISO 9001:2008 Certified Company)

SHEET 1 OF

DATE: 01.09.2014

1.00

General

1.01
1.02

Manufacturer
Trade Mark

Kanadia Fyr Fyter Pvt Ltd


"KAN EX"

aj

1.03

Standard Code

IS 1S683:2006

1.04

Type

Portable Stored Pressure

l.OS

Yes

1.06

Whether Seal is provided to indicate


that Extinguisher has not been used
Quantity

2.00

Materials of Construction

2.01

Extinguishing Medium

2.02

Body

2.03

Neck Ring

Mono Ammonium Phosphate based dry powder-90% Confirms


to IS 14609
Mild Steel Sheet having Max. of 0.2 S% Carbon, 0.0 S%
Phosphorous and O.OS % Sulphur
M.S. Pipe

2.04
2.0S

Valve
Siphon Tube

Brass
Brass

2.06

Discharge Nozzle

Plastic

2.07

Pressure Gauge/indicator

As per IS 15683:2006

2.08

Discharge Hose

Rubber Braided EPDM Hose (Length :S60mm)

2.09

Wall mounting Bracket with screw

Mild steel (Powder Coated)/M.S

3.00

Guaranteed Performance

3.01

Capacity

9 kg (Tolerance of 2% by mass)

3.02

Minimum effective Discharge Time

Minimum: 13 Sec. (Actual : 31 Sec. approx)

3.03

Bulk Range of Discharge

Minimum 2 meter (Actual : 6 meter approx)

3.04

Percentage of Discharge

Not Less than 8 S % (Actual : 92.9% approx)

3.05

Fire Rating

4A:89B

3.06

Temperature Range

-30 C to +SS C

3.07
3.08

Service Pressure
Maximum Ser vice Pressure

15 bar
18 bar

04 Nos.

/\

~PP Ro/ED

I/ ~ ~

~l ve 1::ng11 "''"'''
.

11uJ-rL>=>

LJCVI~

lu...,.c::-~~1

_..

M.S.E.T.C.L. "Prakasngan ga

4.00

Routine Tests

4.01

Pressure test (Pt)

3S bar (3.S MPa)

4.02
4.03

Minimum Burst Pressure test (Pb)


Leakage test

S5 bar (S.5 MPa)


By applying soap solution leakage to checked

:H, V , OCU IUf ct \..._......._..._.l},

1v1u1

, __

I K NEX

TECHNICAL DATASHEET FOR


POWDER(STORED PRESSURE) TYPE
FIRE EXTINGUISHER OF CAPACITY
9KG

KANADIA FYR FYTER PVT. LTD


(An ISO 9001:2008 Certified Company)

4.04

Partial discharge

The second pressure or weight shall not be less than 75 % of the


first after interruption of the Discharge.
Not Jess than 35 bar (3.5 Mpa)

4.05

Burst pressure Test For Discharge Hose

5.00

Extinguishers also pass through the Following Tests (Type tests)

5.01
5.02
5.03
5.04
5.05
5.06
5.07
5.08

Resistance to Temperature changes


Resistance to Impact test
Resistance to Vibrations test
Resistance to Corrosion test -External
Tapping Test
Intermittent Discharge test
Crushing test
Pressure cycling test

6.00

Dimensions

6.01
6.02
6.03
6.04

Maximum Diameter of Fire


Extinguisher
Overall Height of Extinguisher
Thickness of sheet
Full weight of cylinder

7.00

Anti - Corrosive Treatment

Phosphate Treatment Followed by epoxy powder coating of


body DFT Not Jess than SO Micron

8.00

Accessories (brackets & screws)

Provided

9.00

Miscellaneous

9.01

Inspection & Testing

As per approved GTP

9.02

Finish

PO Red as per IS : 5 (Shade 538)

9.03

Marking

As per IS 15683:2006

9.04

Approvals

BIS

9.05

Maintenance, Care and Refilling

As per IS 2190

10.0

Packing

Corrugated boxes (Outer box sizes: 370xl 90x660mm)

"

18010 mm.
575 mm (Approx.)
Made Up of 2 mm
13.3 kg (Approx)

Qc {

~1 1 >-

(ls~ - \ ,

-"'~)

:
DESIGN DATA

r..J

~"'

trPA~ICULARS

(0 8)

DESCRIPTION
9 kg (To lerance
2% by mass)
-30C to +ss 0 c
15 bar
18 bar

02 ITcmpraturc ra nge
03 Service pressure

04 Maximum service

12

~ l~\.J\

ii 3

~S _l'E R IS: 15683-20 06

__ j

_ill![_

!Extinguishing medium

IS.

lever lock

14.

Wa ll bmcket with Screw Mi ld steel (Powder coated) I M.S

Not less than 3S bar


(3.S MPa)

I
I

13.

Safety pin Holder

Rubber/Soft pvc

Safety pin

S.S.

II .

Seal

Plastic

10.

Belt

Plastic

09.

Siphon tube

Plastic

-I

I <l.ti

~I

.L

i1 l~2tc~
.~l
/,~~'j ' ::::- ~'_

~g1neer

& Design Section

0180 10rw1

CLI ENT

.L. "Prakashganga"

11

M SETCL

BKC, Sandra (East),Mumbai - 51

08.

Pressure gauge/Indicator

As per IS : IS683-2006

07.

Discharge hose

Rubber B1:aided EPDM Hose (Length:S60 mm)

06.

Discharge Nozz le

Plastic

OS.

"O" Ri ng

Nit1y lc Rubber

PO.No.

SEC/PO/ 15- 16/ 04

04.

Valve

Brass

TITLE

POWDE R (STORED PRESSURE)

03.

f lorescent Ring

Plastic

02.

Neck ring

01.

Body

FIRE EXTINGUISHER CAPAC ITY 9 KG.


00 .00 .0~ 00.00.00 -

M.S.Pipc
Sheet Having Maximum Of
C=0.25%,P=0.05% and S= 0.05%

- -

Materials of Constructions

CONTRACTOR
M /s SHAH C ONSTRUC TION S

~ M.S.

Sr.No 1 Ite m Description

ID

Mono Ammonium Phosphate based


dry powder-90% (Confim1s to IS: 14609)
Plastic

12.

' IE

Made up of
2 mm S heet

C1
16.

3S bar (3.S MPa)


SS bar (S.S MPa)

t PERFORMANCE PARAMETERS ~
0 11 Effective discharge ti me Mini mu m 13 Sec.
(Actual : 3 1 sec approx)
021Bulk range of discharge Minimum : 2 meter
(Actual : 6 meter approx)
03 Percentage of discharge Not less d1an 8S%
(Actua l : 92.9% approx)
4A : 89B
04 1 Fire Rating
<01

MARKING

Pressure

OS I Pressure test (PT)


06 1 Minimum Burst
J
Pressure Test(PB)
07 Burst pressure of hose

APPROVAL

10

F
\

prcapacity

(Q7/

'"{ ~

I Ir(

00 . 00 .~

Oo.00.00 . 00.0o.00

DR'N

~~

D a te

Rc v.Dt

1 01.0 1.1 41
ol.01.1 4

RNG _j

.(

lO Kn

TPROJ ECT

XXX Name Sign. Date , ~:.~~~?~~~~l~~/~~~5!~~~~r~~lSllAPIR.

D escr iption

DJ-

N Ex
132/33 kV N IMl30Nl SUBSTATION
01.0 1. 14 , ~.,_N_f.:1,f~ ..f.,Yo\,~ FYTER PVT.LTD~G No.
KFP L/GA D/ P/S LP/ P/ 9

APP'D .j A.S hahl


IC HK'DS NC 1

j 00.00.00

Scale NTS
Project

0@

Sheet
of I

IA

REV.
00

1Q SIZE-A4

KANADIA FYR FYTER PVT. LTD.

F/QAC/ 01
QUALITY PLAN FOR INSPECTION (AS PER IS 15683:2006)

MANUFACTURERS NAME & ADDRESS

CLIENT: MSETCL

Kanadia Fyr Fyter Pvt. Ltd.,

ITEM: POWDER TYPE (STORED PRESSURE) 9 KG CAPACITY

Plot No. 8 Paras Indus tria l estate


Nea r Garib s h a Pir.
District: Bhavnagar

QP. NO.: KFPL/GAD/P /SLP /P /9


Rev.: 00
Page: 1 ofl

PROJECT: 132/33kV NIMBONI SUBSTATION


PO.NO: SEC/P0/15-16/04
CONTRACTOR : M/s SHAH CONSTRUCTIONS

Sihor(Gujarat)-364 240
SR.NO.

MOC&TESTS

CHARACTERISTICS

EXTENT OF CHECK
(INTERNAL)

REFERENCE
DOCUMENTS

ACCEPTANCE NORMS

Materials of Construction

Body

Che mi cal

RV/ MTC

IS 15683 :2 006

FORMATS OF
RECORDS

AGENCY
P

I w

REMARKS
RV

10

As per IS 15683 :2006

MTC

--

Neck Ring

Visual

RV I IIR

IS 15683 :2006

As per IS 15683 :2006

MTC

--

Valve

Visual

RV I !IR

IS 15683 :2006

As per IS 15683 :2006

MTC

--

Discharge Ho se

Burst Pressure

RV/MTC/IIR

IS 15683 :2 006

As per IS 15683 :2006

MTC/IIR

--

Dry Powder

Ch em ical

RV/MTC

IS 14609

IS 14609

MTC

--

Pressure Test

Hydro Tes t

100%

IS 15683 :2 006

As per IS 15683 :2 006

IIR

--

Min. Burst Pressure Test

Hydro Tes t

1 Per Lot

IS 15683 :2006

As per IS 15683 :2006

IIR

--

Routine Checks

Leakage test

100%

IS 15683 :2006

As per IS 15683 :2006

IIR

--

1 per order qua ntity for


witness

Performance Test

Performance Tes t

1 Per Lot

IS 15683 :2006

As per IS 15683 :2006

IIR

--

1 pe r order qua ntity for


witness

Resista nce to Temp. changes, Partial


discharge test, Press ure cycling tes t,
Impact test, Vibrations test,
As per IS 15683 :2006
Crushi ng test, Corrosion test External, tapping test &
Intermittent d.ischarge

As per Scheme of
tes ting (STI) of IS IS 15683 :2006
15683: 2006

As per IS 15683 :2 006

Manufacturers
Reco rd

--

Manufacturers Records
to be reviewed (as per
STI of IS 15683:2006)

Painting

Painting

10% Per Lot

IS 15683 :2006

IS 15683 :2006

IIR

--

Ma rking

Marking

10% Per Lot

IS 15683 :2006

IS 15683 :2006

IIR

--

Accesso ries

Bracke ts & Screws

1 Per Lot

Mfrs. Standard

Mfrs Standard

--

--

BIS Approva l

Statutory requirement

Va lid BIS License copy

--

MFGR: SU RESH CHAKRASALI Engg. (Prod.&QC)

APPROVED BY:

,.-:.f-"" /:'"y~

.$
~ c_;?
0

SIGN:

C/

LEGEND FOR INSPECTION

"\

A~

:P

,;.~

~,.:"'
SIGN:

I
I

l'
I

Exe"
~

'
te, ~&E-S2)
-

-;;;V" _.1

.,

- - ..,.-

M.S.E.T.C.L. "Prakashganga "


~ KC,

Sandra (East),Mumbai - 51

. Cli ent/TP I
Kanadia

P : PERFORMING MTC : MATERIAL TEST CERTIFICATES


W: WITNESSING
RV: REVIEWING

ll R : INTERNAL INSPECTION REPORT

K NEX

KAN AD IA FYR FYTER PVT. LTD

TECHNICAL DATASHEET FOR


FOAM(CARTRIDGE OPERATED) TYPE
FIRE EXTINGUISHER OF CAPACITY 9 LTR

KANEX DOC NO.: KFPL/GTP /P /CP /M/9

REV.

PROJECT

132/33 KV Nimboni Substation

CLIENT

MSETCL

CONTRACTOR

M/s SHAH CONSTRUCTIONS

01

(An ISO 9001:2008 Certified Company)

DATE: 01.09.2014

SHEET 1 OF

1.00

General

1.01
1.02

Manufacturer
Trade Mark

Kanadia Fyr Fyter Pvt Ltd


"KAN EX"

1.03

Standard Code

IS 15683:2006

1.04

Type

Portable Cartridge Operated

1.05

Yes

1.06

Whether Seal is provided to indicate


that Extinguisher has not been used
Quantity

2.00

Materials of Construction

2.01

Extinguishing Medium

Water+ AFFF Foam 6% Confirms to IS:4989

2.02

Body

2.03

Neck Ring

Mild Steel Sheet having Max. of 0.25% Carbon, 0.05 %


Phosphorous and 0.05% Sulphur
M.S. Pipe

2.04
2.05

Valve
Siphon Tube

Brass
Plastic

2.06

Discharge Nozzle

PVC

2.07

Gas Cartridge(200 grams)

ISi marked as per IS:494 7

2.08

Discharge Hose

Rubber Braided EPDM Hose (Length : 560 mm)

2.09

Wall mounting Bracket with screw

Mild steel (Powder Coated)/Screw of M.S

3.00

Guaranteed Performance

3.01

Capacity

9 !tr. (Tolerance 0 to 5% by volume)

3.02

Minimum effective Discharge Time

Minimum: 13 Sec. (Actual: 32 Sec. approx)

3.03

Bulk Range of Discharge

Minimum 2 meter (Actual : 5 meter approx)

3.04

Percentage of Discharge

Not Less than 95 % (Actual : 99% approx)

3.05

Fire Rating

4A:34B

3.06

Temperature Range

+5 C to +55 C

3.07

Service Pressure

14 bar

3.08

Maximum Service Pressure

18 bar

4.00

Routine Tests

4.01

Pressure test (Pt)

35 bar (3.5 MPa)

4.02

Minimum Burst Pressure test (Pb)

55 bar (5.5 MPa)

aj

04 Nos.

/\

APPROVED

--

~ ~~

~"..~1neer (D&E-S~)

~,-r"'

' ues1gn

~ection

A""" -

- -.L.

ctKasnganga "

8 KC, Sandra (East),Mumbai - 51

""

""

"

K NEX

TECHNICAL DATASHEET FOR


FOAM(CARTRIDGE OPERATED) TYPE
FIRE EXTINGUISHER OF CAPACITY 9 LTR

KAN AD IA FYR FYTER PVT. LTD


(An ISO 9001:2008 Certified Company)

4.03

Leakage test

By applying soap solution leakage to checked

4.04

Partial discharge

4.05

Burst Pressure For Discharge Hose

The second pressure or weight shall not be less than 75 % of the


first after interruption of the Discharge.
Not less than 35 bar (3.5 Mpa)

5.00

Extinguishers also pass through the Following Tests (Type tests)

5.01
5.02
5.03
5.04
5.05
5.06
5.07
5.08
5.09

Resistance to Temperature changes


Resistance to Impact test
Resistance to Vibrations test
Resistance to Corrosion test -External
Resistance to Corrosion test -Internal
Tapping Test
Intermittent Discharge test
Crushing test
Pressure cycling test

6.00

Dimensions

6.01

Maximum Diameter of Fire Extinguisher

18010 mm.

6.02
6.03
6.04

Overall Height of Extinguisher


Thickness of sheet
Full weight of cylinder

575 mm (Approx.)
Made Up of2 mm
12 kg (Approx)

7.00

Anti - Corrosive Treatment

Phosphate Treatment Followed by epoxy powder coating of


body OFT Not less than 50 Micron

8.00

Accessories (brackets & screws)

Provided

9.00

Miscellaneous

9.01

Inspection & Testing

: As per approved GTP

9.02

Finish

: PO Red as per IS : 5 (Shade 538)

9.03

Marking

: As per IS 15683:2006

9.04

Approvals

: BIS

9.05

Maintenance, Care and Refilling

: As per IS 2190

10.0

Packing

: Corrugated boxes (Outer box sizes: 370xl 90x660mm)

Fl

10

- -('"\
1
.1 1

(~~

_)

DESIGN DATA
~

Sr
DESCRIPTIO N
PARTICULARS
No.
-- - - - 9 Lt r. (Tolcrance
0 to 5% by Vo lume)
+5C to +ss 0
15 bar
18 bar

0 1 Capacity

""'

//~)

El

/ ~

DI

Pressure

I,-

05 Pressure test (PT)


06 Minimum Burst
Pressure Test(PB)
07 Burst pressure of hose

11~ 1-1'\1 T >~


14

MARKING

35 bar (3. 5 MPa)


55 bar (5.5 MPa)

/ ;1

IE

~I
(D

ID

/1

()

'-

Q_
Q_

Not less than 35 bar


(3 .5 MPa)

<I

\~

PERFORMANCE PARAMETERS

CIAPPROVAL

~~

02 Temprature range
03 Service pressure
04 Maximum service

'~-@

0 I Effective discharge time Minimum : 13Scc.


(Actua l:32 sec approx)
02 Bulk ran ge of discharge Minimum : 2 mete r
(Actual:S meter approx)
03 Percentage of discharge Not less th an 95%
(Actual :99% approx)
4A : 34B
04 Fire Rating

IJl

IAS PER IS:l5683-2006


BIS

Made~

2mm Sheet

I Water + AFFF Foam (6%) Confirms to

15.

!Ext in gu ishing medium

14.

Wall bracket with Screw Mild steel (Powder coated) /Screw M.S

13 .

"C" Cli p

--@) .-~~-:-...-r,_~~~~-.

IS:4989

Bl

Al

VED

M.S.

12.

Safely pin Ho lder

Rubber/Soft pvc

II.

Safely pin

S.S.

10.

Seal

Plastic

09.

llelt

Plasti c

08.

Gas Cartridge (60 gm.)

!SI Marked - As per IS 4947

07.

Discharge Nozzle

PVC

06.

Hubber Uraided l::POM Hose (LengU1:S60 mm)

05.

Discharge hose
Strainer

S.S.

04.

Siphone tu be

Plastic

(D&E-S2~ cIJ rNT


Projects & besign Section
BKC, Bandra (East),Mumbai -

.,~

Valve

Brass

Nec k ring

M.S. Pipe

01.

Body

M. S. Sheet Hav ing Maximum Of


C=0.25%,P=0.05% and S= 0.05%
--- -

NTRACTOR

Mi s SHAH CONSTRUCTIONS

00.00.00 00.00.00
00.00.00 00.00.00
00.00.00 00.00.00

-- ---

Date Rev .Dt

-/\PP'D A.S hah!' HK'D SNC


DR'N RNG

Description

XXX

0 1.01. 14
0 1.01. 14
0 1.01. 14

ame S ign. Date

SEC/P0/1 5- 16/04

PO.No.

Material s of Constructions

MSETCL

M.S.E.T.C.L. "Prakashganga "

1TITLE

03.

)--

-@ j

Qty. 04 Nos.

02.

Sr.No l Item Description

018Ql0MM

l!JJ

Kn N EX

-----

FOAM (CARTRIDGE OPERATED) TYPE


FrRE EXTINGUISH ER CAP AClTY 9 LTR.

i PROJECT

----

--

132/33 kVNIMBONI SUBSTATION


'

,~'."J"~~~ . f..'.(!;; FYTER PVT.LTD! DRG .No. KFPL/GAD/P/S LP/CP/M/9


~~~6~~~ ~:.:;~~~~,1~~~;;,s;~1;~:a~:r~:~1s1 1A 1'11t.

Sca le
P roj ect

NTS

IA

00

~ R~V

'

t of I oo

1Q SIZE - A4

KANADIA FYR FYTER PVT. LTD.

101.11.09

IF/ QAC/ 01

QUALITY PLAN FOR INSPECTION (AS PER IS 15683:2006)


MA NU FACTURERS NAME & ADDRESS

CLIENT: MSETCL

Kanadia Fyr Fyter Pvt. Ltd.,

ITEM: FOAM TYPE (CARTRIDGE OPERATED) 9 LTR. CAPACITY

PROJECT: 132/33kV NIMBONI SUBSTATION

Plot No. 8 Pa ras Ind us trial estate


Nea r Garibs ha Pir.
Distri ct : Bha vn aga r

QP.NO.:
Rev.: 00
Page: 1 ofl

PO.NO: SEC/P0/15-16/04
CONTRACTOR: M/s SHAH CONSTRUCTIONS

Si hor(Guja rat)-3 64 240


SR.NO.

MOC & TESTS

CHARACTERISTICS

EXTE NT OF CHECK
(INTERNAL)

REFERENCE
DOCUMENTS

ACCEPTANCE NORMS

FORMATS OF
RECORDS

1
A

Materials of Construction

Body

Chemica l

RV/ MTC

IS 15683 :2006

AGENCY
P I

w
9

As p e r IS 15683 :2006

MTC

REMARKS

10

RV

--

Neck Ring

Visua l

RV/ ll R

IS 15683 :2006

As per IS 15683 :2006

MTC

--

Va lv e

Vis ua l

RV/ llR

IS 15683 :2006

As per IS 1568 3 :2006

MTC

--

Disc harge Hose

Burst Press u re

RV/MTC/ ll R

IS 15683 :2006

As per IS 15683 :2006

MTC/ ll R

AFFF Foam

Ch emical

RV/MTC

IS 4989

IS 49B9

MTC

---

100%

IS 15683 :2006

As per IS 15683 :2006

llR

__ 11 per order qua ntity for


witness

--

--

__ 11 per order q uantity for


w itness

I Pressure Test

I Hydro Tes t

IMin. Burst Pressure Test


IRoutine Checks

IHydro Test

1 Per Lot

IS 15683 :2006

As per IS 15683 :2006

ll R

!Leakage test

100%

IS 15683 :2006

As per IS 15683 :2006

ll R

D
E

I Performance Test

IPerformance Tes t

1 Per Lot

I''

Res ista nce to Temp. changes, I;'artia l

" """ " ' " '. ' ' "." " cycUog OOt

MFGR :

l lmpac.t test, Vibrations test,


Crush ing test, Corros ion testExternal , tapping test &
Intermittent discha rge

IS 15683 :2006

P" Scheme of

As per IS 15683 :2006

tes t ing (ST I) of IS IS 15683 :2006


: 2006
15683

As per IS 15683 :2006

IAs per IS 15683 :2 006

l~:c:~~cturers

-- I

Painting

Painting

10% Pe r Lot

IS 15683 :2006

IS 15683 :2006

llR

ll R

Marking

Marking

10% Per Lot

IS 15683 :2006

IS 15683 :2006

Accesso r ies

Brackets & Screws

1 Per Lot

Mfrs. Standard

Mfrs Standard

BIS Approva l

Statutory require m e nt

Va lid BIS License copy

APPROVED BY:

1. CLI NT/TP I

I Manufacturers Records
to be reviewe d (as per
ST! of IS 15683:2006)

LEGEND FOR INSPECTION

/\
ADIA

SIGN:

ll R

SIGN:

M .S.E.T.C.L. l'Prakashganga ..
B KC , Sandra (East),Mumbai - 51

P: PERFORM ING RV: REVIEW OF CE RTIF ICATES


W: WITNESS ING

MTC : MATER IAL TEST CERTIFICATES

RV: REVIEWING

ll R : INTERNAL IN SPECTION REPORT

K NEX

TECHNICAL DATASHEET FOR COZ


TYPE FIRE EXTINGUISHER OF
CAPACITY 6.5 KG

I KANEX DOC NO.: KFPL/GTP/P/SHP/C/6.5 I REV.


PROJECT

132/33 KV Nimboni Substation

CLIENT

MSETCL

CONTRACTOR

M/s SHAH CONSTRUCTIONS

KAN AD IA FYR FYTER PVT. LTD


(An ISO 9001:2008 Certified Company)

I DATE:

01

01.09.2014

SHEET 1 OF

:L!

1.00

General

1.01
1.02
1.03
1.04
1.05
1.06

Manufacturer
Trade Mark
Standard Code
Type
Whether Seal is provided to indicate
that Extinguisher has not been used
Quantity

2.00

Materials of Construction

2.01
2.02
2.03
2.04
2.05
2.06

Extinguishing Medium
Body
Discharge Valve(Wheel Type)
Discharge Horn
Discharge Hose
Siphon Tube

C02 Of purity-99.5% As per IS:15222


Seamless Manganese Steel-IS! marked confirms to IS:7285
Confirms to IS:3224
Non-Conductor Of Electricity-Polyethylene
Wire Braided Rubber L=lm ID =lOmm
Aluminium confirms to IS:738

2.07
2.08

Trolley
Trolley Wheel

Mild steel (Powder Coated)


Solid Rubber

3.00

Guaranteed Performance

3.01

Capacity

6.5 kg (Tolerance 0 to -5% by mass)

3.02

Filling Ratio

Not to exceed 0.667 percent

3.03

Discharge Duration

10 to 20 sec (Actual: 18 sec approx)

3.04

Percentage of Discharge

Not Less than 9 5 % (Actual: 97.5% approx)

3.0 5

Temperature Range

-30 C to +55 C

3.06
3.07

Hydrostatic Stretch Test


Leakage test

At 250kgf/cm2
By Dipping in water for 2 min. leakage to checked

3.08

Discharge Hose Test

3.09

Intermittent Discharge test

Burst pressure of 27 5 kgf/cm2 in controlled discharge and 140


kgf/cm2 without controlled discharge
Discharge not less than 95%

4.00

Dimensions

4.01

Maximum Diameter of Fire


Extin uisher

14010 mm.

4.02

Overall Height of Extinguisher

960 mm (Approx.)

4.03

Shell thickness

4.5mm

Kanadia Fyr Fyter Pvt Ltd


"KAN EX"
IS 2878:2004
Trolley Mounted Type
Yes
10 Nos.

ection
s
IV

,,,.

ganga

EfKC, Sandra (East),Mumbai -

si

K~NEX
4.04

TECHNICAL DATASHEET FOR C02


TYPE FIRE EXTINGUISHER OF
CAPACITY 6.5 KG

I Full weight of cylinder

KANADIA FYR FYTER PVT. LTD


(An ISO 9001:2008 Certified Company)

I 21 to 23 kg (Approx)

5.00

Color Of Extinguisher body

Painted With Durable Enamel PO red shade No.538 of IS:5

6.00

Accessories (brackets & screws)

Provided

7.00

Miscellaneous

7.01

Inspection & Testing

As per approved GTP

7.02

Finish

PO Red as per IS : 5 (Shade 538)

7.03

Marking

As per IS 2878:2004

7.04

Approvals

BIS & CCOE (PESO)

7.05

Maintenance, Care and Refilling

As per IS 2190

8.00

Packing

Jute Bags (Length:1270 mm Width:254mm)

Fl

\)\

''ANO,,O COOE
TYPE OF EXTINGU IS HER

TROLLEY MOUNTED TYPE

03.

EXTINGU ISH ING MEDIUM

co, - OF PUR ITY 99.5%

I CAPAC ITY

OS.
06.

FILLING RA TIO

I DISCHARGE DURATIO N

IL
t- .\

ol

,,;-;

NOT TO EXCEED 0.667

104\-

c\)

l'
r

08.

TEMPERATURE RANGE

09.

HYDROSTATIC STRETCH
TEST

AT250 KGF/CM'

Bl

960MM (A PPROX)

FfNISH

P.O. RED TO S HADE


N0.538 OF IS : s

I MARKING

,)
,

COTTER PfN

I M.S

I ACCESSORIES

I I.

NUT/BOLT

10.

TROLLEY Wll EEL

SO LID RUllllER

09.

TROLLEY

M.S.POWDER COATED

08.

SEAL

LEAD

07.

SA FETY PfN HO LDER

PVC

06.

SAFETY PfN

S.S.

OS.

S I PHON E TUBE

ALUM INUM CON FIRM TO IS :738

04.

DISCHARG E HOSE

WIRE BRAIDED I MTR. ID- 10 MM.


HA V fN G BURSTING PRESS URE
S HALL 275 KGF/CM' IN CO NTROL
D ISCHARGE AND 140 KGF/CM'
WITHOUT CONTROL DISCHARGE

CONF IRMS TO

I DI SCHARGE VALVE
(WHE EL TYPE)
ODY

llcm Dcscriplion

c....
<(

-(ID

@)--

0
<D
01

11

- -

V>

J1J

JQrnrri

Malcria ls of Co nstructions

MSETCL
CONTRACTOR

gineer (D&E-S2)

Mis SHAH CONSTRUCTrONS

Projects ~ Design Section

PO.No.

M.S.E.T.C.L. "Prakashganga"

ITITL E

B KC, Sandra (East),Mumbal - 51

rs : 3224

SEAMLESS MANGANESE
STEE L - IS i l!m MARKED
CONFIRM S TO IS:728S

t:
t

CLI ENT

I NON CONICITY
DUCTOR OF
POL YETI IYLENE
1

Sr.No

____

-(10\

ELECTR

OJ. J

AS PER IS:2878,Cl.IO.O

Al

''

ll

TOTAL HEIGHT

02.

"\

0140 10MM OD (APPROX)

12.

03 . I DISCHARGE llORN

--(

( I\

11

II.

12.

(13- - -{08)

{05)

1
C 1

,-..

[~1

I 0 - 20 SEC.

I D IA OF BODY

102 >-

/"

NOT LESS THAN 95%

13.

-{07)

6. 5 KG (BY WE IG HT OF
EXTfNGU IS I ll NG CHARGE)

-30C TO +55C

10.

_-.j! J-

(06 >-

1'-4

PERCENTAGE OF
DISCHARGE

07.

10

AS PER IS: l5222

EI

IS 2878 : 2004

02.

04.

--

DESIGN DATA

Oi-j

00.00.~0t

APP'D A. Shnh
: HK'DS NC
DR'N RNG

00.00.00
00.00.00 oo.00.oo
00.00.00 00.00.00

Date

Rcv.DL

Qty. IO Nos.
1 i2 .08.14i
I 2.08.14
12.08. 14

Description

XXX Name Sign. Date

l
oJ
lD Kft. N EX

PROJECT

I 32/33kV NIMBONI SUBSTATION


1-o t oR-G N
. 0.

,'.Y,'.,N..,~1t: ..:.,r~ FYTER PVTL


~~~~~~~~~~~;\~:;.s~i~~:i~t!:~JSuA l'IJl

SEC/PO/ I 5- 16/04

C0 2 TYPE FIRE EXTINGUISHER


OF CAPACITY 6.5 KG.

KFPL/GAD/H/SHP/C/6.5

Sca le NT.bl
Project
SI
lCet REV.
t or
00

O@J

1Q S IZ E - A4

Kanadia Fyr Fyter Pvt. Ltd.

F/QAC/01

QUALITY PLAN FOR INSPECTION (AS PER IS 2878: 2004)


MANUFACTURERS NAME & ADDRESS
Plot No. 8 Pa ras Indus trial estate
Near Ga ribs ha Pir.
Di strict Bhavnagar

CLIENT: MSETCL

ITEM: 6.5 KG CAPACITY C02 TYPE FIRE EXTINGUISHER

Ka nadia Fyr Fyter Pvt. Ltd.,

PROJECT: 132/33kV NIMBONI SUBSTAT ION


PO.NO : SEC/ P0/15-16/04
CO NTRACTOR : M/s SHAH CONSTRUCTIONS

QP. NO. : KFPL/QP/P/SHP/C/6.5


REV.: 00
Page: 1 ofl

Sihor(Gujarat)-364 240
SR.NO.

MOC& TESTS

CHARACTERISTICS

EXTENT OF CHECK
(INTERNAL)

REF. DOCS

ACCEPTANCE
NORMS

FORMATS OF
RECORDS

1
A

AGENCY
p

RV

REMARKS
10

Raw Material

Body

Vi s ua l a nd Dim e ns ional

R/ MTC

IS: 7285

IS: 7285

MTC

--

Va lve

Vis ua l and Dim e ns ional

R/ MTC

IS: 3224

IS: 3224

MTC

--

Hose

Burst Press ure

1 Pe r Lo t

As pe r IS: 2878

As pe r IS: 2878

MTC/llR

--

MTC

--

C02 Gas

Quality of Gas

R/ MTC

Purity as per IS : Purity as per IS :


15222
15222

Syp hon Tub e

Chem ical

R/ MTC

IS : 738

IS: 738

MTC

--

Hydro Test

Hydro Test

R/MTC

IS : 7285

IS: 7285

MTC

--

!S: 2878/2004 CI.9.1 llR

--

1 Per order qua ntity


for Witness

IS:2878/2004 Cl.9.3 llR

--

1 Pe r order qua ntity


for Witness

llR

--

Performance Test

Duration,% discharge

1 Per Lot

IS:2878/2004
Cl.9.1

Leakage Test

Lea kage Test

1 Per Lot

IS:2878/2004
Cl.9.3

Visual Inspection

Pa inting

Vis ual

1 Per Lo t

IS:2878/2004 CI IS:2878/2004
8.1
8.1

Marking

Marking

1 Per Lot

IS: 2878/2004 Cl IS: 2878/2 004


11
CI 11

llR

--

Accessories

Whee l Carriage

1 Pe r Lot

Mfrs. Standard

Mfrs. Standard

---

--

--

--

CI

BIS Approval

Sta tutory require me nt

Va lid BIS Approva l Certificate will provided a t the time of Inspection

C.C.E Nagpur Approval

Statutory requirement

Th e C.C.E. Nagpur a pprova l Certificate will be provided a long w ith s upply

MFGR: SURESH CHAKRASAL! Engg. (Prod.&QC)

f0

APPROVED BY:

/ \

~ RdVED

<
,._,....

SIGN

LEGEND FOR INSPECTION

Ex

SIGN

I
I

11th

t,..,tc:r

(O&E-S2)

Project s & D es ign Section


M.S.E.T.C.L "Prakashg a ng a "

KC, R andm (East),Mumbai - 51

1. CLIE NT /TPI

P: PERFORMING

MTC: MATERIAL TEST CERT IFI CATES

2. KANAD IA

W: WITNESS ING

llR: INTERNAL IN SPECT ION REPORTS

RV : REVIEWING

10

ALL UI M l::NSIUN AKI. I N

M~ t

OTll l::KW ISI:: IN IJ ICATEU.

1258.0 2.0

Part/Item C ode :- KM - 4UU

~
l ~ Pipe"' 1' ~

l~~~~~~~~__:w.c .D..5!bQ.

M.S.Sq Pipe

Detail - A

20x20x2mm

~J

Jl.fLCJ.!ULLJ06 0 1.0_J--r-"

M.~

uo.~

t!60.2mm

Detoil -C

1258 ugQ

'

1/ 4" BSP
Femole Nut

~s;~~
x2Nos.

:ill
...

c
,~. Sq

Pipe

25x25x2mmx2Nos

3 D VIEW

I I

a ou o

11

,.,,0
L 3B2.~

FRONT VIEW

M.S.Plote

50x50x5mmx4Nos.

SIDE VIEW
CLI ENT

.t:IQIE....;::.

EXAMPLE :-

CO NTRACTO R

-82)

M/s SHAH -CON STRU CTION S

Projects & t esign Section

PO.No.

M. S.E.T. C .L. "Prakashganga"


0

oo. oo.o:~ojoo.oo.~
o -

Date Rev.Dt

Qty. 06 Nos.

TITLE

SEC/ P0/ 15-16/04


BUCKET STAND FOR 4 BUCKET

S andra (East),Mumbai - 51

~~ ~ ~23.08.14]

00.00.00 00.00.00
00.00.00 00.00.00

MSETCL

ALL M.S.PIPE REQUIRED HOLES


~MM AT START POINT o!c END POINT

OF

If

DJ

ru KftN Ex

PROJECT

23.08.14 1
132/ 33 kV NIMBONI SUBSTATION
23.08.1 4 , KANAO IA FYR FYTER PVT.LTD ORG.No.

Desc ription

sign. j

oate

KF PL/BST/009

1 y:~J:"~~~~~~~~:~~:~~.~:~~~~:r.%~~1.lS111, ~R.
7

-I A

Scale
P~ojec

O @>

Sheet

REV.

of l

NTS

00

1Q SIZE-A4

You might also like