Professional Documents
Culture Documents
a r t i c l e
i n f o
Article history:
Received 26 August 2015
Received in revised form 3 June 2016
Accepted 9 June 2016
Available online 15 June 2016
Keywords:
Energy savings
Daylight control system
Lighting
Monitoring
School buildings
a b s t r a c t
Daylight control systems, which automatically adjust the articial light levels depending on the daylight
penetration, can result in substantial energy savings. However, their energy saving potential cannot be
estimated accurately because it depends on several building and system parameters, climate conditions,
occupant behaviour and type and commissioning of the daylight control system. The objective of this
paper is to compare the energy saving potential and operation of different daylight control systems in
school buildings. One year monitoring has been carried out simultaneously in 3 neighbouring classrooms,
equipped with a different type of control system. The active power and the electric energy consumption
of the articial lighting were measured continuously on a minute-by-minute basis, as well as the occupancy of the classrooms and the global irradiance outside the building under an unobstructed horizon.
Momentary visual comfort assessments were carried out in the classrooms.
Although all classrooms have comparable occupancy and identical building characteristics, differences
between the annual energy savings of the different daylight control systems are found to be signicant:
the total annual energy savings varied from 18% to 46%. Under the given conditions, the open loop system
with the outward facing daylight sensor was noticed to yield the largest while the closed loop system
with centrally positioned sensor produced the smallest savings. However, it has to be made sure that the
energy savings are not at the expense of the visual comfort. The performance of the systems regarding both
energy savings and visual comfort is related to the operation and the initial commissioning. An in-depth
analysis of the monitoring campaign is discussed to explain the differences in energy savings and visual
comfort. The energy savings due to the implementation of a daylight control system are divided into on
the one hand dimming due to daylight penetration and on the other hand initial dimming to compensate
for the over dimensioning of the lighting system and to take into account constant illuminance control.
2016 Elsevier B.V. All rights reserved.
1. Introduction
Lighting is estimated to represent on average 40% of the total
electrical consumption in ofce buildings [1] and can amount to
70% of the total electrical consumption in school buildings without
mechanical ventilation [2]. Besides the replacement of the luminaires, lighting control systems can be installed to decrease the
energy consumption while preserving the visual comfort. Although
many different lighting control systems are available, it is rather difcult to quantify their energy saving potential. This is particularly
the case for photosensor-controlled electric lighting systems (hereafter called daylight control systems), which automatically adjust
Corresponding author.
E-mail address: Hilde.Breesch@kuleuven.be (H. Breesch).
http://dx.doi.org/10.1016/j.enbuild.2016.06.033
0378-7788/ 2016 Elsevier B.V. All rights reserved.
970
Table 1
Classroom characteristics.
Walls
Ceiling
Floor
Window
(%)
A (m2 )
LT
37
79
12
85.26
71.64
71.64
11.18
0.78
971
972
Table 2
Characteristics of general lighting.
Classroom 1
Classroom 2
Classroom 3
TL5 HE 25 W
80% +
4000 K
94%
9
2
486 W
572 lx
1.19 W/(m2 .100 lx)
TL5 HE 25 W
80% +
4000 K
94%
9
2
531 W
572 lx
1.30 W/(m2 . 100 lx)
TL5 HO 54 W
80% +
4000 K
95%
9
1
540 W
478 lx
1.58 W/(m2 . 100 lx)
Total measured power load is the maximum measured power load when the articial lighting is not dimmed.
(1)
Light on time Ton is dened as the time that the users of the
classrooms need articial lighting during their presence (i.e. when
the lighting is switched on manually). WL,withDCS in Eq. (1) is the
energy consumption monitored by the single-phase energy meters.
WL,withoutDCS in Eq. (1) is the theoretical energy consumption of the
articial lighting during light on time if no daylight control system
would have been installed. It is calculated as the product of the
total measured power load (of the full lighting system or of a single
luminaire row) and the light on time Ton .
The energy savings due to the implementation of a daylight
control system can be divided into 2 parts: energy savings due to
(1) initial dimming without daylight W%initial and due to (2) daylight penetration W%daylight . Initial dimming is used to compensate
for the over dimensioning of the lighting system and to take into
account constant illuminance control [24]. Eq. (1) is consequently
rewritten as Eq. (2) where Pboundary is dened as the average power
973
Table 3
Characteristics of daylight control systems.
Type
Open loop/closed loop
Control system (communication)
Number of different dimming levels
Power loss
Classroom 1
Classroom 2
Classroom 3
WL,without DCS
100
(2)
Table 4
Schedule of classrooms.
Time period
Activity
8h35
8h359h25
9h2510h15
10h1510h25
10h2511h15
11h1512h05
12h05
12h0513h05
13h0513h55
13h5514h45
14h4514h55
14h5515h45
15h45
15h4516h35
16h35
Table 5
Major holidays (based on calendar year 2014).
Holiday
Duration
Period
Christmas holidays
Spring half-term
Easter holidays
Summer holidays
Autumn half-term
2 weeks
1 week
2 weeks
2 months
1 week
974
Table 6
Monthly energy consumption, light on time and occupancy in the 3 classrooms.
Energy consumption (kWh)
December 13
January 14
February 14
March 14
April 14
May 14
June 14
July 14
August 14
September 14
October 14
November 14
Total
Occupancy (h)
Classroom 1
Classroom 2
Classroom 3
Classroom 1
Classroom 2
Classroom 3
Classroom 1
Classroom 2
Classroom 3
15.1
32.5
30.6
16.6
7.1
16.3
7.5
0.1
0.4
19.8
19.1
26.8
192.0
24.3
36.7
33.9
16.2
7.4
22.1
11.1
0.0
0.3
29.7
28.7
41.9
252.3
15.6
25.6
26.5
8.7
1.0
6.4
2.6
0.0
0.0
18.5
26.7
34.0
165.7
41.7
86.0
88.5
57.2
28.9
66.3
32.8
0.3
1.6
71.7
55.1
72.8
602.9
50.6
79.2
77.8
39.0
19.8
55.5
27.3
0.0
0.7
73.1
68.6
88.7
580.2
43.7
68.7
79.7
49.6
13.3
50.2
15.7
0.0
0.5
90.4
72.6
82.2
566.6
45.7
95.2
101.7
72.0
36.2
98.1
57.7
0.0
1.1
109.6
81.5
94.3
793.1
57.0
103.5
108.0
65.2
30.8
96.0
49.7
0.0
1.5
114.5
81.4
98.6
806.1
51.2
87.1
96.1
71.6
35.9
76.7
49.7
0.0
0.8
113.0
80.3
93.1
755.4
4.2. Operation
The results of the energy savings can be explained by evaluating the operation of the different daylight control systems. Fig. 6
shows the cumulative frequency of occurrence of the power on
luminaire rows A and B in the 3 classrooms in May 2014 during Ton .
It is clear that the closed loop system with a centrally positioned
daylight sensor (classroom 2) has a peculiar behaviour compared
to the other daylight control systems. The active power (derived
from the measured energy consumption) of row B in classroom 2
has a narrow spread close to 100% of the total power load: 92% of
the power measurements have a value between 85% and 100% of
the total power load. This implies that the daylight control system
dims this luminaire row very limited in real terms. The same result
is expected for luminaire row C. Despite the fact that the energy
savings of row A in classroom 2 seemed to be normal compared
to the gained energy savings in classrooms 1 and 3, Fig. 6 shows
that the daylight control system does not behave like a continuous
dimming system. 75% of the power measurements of row A in classroom 2 occurred between 19% and 22% of the total power load. The
daylight control system thus generally adjusts its dimming level
to the minimum level of the system, although it was expected to
work as a continuous dimming system. Due to the initial decision
to observe the operation in real circumstances, it is impossible to
explain if this problem is caused by possible malfunctioning of sensor or controller, or less efcient control-strategies or sub-optimal
parameter choice during initial commissioning.
The daylight control systems in classrooms 1 and 3 can be classied as continuous dimming systems. In row B of classroom 1 for
example, where each luminaire is equipped with a daylight sensor,
all dimming levels between 35% and 70% occur more or less in the
same frequency during the examined period. However, in classroom 3 with outward facing daylight sensor, the luminaire rows
A and B switch off at high daylight levels causing a large leap at
0% power load. In addition, a minimum power load for dimming
is clearly determined for all systems. In classroom 1, the minimal
power of row A amounts to 26% of the total power load. In classroom 3, the minimum level for rows A and B is 20% of the total
power load.
Henceforth, the analysis is concentrated on the obtained measurement results of the lighting system of classroom 1 and 3.
Seasonal differences in energy savings are explained in Fig. 7
by comparing the operation of the daylight control system with
individual daylight sensor per luminaire between January and May.
A large effect of the availability of daylight exists on the power
occurrence of all luminaire rows. The differences are the largest for
975
Table 7
Annual lighting energy consumption and energy savings, divided in initial savings and daylight savings in classroom 1 and 3.
Total
Row A
Row B
Row C
Total
Row A
Row B
Row C
Total
Row A
Row B
Row C
Classroom 1
Classroom 3
192.0
59.6
55.3
77.1
56.4
15.1
29.5
11.8
44.6
23.0
12.8
8.8
165.8
50.3
50.7
64.8
41.3
1.5
24.7
15.1
97.4
49.7
26.1
21.6
Fig. 6. Cumulative frequency of occurrence of power of luminaire rows A and B in the 3 classrooms in May 2014 during light on time.
initial dimming and dimming due to daylight penetration is illustrated for classroom 1 in Fig. 8. It shows the course of the power
of all luminaire rows and of the global irradiance during 1 day in
December 2013. The power of row B (in the middle of the room)
is lower than the power of the other 2 rows when the daylight
availability is limited at the start of the lessons due to more initial dimming. As the daylight level rises in the morning, the power
of row A (at the window side) responds the most to the increasing
irradiance. Once a certain global irradiance is exceeded (in this case
around 09:25 a.m.), the power of row A is lower than row B (and C)
due to more daylight penetration on the window side.
Table 7 denes the annual energy savings due initial dimming
and daylight dimming compared to the monitored lighting energy
consumption during light on time Ton for all luminaire rows in
classroom 1 and 3. Furthermore, the total energy consumption and
energy savings are mentioned. Large energy savings due to initial
dimming are noticed for row B in both classrooms. Contrary, row
A has larger total energy savings due to daylight dimming in both
classrooms. This results in classroom 1 in larger energy savings for
row B (i.e. 42.3 kWh) than row A (i.e. 38.1 kWh) and in classroom 3
in equal savings (about 51 kWh) for row A and B (see also Fig. 5).
The effect of daylight availability during the year on the division
in initial and daylight savings for each luminaire row in classroom
1 is shown in Fig. 9. Based on the denition in Eq. (2), the initial
savings for each row are nearly constant throughout the year. On
the contrary, the daylight savings depend on the season, with much
larger daylight savings in spring/autumn than during winter.
976
Fig. 7. Cumulative frequency of power of the 3 luminaire rows in classroom 1 in January and May during light on time.
Fig. 9. Lighting energy savings, divided in initial savings and daylight savings, in classroom 1 (per luminaire row per month).
4.4. Illuminance
The results of the energy savings have to be related to the
obtained visual comfort, in particular to the illuminance level on
the workplane in the classrooms. Table 8 shows momentary measurements of the illuminance at workplane height in all classrooms,
averaged per luminaire row. Two scenarios are considered: (1) only
977
desired 500 lx. These high illuminance values are in line with the
low energy savings on Fig. 5 and high power loads during operation
on Fig. 6. In classroom 3, the measured illuminance without daylight approaches the target value of 500 lx for all rows. However,
row B and C are dimmed to extreme low values in scenario with articial lighting and daylight. The average values are 302 and 340 lx
respectively, which conrms that the dimming curves of rows B
and C are too steep. This result puts the large energy savings of row
978
Table 8
Illuminance (lx) on workplane height, measured on 25/09/2014 between 18h30 and
19 h.
Classroom 1
Classroom 2
Classroom 3
Articial lighting
Articial lighting + daylighting
Articial lighting
Articial lighting + daylighting
Articial lighting
Articial lighting + daylighting
ErowA (lx)
ErowB (lx)
ErowC (lx)
469
826
711
726
537
635
513
589
858
945
536
302
528
553
775
913
507
340
979