Professional Documents
Culture Documents
Gate Valve
Gate Valve
Gate Valve
Low Level
High Level
Feed Flow
Rejection
Wells
Pressure
Switch
Digital Flowmeter
Low Level
RFeed Flow
Pressure
Switch
Reject Flow
F
F
Digital Flowmeter
RO System
Second Stage
Pressure switch
Cut power of Pumping Sys.
If pressure reach to 1 bar
And cut also if pressure reach
to 30 bar
HP Pump
50 m3/hr @30bar
Power 45 KW
Insert Service After 60 sec from
Booster Pump Started
Booster Pump
50 m3/hr@5bar
Powered
Valve
Opened after
Sensor Flow in green mode
Digital Flowmeter
Digital Flowmeter
Reject Tank
Permeate Flow
Permeate Flow
High Level
Low Level
RO System
First Stage
Pressure switch
Cut power of Pumping Sys.
If pressure reach to 1 bar
And cut also if pressure reach
to 20 bar
Feed Flow
HP Pump
150 m3/hr@25 bar
Power 160kw
Works by VFD
280KW
Powered
Valve
Opened after 40sec
From Feed Pump loaded
Feed Tank