Flow Sheet for Sizing Air Supply Outlet


Find the room total air
volume
(CMH)

Base on Formula
Q =
qs
(CMH)
0.288
Room Shape / Layout
Ceiling Type / Shape
Matching with the lighting
Interior Design Requirement
Installation Height (Throw)

Decide the type of Air


Supply Outlet .
(Refer to page 33 & 34 for
Type of Air Supply Outlets.)

* Note (1)

Decide the Number of Air


Supply Outlet

Check the Air Volume


(change the No. of
outlet)

Decide on the Throw /


Radius of diffusion

Limit the Air Outlet


Velocity/Neck Velocity
Refer to page () ,table ( )
* Note (3)

Change
the Air
Velocity

NO
Wthin permissible/specified
Noise Level?
YES

NO
Is Air Volume for each outlet O.K ?

catalogue/technical data,, define


the size of air supply outlet
Confirm the Static Pressure Loss

Note (1) :
Within same system, preferable to use same
type of air Supply outlet.
In case different type of Air Supply Outlets
are used, standardized the Static Pressure
Loss for each outlet. (0.8 ~ 1.8 mm Aq)

COMPLETE
D

Note (2) :
Some manufacturers catalogue /
technical data, the installation height of
grille is based on 2.7m. Do correction if
necessary.

Note (3) :
If base on this Air Velocity, there will
not have any noise problem.

YES