Site Inspection MR508185 Lukaya Tower Strengthening
Site Inspection MR508185 Lukaya Tower Strengthening
Date: 11.06.2015
Site ID: MR508185
Site Name: Lukaya
Co ordinates:
Vendor:
Sub-Contractor: Jarlso
Site Supervisor: Martin
Eaton Engineer:
Emmanuel
Lat:
Long:
Observations
Newly installed bolts: M12 bolts are Grade 4.6 instead of the
required Grade 8.8
Newly installed M12 bolts not painted. Secondary horizontals with
undercoat but no final paint touch up done
Two Missing M20 bolts at joint of section 2 and 3 Contractor left on
site mobilizing to install
Torque test not done on some bolts due lack of ``accessibility`` arising from the nature of installation (Last two Photos)
Photos
Page 1 of 3
Newly installed bolts: Some M12 bolts are Grade 4.6 instead of the
required Grade 8.8
Two Missing M20 bolts at joint of section 2 and 3 Contractor left on site
mobilizing to install
Page 2 of 3