VSD PDF
VSD PDF
and Application
Application Guide AP04014005E
Introduction
ac Line
ac/dc
Converter
Filter
Inverter
Motor
Speed
Voltage
Regulator
Frequency
Control
Line-toNeutral
Voltage
ac
Line
Diode Bridge
Rectifier
Filter
Inverter
Motor
Speed
Reference
Voltage and
Frequency Control
EATON CORPORATION Cutler-Hammer AC Drive Theory and Application Application Guide AP04014005E Effective: May 2008
Line-to
Neutral
Voltage
Line
Current
XL = 2 f L
Where L = inductance
XL = reactance
Percent
Torque
200
Pull Out or
Breakdown
Torque
V = voltage
Im = magnetizing current
Im
V
= -----XL
Locked Rotor
or
Stall Torque
100
Operating
Point
Load Torque (Friction)
1
V
I m = ------------------------- --2fL f
For steady-state operation, a constant volts per hertz ratio must be
maintained. This is equal to the motor rated voltage divided by the
rated frequency.
Example: 460 volt motor
60 hertz
Slip
10
20
30
40 50 60 70
Percent Speed
80
90
100
Operating Speed
Synchronous Speed
FIGURE 5. NEMA DESIGN B MOTOR SPEED/TORQUE CURVE
EATON CORPORATION Cutler-Hammer AC Drive Theory and Application Application Guide AP04014005E Copyright 2008
Ignored
Compensated for by the drive based on motor current and a
programmed speed-torque characteristic of the motor
Compensated for by a control loop external to the drive. An
example would be a pump where a certain flow rate is desired.
The flow control loop tells the drive to either speed up or slow
down to reach the desired flow. The actual speed of the pump
has no importance.
Percent Torque
300
200
Air Gap
Voltage
100
0
0 2
Motor
Terminal
Voltage
10
20
30
40
50
60
Frequency - Hz
FIGURE 6. FAMILY OF IDEAL SPEED/TORQUE CURVES
EATON CORPORATION Cutler-Hammer AC Drive Theory and Application Application Guide AP04014005E Effective: May 2008
Soft Start
Constant V/Hz
(Constant Torque)
Operating Range
500
Percent Torque/ Percent Current
Current
Torque
400
Constant V/Hz
(Constant hp)
Operating Range
Intermittent Torque
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
Hor
sep
Tor
qu
owe
p
se
Ho
20
300
40
60
80
100
120
200
100
Load Characteristics
Most loads are divided into two categories:
0
0 2
10
20
30
40
Frequency - Hz
50
60
120
100
Percent Torque
If the motor is line started, we can see from Figure 8 that the current
inrush will be approximately 600% of full load current. We can also
see that at the 2 Hz curve we are already on the solid portion of the
curve at start. This means that if a motor is started at 2 Hz or less we
will not require a high starting current. If we start at a low frequency
and then increase speed by increasing frequency, the motor will
always operate on the solid portion of the curves and never require
more than 150% of rated current.
80
60
40
Motor Sizing
20
20
40
60
Percent Speed
80
100
EATON CORPORATION Cutler-Hammer AC Drive Theory and Application Application Guide AP04014005E Copyright 2008
220
200
180
160
Percent Torque
140
120
100
4-Pole Motor Continuous Torque
80
60
40
Torque for 6-Pole motor is based on percent of rated torque of 4-Pole motor of the same
hp rating. Rating torque of 6-Pole motor is 1.5 times of rated torque of same hp 4-Pole motor.
20
0
0
10
20
30
40
50
60
Frequency (Hz)
80
70
1800 RPM
4-Pole Motor
90
1800 RPM
6-Pole Motor
120
110
100
Percent Torque
90
80
70
60
50
0
10
20
30
Frequency
40
50
60
This is usually not a problem for fan or pump applications, since the
load is very small at light loads.
EATON CORPORATION Cutler-Hammer AC Drive Theory and Application Application Guide AP04014005E Effective: May 2008
AC Drive Application
120
100
Percent Torque
Most modern AC Drives are designed for use with various voltages
and frequencies. By adjusting the V/Hz properly, almost any 3-phase
motor can be used.
60
Output Current
40
20
0
0
20
40
60
80
120
100
Percent Speed
140
160
180
200
AC drive full load currents are matched to typical full load motor
current ratings as listed in NEC Table 430-150. Usually an AC drive
can be matched to an AC motor by their hp ratings, however, actual
motor current required under operating conditions is the determining
factor. If the motor will be run at full load, the drive current rating
must be at least as high as the motor current rating. If the drive is
to be used with multiple motors, the sum of all the full load current
ratings must be used, and adding up the hp ratings of the motors will
usually not provide an accurate estimate of the drive needed.
Motor Protection
The thick line is the drive+motor torque curve.
The thin line is a typical speed torque curve for a centrifugal fan or
pump. No overspeed is possible for this type of load, since the load
torque exceeds the motor torque.
Operating above rated speed requires either:
Mechanical Considerations
Operating above the motors rated speed should be carefully
reviewed.
The NEMA MG-1 Standard gives typical overspeed capabilities of
induction motors.
Motor overload protection must be provided as required by the applicable codes. Motor protection is not automatically provided as part of
all AC drives. It may be provided as a standard feature on one model
or it may be an optional feature on another.
The best means of motor protection is a direct winding over temperature protection such as an over temperature switch imbedded in the
motor windings. Direct over temperature protection is preferred
because overheating can occur at normal operating currents at
low speeds.
Most AC drives are equipped with electronic overcurrent protection,
such as I2t protection, similar to a conventional overload. Conventional overloads also may be used. In some modern drives, the I 2t
protection can be configured to protect the motor during low speed
operation.
In multiple motor applications, individual motor overload protection
must be provided even where electronic protection is provided by the
drive. In some cases, short circuit protection may be required.
EATON CORPORATION Cutler-Hammer AC Drive Theory and Application Application Guide AP04014005E Copyright 2008
AC Drive Performance
Operator Control and Interface Requirements
A means must be provided to start and stop the drive and provide a
speed reference. This may be accomplished with a simple run/stop
switch and a speed potentiometer, or by more elaborate means.
Additional functions that may be required include reversing; lights
or relays to indicate drive status; and meters to indicate operating
speed, load, etc.
Speed Range
Speed range is usually determined by the characteristics of the
motor, as the AC drive output frequency range is usually wider than
the motor range.
Speed Regulation
As most AC drives do not use encoder feedback, speed regulation is
determined by the slip of the motor. Typical slip for a NEMA B motor
provides for 3% regulation. Slip compensation circuits can be used to
improve this to about 1.0% regulation. In extreme cases, where very
close speed regulation is essential, a motor encoder can be
supplied to give 0.0l% speed regulation.
Current Limit
AC drives are equipped with current limit circuits. If current limit is
not provided, the overcurrent trip circuits will shut you down in the
event of an overload or attempting to accelerate too fast.