CALCULATION OF THE REQUIRED SEALANT BITE
ASTM C1401-02 STRUCTURAL SEALANT DESIGN CONSIDERATIONS
JOLLIBEE TOWER - Ortigas Center, Pasig City
Mechanical Property
t.tw 138.00kPa
t.hw 207.00kPa
Load Parameters
qtw 4.44 kPa
b 1500mm
tw 0.5 b 750.00 mm
Tributary width
(mullion to glass)
(mullion to glass)
*GE to provide certification for the use of their sealant for this
project.
Applied Loads
Glass to Mullion Sealant - Typical Wind
sb1.a 27.5mm
tw qtw
sb1.r
24.13 mm
t.tw
Comparing,
sb 1.a = 27.50 mm
>
sb 1.r = 24.13 mm
Since the actual sealant bite is greater than the required sealant bite,
THE SEALANT BITE IS WITHIN THE ALLOWABLE LIMIT.
tw qhw
sb1.r
26.05 mm
t.hw
Comparing,
sb 1.a = 27.50 mm
>
sb 1.r = 26.05 mm
Since the actual sealant bite is greater than the required sealant bite,
THE SEALANT BITE IS WITHIN THE ALLOWABLE LIMIT.
THUS, THE SEALANT BITE IS STRUCTURALLY ADEQUATE.