You are on page 1of 4

DEW POINT CALCULATION

OUTSIDE DRY BULB


TEMPERATURE

30

RELATIVE HUMIDITY

75

DEW POINT

25.0833774001

PIPE SIZE

INSIDE FLUID TEMP

250 MM
0.25 M
-10 C
651 KG/M3

DENSITY OF INSIDE FLUID


INSIDE FLUID VELOCITY

0.5 M/S

OUTSIDE HEAT TRANSFER CALCULATION


RADIATIVE HEAT TRANSFER COEFFICIENT

ts,tsurr
hr

303 K
4.42 W/M2K

OUTSIDE CONVECTIVE HEAT TRANSFER COEFFICIENT

INSIDE CONVECTIVE HEAT TRANSFER COEFFICIENT

hi

420.91 W/M2K

EQUATIONS USED

DEW POINT

AUGUST-ROCHE-MAGNUS
APPROXIMATION

RADIATIVE HEAT TRANSFER


COEFFICIENT

ASHRAE FUNDAMENTALS 4.2 EQ


4

INSIDE CONVECTIVE HEAT


TRANSFER COEFFICIENT

outside CONVECTIVE HEAT


TRANSFER COEFFICIENT