DORMITORIES
FSS
No:
1.6.2
Item
Provisions
Notes
1.0
TheprovisionsofNFPA101Chapter28shallbeappliedtoallDormitory
occupanciesexceptasmodifiedbythefollowingParticular
Requirements.
DORMITORIESWITHAHBABITABLEHEIGHTLESSTHAN28m
2.1
Dormitorieshavingahabitableheightof28mandlessshallnotrequire
sprinklerprotectionprovidedallofthefollowingconditionsaremet.
ApplicableCodes
and
Requirements
Exemption1
Thefloorareaperstoreydoesnotexceed2,400m2
ThebuildingconstructiontypeisTypeII(111)orbetter
Firecompartmentationbetweenguestsuites/sleepingroomsand
betweenguestsuites/sleepingroomsandcommoncorridorsshallhave
aminimumfireresistanceratingof1hourwithdoorshavingaminimum
fireresistanceratingof1hour
Anautomaticsmokedetectionsystemisinstalledthroughoutthe
building
ManualCallPoints,FireHoseReelsandportableextinguishersare
installedthroughoutthebuilding
Whereaccesstofireescapesarethroughinternalcorridors,thebuilding
hasasmokecontrolsystemdesignedtopressurizethecorridorin
accordancewithNFPA92A
2.2
SeparationofFireEscapeStairsfromotherpartsofthebuildingmaybe
reducedtonotlessthan1hourfireresistancerating.
DORMITORIESWITHHABITABLEHEIGHTGREATERTHAN28mABOVE
FIREENGINEACCESSLEVEL
3.1 Dormitorieshavingahabitableheight28mormoreshallrequirean
automaticsprinklersystemdesignedandinstalledinaccordancewith
NFPA13LightHazard,forthecorridorsandcommonspacesonly
providedallofthefollowingconditionsaremet.
Exemption2
Exemption3
Thefloorareaperstoreydoesnotexceed2,400m2
QCDFSS-1.6.2 Dormitories_Rev B3.doc
Revision B3
Page 1 of 2
DORMITORIES
Item
Provisions
1.6.2
Notes
ThebuildingconstructiontypeisTypeII(III)orbetter
Firecompartmentationbetweenguestsuites/sleepingroomsshallhave
aminimumfireresistanceratingof1hourwithdoorshavingaminimum
fireresistanceratingof1hour
Firecompartmentationbetweenguestsuites/sleepingroomsand
commoncorridorsshallhaveaminimumfireresistanceratingofhour
withdoorshavingaminimumfireresistanceratingofhour
Anautomaticsmokedetectionsystemisinstalledthroughoutthe
building
ManualCallPoints,FireHoseReelsandportableextinguishersare
installedthroughoutthebuilding
Whereaccesstofireescapesarethroughinternalcorridors,thebuilding
hasasmokecontrolsystemdesignedtopressurizethecorridorin
accordancewithNFPA92A
Prepared by:
PaulKhoo&YeoSweeKhiank
Revision B3
Date:
July28,2008