Chillers or VRF
Chillers or VRF
Efficiency Wise
Ahmed.alarouri@lge.com
What is EER ??
EER means : Energy Efficiency Ratio, ratio of the cooling capacity (in British thermal
units [Btu] per hour) to the power input (in watts). The higher the EER rating, the more
efficient the air conditioner
EER measures the efficiency of the unit at Full Load conditions
Higher EER
Less energy
consumption
Less
Electricity
cost
What is IEER ??
A newly developed measurement that evaluates the efficiency of a unitary air conditioning
or heat pump system on a seasonal basis is the IEER [integrated energy efficiency ratio]
IEER measures the efficiency of the unit at Part Load conditions, like operating the
system at 25%, 50%, 75% of its total capacity
Both!
But in real life, most HVAC systems operates at part load conditions
For Example :
Office building with 20 offices, will have different load characteristics, peak load (Full
load) will happen for short time, when the ambient is highest and occupancy is highest.
ASHRAE specified the formula :
IEER = (0.02A) + (0.617B) + (0.238C) + (0.125D)
A = EER at 100 percent net capacity at AHRI standard condition (95F)
B = EER at 75 percent net capacity and reduced ambient
C = EER at 50 percent net capacity and reduced ambient
D = EER at 25 percent net capacity and reduced ambient
Which means that the system operates only 2% of time at full load (in Average) ..
So, in general, for most applications specially the Office buildings, Hotels, Residential
apartments etc , the Part load performance is more important
Multi-V :
EER ~15
IEER ~25
Conclusion
The Multi-V can offer excellent energy efficiency, at full load, but a superb efficiency at
part load conditions