You are on page 1of 21

KINGDOM OF SAUDI ARABIA

FAKEEH COLLEGE FOR MEDICAL SCIENCES JEDDAH

Project : RENOVATION OF BUILDING No. 3


3 :

FIRE PROTECTION CALCULATION



J15-04000
Final Design Stage

TABLE OF CONTENTS
NO

page no.

TABLE OF CONTENTS

REFERENCES

ABBREVIATIONS

NOVEC 1230

CO2

15 FIRE PROTECTION HYDRAULIC CALCULATIONS

DESIGN CALCULATION SHEETS


TABLE OF CONTENT

REFERENCES

1- SASO - SAUDI ARABIAN STANDARD ORGANIZATION.

2- ANSI - AMERICAN NATIONAL STANDARD INSTITUTE.

3- UPC - UNIFORM PLUMBING CODE.

4- NPC - NATIONAL PLUMBING CODE.

5- UBC - UNIFORM BUILDING CODE.

6- ASTM - AMERICAN SOCIETY FOR TESTING AND MATERIAL.

7- ASHRAE - AMERICAN SOCIETY OF HEATING REFRIGERATION,


AND AIR CONDITIONING ENGINEERS.

8- PRACTICAL PLUMBING DESIGN GUIDE

9- NFPA -National Fire Protection Association

10- NHS Medical Gas Pipeline System

DESIGN CALCULATION SHEETS


REFERENCES
2

ABBREVIATIONS :

fps

FEET PER SECOND.

ft

FEET.

gals

GALLONS

gph

GALLON PER HOUR.

gpm

GALLON PER MINUTE.

kpa

KILOPASCAL

l/min

LITERS PER MINUTE.

L/h

LITERS PER HOUR.

lps

LITERS PER SECOND.

METER.

m2

SQUARE METER.

m3

CUBIC METER.

m3/min

CUBIC METERS/MINUTE.

m3/sec

CUBIC METERS/SECOND.

min

MINUTE

mm

MILLIMETER

pcs

PIECES

PS

PERINEAL SPRAY

psi

POUNDS PER SQUARE INCH

qty

QUANTITY

stc

STORAGE TANK CAPACITY.

J14-04800 (B08)

ABB
3

NOVEC 1230 CALCULATIONS


o

Specific Volume @ 20 C

NOTE:

0.072 m /Kg

Volume Of
Total
Design
Design Qty.of Chosen Qty.of
protected area Room Hight(m) Protected Area Concentration Novec-1230
Novec-1230
2
3
%
Calc.(Kg.)
Calc.(Kg.)
(m )
(m )

Cylinder
Capacity
(kg.)

CALC.
No.

Cylinders
No.

16

17

30

20

17

29

13

36

27.0

27

42.0

42

PROTECTED AREA

Floor

ELEC. ROOM(6-013)

SIXTH

5.175

3.2

16.56

4.7

11.36

16.0

COMM. ROOM(6-026)

SIXTH

6.975

3.2

22.32

4.7

15.31

16.0

ELEC. ROOM(6-002)

SIXTH

7.2925

3.2

23.336

4.7

16.01

17.0

GSM ROOM(6-006)

SIXTH

11.36

3.2

36.352

4.7

24.94

30.0

TV. ROOM(6-007)

SIXTH

16.64

2.6

43.264

4.7

29.68

30.0

ELEC. ROOM(5-004)

FIFTH

5.175

3.2

16.56

4.7

11.36

20.0

COMM. ROOM(5-017)

FIFTH

8.8

3.2

28.16

4.7

19.32

20.0

ELEC. ROOM(5-024)

FIFTH

7.2925

3.2

23.336

4.7

16.01

17.0

ELEC. ROOM(4-023)

FOURTH

5.175

3.2

16.56

4.7

11.36

17.0

COMM. ROOM(4-022)

FOURTH

12.7575

3.2

40.824

4.7

28.01

29.0

ELEC. ROOM(4-034)

FOURTH

5.545

3.2

17.744

4.7

12.17

13.0

ELEC. ROOM(3-050)

THIRD

5.175

20.7

4.7

14.20

36.0

COMM. ROOM(3-051)

THIRD

12.7575

51.03

4.7

35.01

36.0

ELEC. ROOM(3-004)

THIRD

6.9325

5.6

38.822

4.7

26.63

COMM. ROOM(3-006)

THIRD

23.075896

2.6

59.9973296

4.7

41.16

DESIGN CALCULATION SHEETS


NOVEC 1230

NOVEC 1230 CALCULATIONS


o

Specific Volume @ 20 C

NOTE:

0.071886 m /Kg

Volume Of
Total
Design
Design Qty.of Chosen Qty.of
protected area Room Hight(m) Protected Area Concentration Novec-1230
Novec-1230
2
3
%
Calc.(Kg.)
Calc.(Kg.)
(m )
(m )

PROTECTED AREA

Floor

ELEC. ROOM(2-048)

SECOND

7.4175

29.67

4.7

20.36

36.0

COMM. ROOM(2-047)

SECOND

13.06125

52.245

4.7

35.84

36.0

ELEC. ROOM(2-004)

SECOND

4.745

5.6

26.572

4.7

18.23

19.0

Cylinder
Capacity
(kg.)

CALC.
No.

Cylinders
No.

36

19

1
1

BACKUP SERVER ROOM


(2-006)

SECOND

11.4

45.6

4.7

31.28

32.0

32

ELEC. ROOM(G-022)

GROUND

6.58

19.74

4.7

13.54

14.0

14

1
1
1

ELEC. ROOM(G-014)

GROUND

5.585

16.755

4.7

11.49

12.0

12

ELEC. ROOM(G-011)

GROUND

5.585

16.755

4.7

11.49

12.0

12

EXISTING ELEC. ROOM

GROUND

42.7

128.1

4.7

88

88.0

88

DESIGN CALCULATION SHEETS


NOVEC 1230

CO2 CALCULATIONS

PROTECTED AREA

Total protected area (m2)

Room Height(m)

Volume Of Protected
Area (m3)

Qty.of CO2
Calc.(Kg.)

NEW TRANSFORMER
(G-029)

24.05

72.15

96

NEW MDP ROOM


(G-030)

26.04

78.12

104

24.8

74.4

99

11.18

33.54

45

33.46

100.38

134

25.89

3.3

85.437

114

=
=

1.6
1.33

EXISTING MDP
(G-027)
SCECO ROOM
(GROUND FLOOR)
EXISTING
TRANSFORMER
(GROUND FLOOR)
EXISTING
ELECTRICAL
SUBSTATION
(BASEMENT FLOOR)

NOTE:

DESIGN CALCULATION SHEETS


CO2

FLOODING FACTOR
FLOODING FACTOR

Cylinder
Capacity
(kg.)

Cylinder
Capacity CALC.No.
(Pounds)

Cylinders
No.

45.4

100

45.4

100

45.4

100

FAKEEH COLLEGE FOR MEDICAL SCIENCES


Fire Sprinkler Reports

for

FAKEEH COLLEGE OF SCIENCE

Prepared By:
ZFP

March 09, 2016

FIRE - Fire Sprinkler Hydraulics Calculation Program


El Estesharyoon Zuhair Fayez P 2023587073 202358851 Fax

Elite Software Development, Inc.


FAKEEH COLLEGE FOR MEDICAL SCIENCES Page 2

General Project Data Report


General Data
Project Title:
Designed By:
Code Reference:
Client Name:
Address:
Company Name:
Company Address:
Phone:
Building Name:
Contact at Building:

FAKEEH COLLEGE FOR MEDICAL


Project File Name:
SCIENCES
ZFP
Date:
Approving Agency:
FAKEEH COLLEGE OF SCIENCE
Phone:
City, State Zip Code:
Representative:
City And State:
FAKEEH COLLEGE FOR MEDICAL
Building Owner:
SCIENCES
Phone at Building:

FOM SPRINKLER.fiw
March 09, 2016

FAKEEH

Project Data
Description Of Hazard:
Design Area Of Water Application:
Default Sprinkler K-Factor:
Inside Hose Stream Allowance:
In Rack Sprinkler Allowance:

Ordinary 1
1500
5.60
0.00
0.00

ft
K
gpm
gpm

Sprinkler Specifications
Make:
Size:

Sprinkler System Type:


Wet
Maximum Area Per Sprinkler:
130 ft
Default Pipe Material:
SCHED 40 WET STEEL
Outside Hose Stream Allowance:
0.00 gpm

Model:
Temperature Rating:

68 F

Water Supply Test Data


Source Of Information:
Test Hydrant ID:
Hydrant Elevation:
Test Flow Rate:

Date Of Test:
0 ft
0.00 gpm

Static Pressure:
Test Residual Pressure:

0.00 psi
0.00 psi

Calculation Project Data


Calculation Mode:
System Inflow Number:
Number Of Active Nodes:
Number Of Active Pipes:
Number Of Active Sprinklers:

Supply
10.00
28
27
12

Specified Inflow Node Residual


Pressure:

118.00 psi

Number Of Inactive Pipes:


Number Of Inactive Sprinklers:

0
0

Active Version 6.0.189

1000 Pipe Capacity

Wednesday, March 30, 2016

FIRE - Fire Sprinkler Hydraulics Calculation Program


El Estesharyoon Zuhair Fayez P 2023587073 202358851 Fax

Elite Software Development, Inc.


FAKEEH COLLEGE FOR MEDICAL SCIENCES Page 3

Fire Sprinkler Input Data


Node Input Data
Sprinkler
KFactor (K)

Pressure
Estimate (psi)

Node
Elevation
(feet)

Non-Sprinkler
Discharge
(gpm)

No Discharge

N/A

118.00

0.00

0.00

20

No Discharge

N/A

68.32

98.80

0.00

25

Non-Sprinkler

N/A

66.45

94.80

50.00

30

No Discharge

N/A

66.74

94.80

0.00

40

No Discharge

N/A

57.59

94.80

0.00

41

No Discharge

N/A

48.25

94.80

0.00

42

Sprinkler

5.60

48.23

93.50

0.00

43

No Discharge

N/A

31.06

94.80

0.00

44

Sprinkler

5.60

30.47

93.50

0.00

45

Sprinkler

5.60

27.44

93.50

0.00

50

No Discharge

N/A

53.36

94.80

0.00

51

No Discharge

N/A

43.93

94.80

0.00

52

Sprinkler

5.60

43.96

93.50

0.00

53

No Discharge

N/A

27.83

94.80

0.00

54

Sprinkler

5.60

27.82

93.50

0.00

55

Sprinkler

5.60

25.03

93.50

0.00

60

No Discharge

N/A

50.40

94.80

0.00

61

No Discharge

N/A

43.39

94.80

0.00

62

Sprinkler

5.60

43.42

93.50

0.00

63

No Discharge

N/A

28.56

94.80

0.00

64

Sprinkler

5.60

28.77

93.50

0.00

65

Sprinkler

5.60

26.34

93.50

0.00

70

No Discharge

N/A

47.91

94.80

0.00

71

No Discharge

N/A

41.22

94.80

0.00

72

Sprinkler

5.60

41.28

93.50

0.00

73

No Discharge

N/A

27.09

94.80

0.00

74

Sprinkler

5.60

27.31

93.50

0.00

Node No.

Node Description

10

Area Group

Active Version 6.0.189

1000 Pipe Capacity

Wednesday, March 30, 2016

FIRE - Fire Sprinkler Hydraulics Calculation Program


El Estesharyoon Zuhair Fayez P 2023587073 202358851 Fax

Elite Software Development, Inc.


FAKEEH COLLEGE FOR MEDICAL SCIENCES Page 4

Fire Sprinkler Input Data


Node Input Data (cont'd)
Node No.

Node Description

75

Sprinkler

Area Group

Sprinkler
KFactor (K)

Pressure
Estimate (psi)

Node
Elevation
(feet)

Non-Sprinkler
Discharge
(gpm)

5.60

25.01

93.50

0.00

10

Active Version 6.0.189

1000 Pipe Capacity

Wednesday, March 30, 2016

FIRE - Fire Sprinkler Hydraulics Calculation Program


El Estesharyoon Zuhair Fayez P 2023587073 202358851 Fax

Elite Software Development, Inc.


FAKEEH COLLEGE FOR MEDICAL SCIENCES Page 5

Fire Sprinkler Input Data


Pipe Input Data
Nominal
Diameter
(inch)

Type
Group

Fitting
Data

Nominal
Length
(feet)

Fitting
Length
(feet)

SCHED 40 WET STEEL

4.000

ET

95.47

30.00

125.47

120

25

SCHED 40 WET STEEL

1.500

4E

24.93

16.00

40.93

120

20

30

SCHED 40 WET STEEL

4.000

ETGC

21.65

54.00

75.65

120

30

40

SCHED 40 WET STEEL

4.000

E6T

78.74

130.00

208.74

120

40

41

SCHED 40 WET STEEL

2.000

E5T

45.93

55.00

100.93

120

41

42

SCHED 40 WET STEEL

1.000

1.31

0.00

1.31

120

41

43

SCHED 40 WET STEEL

1.000

10.17

7.00

17.17

120

43

44

SCHED 40 WET STEEL

1.000

3.94

0.00

3.94

120

43

45

SCHED 40 WET STEEL

1.000

2E

11.81

4.00

15.81

120

40

50

SCHED 40 WET STEEL

3.000

2T

14.76

30.00

44.76

120

50

51

SCHED 40 WET STEEL

2.000

E6T

45.93

65.00

110.93

120

51

52

SCHED 40 WET STEEL

1.000

1.31

0.00

1.31

120

51

53

SCHED 40 WET STEEL

1.000

10.50

7.00

17.50

120

53

54

SCHED 40 WET STEEL

1.000

2.13

0.00

2.13

120

53

55

SCHED 40 WET STEEL

1.000

2E

9.84

4.00

13.84

120

50

60

SCHED 40 WET STEEL

2.500

11.02

12.00

23.02

120

60

61

SCHED 40 WET STEEL

2.000

E3T

45.93

35.00

80.93

120

61

62

SCHED 40 WET STEEL

1.000

1.31

0.00

1.31

120

61

63

SCHED 40 WET STEEL

1.000

10.50

5.00

15.50

120

63

64

SCHED 40 WET STEEL

1.000

1.31

0.00

1.31

120

63

65

SCHED 40 WET STEEL

1.000

8.96

2.00

10.96

120

60

70

SCHED 40 WET STEEL

2.000

2T

10.17

20.00

30.17

120

70

71

SCHED 40 WET STEEL

2.000

5ET

45.93

35.00

80.93

120

71

72

SCHED 40 WET STEEL

1.000

1.31

0.00

1.31

120

71

73

SCHED 40 WET STEEL

1.000

10.50

5.00

15.50

120

73

74

SCHED 40 WET STEEL

1.000

1.31

0.00

1.31

120

73

75

SCHED 40 WET STEEL

1.000

8.92

2.00

10.92

120

Beg.
Node

End.
Node

Pipe Description

10

20

20

ET

ET

Total
CFactor
Length (gpm/inch(feet)
psi)

11

Active Version 6.0.189

1000 Pipe Capacity

Wednesday, March 30, 2016

FIRE - Fire Sprinkler Hydraulics Calculation Program


El Estesharyoon Zuhair Fayez P 2023587073 202358851 Fax

Elite Software Development, Inc.


FAKEEH COLLEGE FOR MEDICAL SCIENCES Page 6

Fire Sprinkler Output Data


Overall Node Groupings Output Data
Pipe Segment
Beg.
End.
Node
Node

Pipe
Type
Group

Pipe
Flow Rate
(gpm)

Sprinkler Flow
At Beg. Node
(gpm)

Non-Sprinkler Flow
Out (+)
In (-)
(gpm)
(gpm)

Beg. Node
Residual
Pressure (psi)

Imbalance
Flow At Beg.
Node (gpm)

10

20

432.75

0.00

0.00

-432.75

118.00

20
20
20

10
25
30

0
0
0

-432.75
50.00
382.75

0.00

0.00

0.00

68.32

0.00000

25

20

-50.00

0.00

50.00

0.00

66.45

0.00000

30
30

20
40

0
0

-382.75
382.75

0.00

0.00

0.00

66.74

0.00000

40
40
40

30
41
50

0
0
0

-382.75
99.14
283.61

0.00

0.00

0.00

57.59

0.00000

41
41
41

40
42
43

0
0
0

-99.14
38.89
60.25

0.00

0.00

0.00

48.25

0.00000

42

41

-38.89

38.89

0.00

0.00

48.23

0.00000

43
43
43

41
44
45

0
0
0

-60.25
30.91
29.33

0.00

0.00

0.00

31.06

0.00000

44

43

-30.91

30.91

0.00

0.00

30.47

0.00000

45

43

-29.33

29.33

0.00

0.00

27.44

0.00000

50
50
50

40
51
60

0
0
0

-283.61
94.68
188.93

0.00

0.00

0.00

53.36

0.00000

51
51
51

50
52
53

0
0
0

-94.68
37.13
57.55

0.00

0.00

0.00

43.93

0.00000

52

51

-37.13

37.13

0.00

0.00

43.96

0.00000

53
53
53

51
54
55

0
0
0

-57.55
29.54
28.02

0.00

0.00

0.00

27.83

0.00000

54

53

-29.54

29.54

0.00

0.00

27.82

0.00000

55

53

-28.02

28.02

0.00

0.00

25.03

0.00000

60
60
60

50
61
70

0
0
0

-188.93
95.68
93.25

0.00

0.00

0.00

50.40

0.00000

61
61
61

60
62
63

0
0
0

-95.68
36.90
58.77

0.00

0.00

0.00

43.39

0.00000

Active Version 6.0.189

12

1000 Pipe Capacity

Wednesday, March 30, 2016

FIRE - Fire Sprinkler Hydraulics Calculation Program


El Estesharyoon Zuhair Fayez P 2023587073 202358851 Fax

Elite Software Development, Inc.


FAKEEH COLLEGE FOR MEDICAL SCIENCES Page 7

Fire Sprinkler Output Data


Overall Node Groupings Output Data (cont'd)
Pipe Segment
Beg.
End.
Node
Node

Pipe
Type
Group

Pipe
Flow Rate
(gpm)

Sprinkler Flow
At Beg. Node
(gpm)

Non-Sprinkler Flow
Out (+)
In (-)
(gpm)
(gpm)

Beg. Node
Residual
Pressure (psi)

Imbalance
Flow At Beg.
Node (gpm)

62

61

-36.90

36.90

0.00

0.00

43.42

0.00000

63
63
63

61
64
65

0
0
0

-58.77
30.03
28.74

0.00

0.00

0.00

28.56

0.00000

64

63

-30.03

30.03

0.00

0.00

28.77

0.00000

65

63

-28.74

28.74

0.00

0.00

26.34

0.00000

70
70

60
71

0
0

-93.25
93.25

0.00

0.00

0.00

47.91

0.00000

71
71
71

70
72
73

0
0
0

-93.25
35.98
57.27

0.00

0.00

0.00

41.22

0.00000

72

71

-35.98

35.98

0.00

0.00

41.28

0.00000

73
73
73

71
74
75

0
0
0

-57.27
29.27
28.00

0.00

0.00

0.00

27.09

0.00000

74

73

-29.27

29.27

0.00

0.00

27.31

0.00000

75

73

-28.00

28.00

0.00

0.00

25.01

0.00000

13

Active Version 6.0.189

1000 Pipe Capacity

Wednesday, March 30, 2016

FIRE - Fire Sprinkler Hydraulics Calculation Program


El Estesharyoon Zuhair Fayez P 2023587073 202358851 Fax

Elite Software Development, Inc.


FAKEEH COLLEGE FOR MEDICAL SCIENCES Page 8

Fire Sprinkler Output Data


Overall Pipe Output Data
Beg.
End.
Node

Nodal
KFactor
(K)

Elevation
(feet)

Spk/Hose
Discharge
(gpm)

Nom. Dia.
Residual
Inside Dia.
Pressure
C-Value
(psi)

Q (gpm)
Velocity
(fps)

F. L./ft
(psi/ft)
Fittings
Type-Grp

Pipe-Len.
Fit-Len.
Tot-Len.
(ft)

PF-(psi)
PE-(psi)
PV-(psi)

10
20

0.00
0.00
0.00
0.00
98.80
0.00
SCHED 40 WET STEEL

118.00
68.32

4.00
4.026
120

432.75
10.91

0.05499
ET
0

95.47
30.00
125.47

6.900
42.780
0.800

20
25

0.00
98.80
0.00
0.00
94.80
50.00
SCHED 40 WET STEEL

68.32
66.45

1.50
1.610
120

50.00
7.88

0.08805
4E
0

24.93
16.00
40.93

3.604
-1.732
0.418

20
30

0.00
98.80
0.00
0.00
94.80
0.00
SCHED 40 WET STEEL

68.32
66.74

4.00
4.026
120

382.75
9.65

0.04382
ETGC
0

21.65
54.00
75.65

3.315
-1.732
0.626

30
40

0.00
94.80
0.00
0.00
94.80
0.00
SCHED 40 WET STEEL

66.74
57.59

4.00
4.026
120

382.75
9.65

0.04382
E6T
0

78.74
130.00
208.74

9.147
0.000
0.626

40
41

0.00
94.80
0.00
0.00
94.80
0.00
SCHED 40 WET STEEL

57.59
48.25

2.00
2.067
120

99.14
9.48

0.09253
E5T
0

45.93
55.00
100.93

9.339
0.000
0.605

40
50

0.00
94.80
0.00
0.00
94.80
0.00
SCHED 40 WET STEEL

57.59
53.36

3.00
3.068
120

283.61
12.31

0.09452
2T
0

14.76
30.00
44.76

4.231
0.000
1.020

41
42

0.00
94.80
0.00
5.60
93.50
38.89
SCHED 40 WET STEEL

48.25
48.23

1.00
1.049
120

38.89
14.44

0.44557
----0

1.31
0.00
1.31

0.584
-0.563
1.403

41
43

0.00
94.80
0.00
0.00
94.80
0.00
SCHED 40 WET STEEL

48.25
31.06

1.00
1.049
120

60.25
22.37

1.00139
ET
0

10.17
7.00
17.17

17.194
0.000
3.366

43
44

0.00
94.80
0.00
5.60
93.50
30.91
SCHED 40 WET STEEL

31.06
30.47

1.00
1.049
120

30.91
11.48

0.29137
----0

3.94
0.00
3.94

1.148
-0.563
0.886

43
45

0.00
94.80
0.00
5.60
93.50
29.33
SCHED 40 WET STEEL

31.06
27.44

1.00
1.049
120

29.33
10.89

0.26444
2E
0

11.81
4.00
15.81

4.181
-0.563
0.798

50
51

0.00
94.80
0.00
0.00
94.80
0.00
SCHED 40 WET STEEL

53.36
43.93

2.00
2.067
120

94.68
9.05

0.08498
E6T
0

45.93
65.00
110.93

9.427
0.000
0.552

50
60

0.00
94.80
0.00
0.00
94.80
0.00
SCHED 40 WET STEEL

53.36
50.40

2.50
2.469
120

188.93
12.66

0.12839
T
0

11.02
12.00
23.02

2.956
0.000
1.079

51
52

0.00
94.80
0.00
5.60
93.50
37.13
SCHED 40 WET STEEL

43.93
43.96

1.00
1.049
120

37.13
13.78

0.40894
----0

1.31
0.00
1.31

0.536
-0.563
1.279

1.00

57.55

0.92017

10.50

16.103

51

0.00

Active Version 6.0.189

94.80

0.00

43.93

14

1000 Pipe Capacity

Wednesday, March 30, 2016

FIRE - Fire Sprinkler Hydraulics Calculation Program


El Estesharyoon Zuhair Fayez P 2023587073 202358851 Fax

Elite Software Development, Inc.


FAKEEH COLLEGE FOR MEDICAL SCIENCES Page 9

Fire Sprinkler Output Data


Overall Pipe Output Data (cont'd)
Beg.
End.
Node

Nodal
KFactor
(K)

Elevation
(feet)

Spk/Hose
Discharge
(gpm)

Nom. Dia.
Residual
Inside Dia.
Pressure
C-Value
(psi)

Q (gpm)
Velocity
(fps)

F. L./ft
(psi/ft)
Fittings
Type-Grp

Pipe-Len.
Fit-Len.
Tot-Len.
(ft)

PF-(psi)
PE-(psi)
PV-(psi)

53

0.00
94.80
0.00
SCHED 40 WET STEEL

27.83

1.049
120

21.37

ET
0

7.00
17.50

0.000
3.072

53
54

0.00
94.80
0.00
5.60
93.50
29.54
SCHED 40 WET STEEL

27.83
27.82

1.00
1.049
120

29.54
10.97

0.26784
----0

2.13
0.00
2.13

0.571
-0.563
0.809

53
55

0.00
94.80
0.00
5.60
93.50
28.02
SCHED 40 WET STEEL

27.83
25.03

1.00
1.049
120

28.02
10.40

0.24289
2E
0

9.84
4.00
13.84

3.362
-0.563
0.728

60
61

0.00
94.80
0.00
0.00
94.80
0.00
SCHED 40 WET STEEL

50.40
43.39

2.00
2.067
120

95.68
9.15

0.08664
E3T
0

45.93
35.00
80.93

7.012
0.000
0.563

60
70

0.00
94.80
0.00
0.00
94.80
0.00
SCHED 40 WET STEEL

50.40
47.91

2.00
2.067
120

93.25
8.92

0.08262
2T
0

10.17
20.00
30.17

2.493
0.000
0.535

61
62

0.00
94.80
0.00
5.60
93.50
36.90
SCHED 40 WET STEEL

43.39
43.42

1.00
1.049
120

36.90
13.70

0.40434
----0

1.31
0.00
1.31

0.530
-0.563
1.263

61
63

0.00
94.80
0.00
0.00
94.80
0.00
SCHED 40 WET STEEL

43.39
28.56

1.00
1.049
120

58.77
21.82

0.95657
T
0

10.50
5.00
15.50

14.827
0.000
3.204

63
64

0.00
94.80
0.00
5.60
93.50
30.03
SCHED 40 WET STEEL

28.56
28.77

1.00
1.049
120

30.03
11.15

0.27624
----0

1.31
0.00
1.31

0.362
-0.563
0.837

63
65

0.00
94.80
0.00
5.60
93.50
28.74
SCHED 40 WET STEEL

28.56
26.34

1.00
1.049
120

28.74
10.67

0.25460
E
0

8.96
2.00
10.96

2.790
-0.563
0.766

70
71

0.00
94.80
0.00
0.00
94.80
0.00
SCHED 40 WET STEEL

47.91
41.22

2.00
2.067
120

93.25
8.92

0.08262
5ET
0

45.93
35.00
80.93

6.686
0.000
0.535

71
72

0.00
94.80
0.00
5.60
93.50
35.98
SCHED 40 WET STEEL

41.22
41.28

1.00
1.049
120

35.98
13.36

0.38585
----0

1.31
0.00
1.31

0.505
-0.563
1.201

71
73

0.00
94.80
0.00
0.00
94.80
0.00
SCHED 40 WET STEEL

41.22
27.09

1.00
1.049
120

57.27
21.26

0.91173
T
0

10.50
5.00
15.50

14.132
0.000
3.042

73
74

0.00
94.80
0.00
5.60
93.50
29.27
SCHED 40 WET STEEL

27.09
27.31

1.00
1.049
120

29.27
10.86

0.26329
----0

1.31
0.00
1.31

0.345
-0.563
0.794

27.09
25.01

1.00
1.049

28.00
10.40

0.24267
E

8.92
2.00

2.650
-0.563

73
75

0.00
5.60

Active Version 6.0.189

94.80
93.50

0.00
28.00

15

1000 Pipe Capacity

Wednesday, March 30, 2016

FIRE - Fire Sprinkler Hydraulics Calculation Program


El Estesharyoon Zuhair Fayez P 2023587073 202358851 Fax

Elite Software Development, Inc.


FAKEEH COLLEGE FOR MEDICAL SCIENCES Page 10

Fire Sprinkler Output Data


Overall Pipe Output Data (cont'd)
Beg.
End.
Node

Nodal
KFactor
(K)

Elevation
(feet)

Spk/Hose
Discharge
(gpm)

SCHED 40 WET STEEL

Nom. Dia.
Residual
Inside Dia.
Pressure
C-Value
(psi)

Q (gpm)
Velocity
(fps)

120

F. L./ft
(psi/ft)
Fittings
Type-Grp

Pipe-Len.
Fit-Len.
Tot-Len.
(ft)

PF-(psi)
PE-(psi)
PV-(psi)

10.92

0.727

16

Active Version 6.0.189

1000 Pipe Capacity

Wednesday, March 30, 2016

FIRE - Fire Sprinkler Hydraulics Calculation Program


El Estesharyoon Zuhair Fayez P 2023587073 202358851 Fax

Elite Software Development, Inc.


FAKEEH COLLEGE FOR MEDICAL SCIENCES Page 11

Fire Sprinkler Output Data


Overall Sprinkler Output Data
Flowing
Sprinkler
Node No.

Sprinkler
KFactor (K)

Sprinkler
Elevation
(feet)

Flowing
Density
(gpm/ft)

Sprinkler
Discharge
(gpm)

42
Sub Totals For Non-Group

5.60

93.50

48.23

107.00
107.00

0.363
0.363

38.89
38.89

44
Sub Totals For Non-Group

5.60

93.50

30.47

107.00
107.00

0.289
0.289

30.91
30.91

45
Sub Totals For Non-Group

5.60

93.50

27.44

112.00
112.00

0.262
0.262

29.33
29.33

52
Sub Totals For Non-Group

5.60

93.50

43.96

107.00
107.00

0.347
0.347

37.13
37.13

54
Sub Totals For Non-Group

5.60

93.50

27.82

107.00
107.00

0.276
0.276

29.54
29.54

55
Sub Totals For Non-Group

5.60

93.50

25.03

112.00
112.00

0.250
0.250

28.02
28.02

62
Sub Totals For Non-Group

5.60

93.50

43.42

107.00
107.00

0.345
0.345

36.90
36.90

64
Sub Totals For Non-Group

5.60

93.50

28.77

107.00
107.00

0.281
0.281

30.03
30.03

65
Sub Totals For Non-Group

5.60

93.50

26.34

112.00
112.00

0.257
0.257

28.74
28.74

72
Sub Totals For Non-Group

5.60

93.50

41.28

107.00
107.00

0.336
0.336

35.98
35.98

74
Sub Totals For Non-Group

5.60

93.50

27.31

107.00
107.00

0.274
0.274

29.27
29.27

75
Sub Totals For Non-Group

5.60

93.50

25.01

112.00
112.00

0.250
0.250

28.00
28.00

1304.00

0.294

382.75

Area Group
Code

Residual
Flowing Area
Pressure
(ft)
(psi)

Totals For All Groups

17

Active Version 6.0.189

1000 Pipe Capacity

Wednesday, March 30, 2016

FIRE - Fire Sprinkler Hydraulics Calculation Program


El Estesharyoon Zuhair Fayez P 2023587073 202358851 Fax

Elite Software Development, Inc.


FAKEEH COLLEGE FOR MEDICAL SCIENCES Page 12

Fire Sprinkler Output Summary


Hydraulically Most Demanding Sprinkler Node
HMD Sprinkler Node Number:
HMD Actual Residual Pressure:
HMD Actual GPM:

75
25.01 psi
28.00 gpm

Sprinkler Summary
Sprinkler System Type:
Specified Area Of Application:
Minimum Desired Density:
Application Average Density:
Application Average Area Per Sprinkler:
Sprinkler Flow:
Average Sprinkler Flow:

Wet
1500.00
0.100
0.255
125.00
382.75
31.90

ft
gpm/ft
gpm/ft
ft
gpm
gpm

Flow Velocity And Imbalance Summary


Maximum Flow Velocity ( In Pipe 41 - 43 )
Maximum Velocity Pressure ( In Pipe 41 - 43 )
Allowable Maximum Nodal Pressure Imbalance:
Actual Maximum Nodal Pressure Imbalance:
Actual Average Nodal Pressure Imbalance:
Actual Maximum Nodal Flow Imbalance:
Actual Average Nodal Flow Imbalance:

22.37 ft/sec
3.37 psi
0.0000
0.0000
0.0000
0.0000
0.0000

psi
psi
psi
gpm
gpm

Overall Network Summary


Number Of Unique Pipe Sections:
Number Of Flowing Sprinklers:

27
12

Pipe System Water Volume:

178.64 gal

Sprinkler Flow:
Non-Sprinkler Flow:
Total System Demand Flow:

382.75 gpm
50.00 gpm
432.75 gpm

Specified Residual Pressure At System Inflow Node:


Demand Flow At System Inflow Node:

118.00 psi
432.75 gpm

18

Active Version 6.0.189

1000 Pipe Capacity

Wednesday, March 30, 2016

FIRE - Fire Sprinkler Hydraulics Calculation Program


El Estesharyoon Zuhair Fayez P 2023587073 202358851 Fax

Elite Software Development, Inc.


FAKEEH COLLEGE FOR MEDICAL SCIENCES Page 13

Fire Sprinkler Output Data


Hydraulic Supply/Demand Graph

200
180
160

Pressure psi

140
120
100
80
60
40
20
0

0
1

10

Flowrate(x100) gpm

Adjusted Hydrant Data


Static Pressure: 0 psi
Test Residual Pressure: 0 psi
Test Flow Rate: 0 gpm

Demand Point Data


Calculated Residual Pressure: 118.00 psi
Calculated Flow Rate: 432.75 gpm
Excess Available Inflow Residual Pressure: -118 psi

19

Active Version 6.0.189

1000 Pipe Capacity

Wednesday, March 30, 2016

20

You might also like