Technical Specification For Current Transformers 1.0 General
Technical Specification For Current Transformers 1.0 General
1.0 GENERAL
1.1 This specification covers manufacture, test, & supply of LT Current transformers
of class 0.5 accuracy.
1.2 The CTs shall be suitable for metering purpose.
2.0 TYPE:
2.1 The CTs shall be of ring type or window type (bar type or bus-bar type CTs shall
not be accepted).
2.2 The secondary leads shall be terminated with Tinned Cooper rose contact
terminals with arrangements for sealing purposes.
2.3 Polarity (both for primary and second leads) shall be marked.
2.4 The CTs shall be varnished, fiberglass tape insulated or cast resin, air-cooled type.
Only super enameled electrolytic grade copper wires shall be used.
2.5 The CTs shall conform to IS 2705:Part-I & II/IEC:185 with latest amendments.
3.0 TECHNICAL DETAILS:
3.1 Technical details shall be as given below:
1.
2.
3.
4.
5.
6.
7.
Class of Accuracy
Rated Burden
Power Frequency Withstand Voltage
Highest System Voltage
Nominal System Voltage
Frequency
Supply System
0.5
5.00 VA
3KV
433 V
400 V
50 Hz
3 Ph. Solidly grounded Neutral System
3.2 Transformation ratio shall be specified from the following standard ratings as per
requirement :
Ratio
50/5
150/5
300/5
400/5
1000/5
(Secondary with 1 A may be specified by the utility incase the same is desired.)
3.3 Bore diameter of the CT shall not be less than 40 mm. Ring type CTs shall have
suitable clamp to fix the CT to panel Board, wherever required.
3.4 The limits of current error and phase angle displacement as per IS:2705 at several
defined percentage of rated current are:
Accuracy
Class
0.5
current
5
20
1.5
0.75
100
0.5
120
0.5
of rated current
5
20
100
90
45
30
120
30
DESCRIPTION
Makers Name & address
Type and capacity
Rated voltage
Highest system Voltage
Rated Primary Current
Rated Secondary Current
Rated Output
Rated continuous thermal current Temperature
rise over ambient
Power Frequency WithstandVoltage
Class of Accuracy
Material
Core
Conductor
Insulation
Base MS Zinc plated
Dimension in mm
Inner Dia. of CT
Outer Dia. of CT
Height of center of CT from base
Secondary termination
ISF
Extended primary current
150/5A