Turn Winter/Summer
selector to Summer
position.
The display is switch on.
NO
Go to section A
YES
Error 110 flashing
Error 131 flashing
Error 133 flashing
YES
YES
Go to section E
YES
Go to section C
YES
NO
Error 20, 28 or 50 flashing
NO
Error 119 flashing
NO
YES
Go to section G
YES
NO
YES
3 way valve is addressed
towards DHW circuit
NO
Go to section K
YES
Pump runs
NO
Go to section B
Error 125 flashing
YES
Fan runs
NO
NO
YES
Fan runs at correct speed
YES
Go to section L
YES
pag. 1/8
NO
YES
Go to section H
Turn the selector to reset
YES
Burner lights
NO
YES
YES
NO
Go to section F
YES
NO
YES
DHW flow sensor senses
no flow. Burner goes out
YES
YES
YES
pag. 2/8
Turn Winter/Summer
selector to Winter position.
The display is switch on.
NO
Go to section A
YES
Error 110 flashing
Error 133 flashing
YES
YES
Go to section E
YES
Go to section C
YES
NO
Error 20, 28 or 50 flashing
NO
Error 119 flashing
NO
Ensure controls are set to
demand and verify the
contacts are closed
NO
YES
NO
NO
YES
Go to section B
Error 125 flashing
Go to section K
YES
Fan runs
NO
NO
YES
Fan runs at correct speed
YES
Go to section L
YES
pag. 3/8
NO
YES
Go to section H
Turn the selector to reset
YES
Burner lights
NO
YES
YES
NO
Go to section F
YES
YES
YES
Pump continues to
run for 3 minutes
(room thermostat open)
YES
pag. 4/8
A
Check line voltage at:
1.
2.
3.
NO
NO
Replace fuse
NO
NO
Boiler working
display illuminated
Check wiring
B
Check line voltage at:
1.
Pump
YES
NO
Replace pump
NO
Replace main PCB
YES
Change pump supple cable
C
1.
YES
Re-pressurise system
NO
Check connection water
pressure switch terminal
COM NO and PCB
connector X400 terminals 3,4
2.
YES
Replace water
pressure switch
NO
Open the automatic air
D
Fan connections correct at fan.
PCB X2 connector is 230 V AC
across terminals 3,4
YES
NO
Fan jammed or
faulty winding
YES
Replace fan
pag. 5/8
E
Temperature sensors faulty.
Cold resistance
10 k @ 25C (DHW and CH sensors)
20 k @ 25C (FLUE sensor)
NO
Replace sensor
F
1.
2.
Gas at burner
NO
PCB X3 connector is
230 V AC across terminals 1,2
YES
NO
Replace main PCB
G
Check and correct:
1. the position of the electronic sensor on the
hydraulic group of the gas boiler
2. the connexion between the PCB X400
connector terminals 3,6,7 and the electronic
sensor
YES
NO
Replace main PCB
YES
Replace the
electronic sensor
H
Check and correct:
1. Ignition electrode and lead
2. Electrode connection
3. Spark gap and position
YES
NO
Voltage at main PCB X2
connector is 230 V AC
across terminals 2,5
Check wiring
YES
Replace igniter
pag. 6/8
I
Check the gas supply pressure:
1. For Natural Gas > 10-11 mbar
Check and correct:
1. the mechanical set of the gas valve
(CO2 values - see instruction)
2.
2. Flame sensing electrode and lead
connections
3. Flame sensing electrode position
YES
Flame current should be more than 0,5 A
NO
J
Overheat thermostat operated
or faulty, i.e. continuity across
thermostat terminals
YES
NO
Allow to cool.
Continuity across
thermostat terminals
more than 1,5 ohm
YES
K
Check line voltage at:
1.
2.
YES
NO
YES
Change motor supple cable
L
1.
YES
Replace fan
pag. 7/8
M
1.
NO
Replace sensor
YES
Replace exchanger
2.
pag. 8/8