Professional Documents
Culture Documents
6 Prelocation Transient Methods en PDF
6 Prelocation Transient Methods en PDF
Prelocation
Transient Methods
Contents:
1.
2.
3.
Introduction
DECAY (voltage decoupling)
ICE (current decoupling)
1.
Introduction
+Ureturn
+2U
+U
+Uinc.
cable end
cable start
The current wave which initially arrives at the cable end in phase with the voltage
wave is also reflected with the same amplitude, but with opposite polarity, so that
both current wave parts cancel each other at the cable end.
+i
+i
i-inc.
i-return
cable start
-i
cable end
The simplest and probably the oldest method is the travelling wave pre-localisation,
in short the DECAY method. For this purpose the cable is charged with direct voltage
until the voltage exceeds the breakdown voltage of the fault. The energy stored in the
cable capacitance discharges itself via the fault and creates a travelling wave that
can be measured as damped (decaying) oscillation. The length of this oscillation
contains the distance to the fault; but it also includes test leads. During this process
the signal is decoupled from the hot part of the high voltage via a capacitive coupler.
For preparing the measurement it is very helpful to adjust the distance range to 5 to
10-times the known cable length and to reduce the amplification at least by factor 2 in
respect to a normal reflection measurement before starting the measurement. This
ensures that the first shot is a hit providing a result which only requires a minimum
amount of correction.
The advantage of this technology is, that the voltage is nearly unlimited. Prelocalisations of up to 400 kV and even higher have already been achieved with this
method.
A disadvantage to be mentioned is, that due to the high-frequency of the travelling
wave, in combination with the very high voltage, additional damage to cables that are
already aged by operation, can happen. In such cases it is recommended to proceed
very carefully to avoid possible consequential damage.
50m
=
G
TDR
Figure 4: Decay travelling wave decoupling on an 8 km cable with marker and cursor
3.
This method is comparable to the Decay, but does not work capacitive but inductive
by decoupling the current. Instead of using a capacitor for decoupling, a coil or
transformer is used. Typically Rogowski coils are used. The standard ICE method is
done with a surge generator. A capacitive discharge of the surge generator via the
surge switch triggers and ignites the fault and causes it to a flash over. This flashover
results in a travelling wave shown on the Reflectometer.
For evaluation, the second largest reflection is taken as reference. Any reflections
visible before this reflection are delayed by the ionisation time and represent the
process during which the fault begins to ignite. Furthermore, an attenuated transient
wave subsequently travels back and forth between fault and surge generator. Here
the capacitor of the surge generator as well as the arc at the fault represent a short
circuit for the high-frequency wave. The result is an oscillation where the period
length corresponds directly to the fault distance. The test leads must be subtracted to
determine the fault distance.
Fault distance = length of an oscillation test leads
The most accurate measurement results are achieved when the oscillation
measurement is done at the zero crossings. Another alternative is the shift
technology, where an identical copy of the trace is side shifted until the next
oscillation is completely overimposed with the original trace. For preparing the
measurement it is very helpful to set the distance range to 5 to 10-times the cable
length before starting the measurement. However, in this case the amplification
should be increased in respect to the normal reflection measurement since the
signals received from the decoupling coils are significantly weaker. An advantage of
the ICE technology is that the decoupling coil is in the earth path of the cable. It is not
exposed to any high voltage. Therefore, no complex insulation design is necessary.
The coil itself is very small and can be integrated in almost any device.
As for all transient methods, the disadvantage is that there is only information about
the fault distance without any other details on the cable or the fault itself. The
precision of transient methods is partly limited and cannot be compared with genuine
reflection methods.
Current measuring method
Another possibility is charging the cable up to the breakdown voltage with the surge
generator with closed surge switch and then using the cable capacitance itself as a
capacitor. With this method the available surge capacitance can be significantly
increased and this is particularly helpful with very long cables. The surge energy
does not have to run from the surge generator to the fault as it is already provided by
the cable and its charged capacitance. There is no ionisation time.. The remaining
measuring process is completely identical to the normal ICE current decoupling
process.
TDR
tx
parasitic
reflections
tx
tx
Figure 8: Reflectogram of a fault location measurement with the ICE method single phase
The fault does not ignite reflection at open cable end
TDR
tx
tx
tx
tx
parasitic
reflections
Figure 10: Reflectogram of a fault location measurement with the ICE method single phase
short circuit reflection of the transient current wave at the fault location without ignition delay,
amplitude and polarity remain the same
TDR
tx
Figure 11: Basic schematic for the ICE process single phase flashing fault
tx+ t
tx
tx
parasitic
reflections
Figure 12: Reflectogram of a fault location measurement with the ICE method single phase
flashover reflection at the fault location with ignition delay
tx
tx
tx
parasitic
reflections
parasitic
reflections
Figure 13: Reflectogram of a fault location measurement with the ICE method single phase
flashover ignition delay is so extensive that the reflection first takes place
at the cable end
10
The ICE current decoupling processes have proven their suitability in particular with
faults in the lower kOhm range and very large fault distances where it is not possible
to get results with the ARM process. However, it is always a requirement that the arc
lasts for a few milliseconds. The capacity of the surge capacitor and the impedance
of the cable determine the pulse widths of the travelling wave in the s range. These
flat slopes caused by the wide pulses as well as by the attenuation of the cable
reduce the accuracy of the results. Usually, the fault distances determined that way
are up to 5 to 10 % longer. For exact and fast fault location process, the
measurement technician should walk from the pre-localised distance into the
direction of the fault location system. The test leads must be subtracted from the
result as for all transient measurement methods.
large measurement
range
11
fault distance
12
4.
13