GEH6273E
Users Guide
GEH6273E
WARNINGS, CAUTIONS, AND NOTES
AS USED IN THIS PUBLICATION
WARNINGS
Warning notices are used in this publication to emphasize that hazardous voltages, currents, or other conditions that could cause personal injury exist in this equipment or may
be associated with its use.
Warning notices are also used for situations in which inattention or lack of equipment
knowledge could cause either personal injury or damage to equipment.
CAUTIONS
Caution notices are used for situations in which equipment might be damaged if care is
not taken.
NOTES
Notes call attention to information that is especially significant to understanding and
operating the equipment.
This document is based on information available at the time of its publication. While
efforts have been made to ensure accuracy, the information contained herein does not
cover all details or variations in hardware and software, nor does it provide for every possible contingency in connection with installation, operation, and maintenance. Features
may be described herein that are not present in all hardware and software systems. GE
Electrical Distribution & Control assumes no obligation of notice to holders of this document with respect to changes subsequently made.
GE Electrical Distribution & Control makes no representation or warranty, expressed,
implied, or statutory, with respect to, and assumes no responsibility for the accuracy,
completeness, sufficiency, or usefulness of the information contained herein. No warrantees of merchantability or fitness for purpose shall apply.
ii
iii
Appendices
Catalog Numbers for RMS9C Units in AK/AKR Circuit Breakers .................................. 36
Catalog Numbers for RMS9C Units in Power Break Circuit Breakers.......................... 37
Catalog Numbers for RMS9D Units in Power Break II Circuit Breakers...................... 38
Trip Unit Battery Suppliers............................................................................................. 39
iv
vi
vii
Frequency (Hz)
Protective relaying
Undervoltage
Overvoltage
Voltage unbalance
Current unbalance
Power reversal
Suffix
Character
2000 A
2500/3000/3200 A
4000 A
5000 A
Ground fault
GD
Z1 or
Z2
Protective Function
Characters
CT Size
01
150 A
RMS9C
02
200 A
both
03
225 A
RMS9C
04
400 A
both
06
600 A
RMS9C
08
800 A
both
Suffix
Function
10
1000 A
both
(none)
16
1600 A
both
PM
20
2000 A
both
25
2500 A
both
30
3000 A
both
32
3200 A
RMS9C
40
4000 A
both
50
5000 A
RMS9C
The fifth character of the catalog number is the letter L, which indicates that all Trip Units come with
long-time overcurrent protection. Additional letters
are appended to the catalog number to indicate
installed protective functions, as in Table 4. These
suffixes are valid for both MicroVersaTrip Plus and
MicroVersaTrip PM style Trip Units. They are
appended from left to right in the order given.
Sensor
Rating,
Amps
150
200
225
400
600
800
1000
Plug
Rating
60
80
100
125
150
100
150
200
100
150
225
150
200
225
250
300
400
300
400
450
500
600
300
400
450
500
600
700
800
400
600
800
1000
Catalog
Number
Breaker Frames
Sensor
Rating,
Amps
TR16B600
TR16B800
TR16B1000
TR16B1100
TR16B1200
TR16B1600
TR20B750
TR20B800
TR20B1000
TR20B1200
TR20B1500
TR20B1600
TR20B2000
TR25B1600
TR25B2000
TR25B2500
TR30B12002
TR30B16002
TR30B2000
TR30B2500
TR30B3000
TR32B1200
TR32B1600
TR32B2400
TR32B3200
TR40B1600
TR40B2000
TR40B2500
TR40B3000
TR40B36001
TR40B4000
TR50B3200
TR50B4000
TR50B5000
AKR30
AKR30S, AKR30H
Conversion Kits
SSD, SSF, SHD, SHF
TP82, THP82
TC82, THC82
Conversion Kits
SSD, SSF, SHD, SHF
AKR30
TP84, THP84
TC84, THC84
AKR30S, AKR30H
Conversion Kits
Conversion Kits
1600
2000
2500
3000
3200
4000
5000
Plug
Rating
600
800
1000
1100
1200
1600
750
800
1000
1200
1500
1600
2000
1600
2000
2500
1200
1600
2000
2500
3000
1200
1600
2400
3200
1600
2000
2500
3000
3600
4000
3200
4000
5000
Breaker Frames
SSD, SSF, SHD, SHF
TC1610, THC1610
AKR50S, AKR50H
TP1616, THP1616
Conversion Kits
SSD, SSF, SHD, SHF
TC2020, THC2020
TC2520, THC2520
TP2020, THP2020
TP2520, THP2520
AKRT50H
Conversion Kits
SSD, SSF, SHD, SHF
TC2525, THC2525
TP2525, THP2525
SSD, SSF, SHD, SHF
TC3030, THC3030
TP3030, THP3030
Conversion Kits
AKR75, AKR75H
Conversion Kits
SSD, SSF, SHD, SHF
TC4040, THC4040
TP4040, THP4040
AKR100
Conversion Kits
AKR125
A T T E N T I O N : Un transformateur de courant de
neutre est ncessaire pour les rseaux 3 phases +
neutre. Si le neutre nest pas distribu, les bornes de
neutre du dclencheur doivent tre laisses ouvertes.
Ne pas les court-circuiter (ceci peut endommager le
dclencheur et entrainer un mauvais
fonctionnement du systme lectrique.
Battery Function
Pressing the BATTERY key on the face of the Trip
Unit powers the unit from its internal battery. Battery power is maintained for 30 seconds after the last
key is pressed. This self-powered mode allows setting
up the Trip Unit or viewing trip targets when the
breaker is de-energized and external control power is
unavailable. All normal setup, meter, and status
functions can be performed with battery power.
Note that at temperatures above 40 C, the BATTERY A T T E N T I O N : La batterie peut exploser en cas de
key may have to be held down for up to 5 seconds for mauvaise utilisation. Ne pas la recharger, louvrir ou
la jeter dans un feu. Doit tre garder hors de porte
the Trip Unit to be powered.
des enfants. Une fois use, la batterie doit tre jet
rapidement.
Batteries
The Trip Unit uses a lithium sulfuryl chloride battery with a typical life of two years in a normally
8
Full-Scale
Accuracy
Resolution
2%
0.5 digit
Voltage (V)
1.5%
0.5 digit
3.5%
0.5 digit
3.5%
0.5 digit
3.5%
0.5 digit
Frequency (Hz)
1 Hz
1 Hz
1 sec
1 sec
Value
Figure 7 illustrates the LCD with all segments illuminated. The various segments are energized in
response to conditions sensed by the Trip Unit.
All percentages are based on full-scale values. Fullscale current is xIn, the rating of the breakers rating
plug. Full-scale voltage is the potential transformer
primary voltage rating. These data do not include
the accuracy rating of any measuring instrument.
Refer to the trip-time curves listed in Table 8 for
characteristics and accuracies of overcurrent protection.
Breaker Type
Trip-Time
Curves
Ground-Fault
Curves
AKR
GES-9910
GES-9911
GES-9909
GES-9911
Power Break II
GES-9989
GES-9990
Description
xIn
xCT
xLT
10
Key
Symbol
Setup
Status
FUNCTION
SELECT
VALUE
No effect
ENTER
No effect
No effect
Figure 8. Operation of FUNCTION key, showing progression among Trip Unit operating modes.
Set points are entered into memory in three steps:
display, select, and activate, as described below:
1. Press the VALUE key until the desired set point
is displayed flashing on the LCD.
11
12
13
Band
Delay, sec
2.4
4.9
9.8
20
Short-Time Pickup
The short-time pickup function establishes the current at which short-time trip is activated. Short-time
Figure 11. Time-current curve illustrating long-time pickup.
pickup is coupled with long-time pickup and the
choices of pickup settings are from 1.5 to 9.0 times
Long-Time Delay
the long-time setting, xLT , in steps of 0.5 xLT . The
The Trip Unit display for long-time delay is illus- Trip Unit display is illustrated in Figure 14.
trated in Figure 12. This function allows normal
momentary overloads without nuisance tripping.
The time delays at the lower limit of the bands at
600% of the long-time current setting, xLT, are listed
16
Figure 14. Trip Unit display for short-time pickup coupled with
long-time pickup.
Band
0.10
0.21
0.35
Table 12. Lower-limit delays for I2T OUT short-time delay bands.
Short-Time Delay
The Trip Unit display for short-time delay is shown
in Figure 16. This function delays the breaker trip on
a short-time trip. The choices of time-delay bands
are listed in Table 12. The delay with I2T IN is for a
current of 600% of xLT at the lower limit of the
band. The delay with I2T OUT is for the lower limit of
each band.
Figure 17. Time-current curve for short-time delay with I2T OUT.
17
Figure 18. Time-current curve for short-time delay with I2T IN.
Ground-Fault Pickup
The trip unit display for ground-fault pickup is
shown in Figure 21. This function sets the pickup
current for ground-fault protection. The available
settings are listed in Table 14 as multiples of xCT the
current sensor rating, in steps of 0.01 xCT . The
maximum value is limited to 1200 A. Figure 22
illustrates the time-current curve for ground-fault
pickup.
Sensor, A
Set Points
Setpoints
Without ST
Setpoints
With ST
1502000
0.200.60
25003200
0.200.37
2000
1.510.0 xIn
1.515.0 xIn
4000
0.200.30
3200
1.510.0 xIn
1.513.0 xIn
4000
1.59.0 xIn
1.59.0 xIn
5000
1.57.0 xIn
1.57.0 xIn
OFF
Disabled
0.10
0.21
0.35
Ground-Fault Delay
This function sets the delay before the breaker trips
when the ground-fault pickup current has been
detected. The Trip Unit display is shown in Figure
23. The choices are listed in Table 15. The delay for
I2T OUT is at the lower limit of each band. The delay
for I2T IN is at 200% of the pickup setting at the lower
limit of the band.
Figure 25. Time-current curve for ground-fault delay with I2T IN.
Figure 23. Trip Unit display for ground-fault delay, showing I2T
out.
19
This function sets the delay time before a voltageunbalance trip occurs. The range of delays is 1 to 15
seconds, in steps of 1 second. Choosing OFF disables
voltage-unbalance protection. The Trip Unit display
is shown in Figure 27.
Figure 31. Trip Unit display for undervoltage relay zero-volt trip
disabled.
Figure 32. Trip Unit display for undervoltage relay zero-volt trip
enabled.
This function selects the normal power flow direction for the breaker, either from line to load or from
load to line. Figure 37 shows the setup display for
normal power flow of line to load. This direction
setup also affects the sign of the normal power
metering displays.
Figure 37. Trip Unit display for power direction setup, showing
line to load.
This function sets the delay time before an overvoltage trip occurs. The range of delays is 1 to 15 sec- This function sets the delay time before a poweronds, in steps of 1 second. Choosing OFF disables reversal trip occurs. The range of delays is 1 to 15
overvoltage protection. The Trip Unit display is seconds, in steps of 1 second. Choosing OFF disables
shown in Figure 35.
21
60, 80, 100, 125, 150, 200, 225, 250, 300, 400,
8002000 450, 500, 600, 630, 700, 750, 800, 900, 1000,
A
1100, 1200, 1250, 1500, 1600, 2000
5000 A
Communication Address
Note that this step applies only to MicroVersaTrip
PM Trip Units connected to either POWER
LEADER or Epic MicroVersaTrip systems.
With POWER LEADER systems, the address is
assigned at the breaker. The address options are
from 256 to 999, in steps of 1, as illustrated in Figure
43.
Setting
Disabled
Disabled
Enabled
Disabled
Disabled
Enabled
Function
Shunt Trip or Shunt Trip with
Lockout activates Bell
AlarmAlarm Only
UVR trip activates Bell
AlarmAlarm Only
Protection trip activates Bell
AlarmAlarm Only
Shunt Trip or Shunt Trip with
Lockout activates Bell Alarm with
Lockout
UVR trip activates Bell Alarm with
Lockout
Protection trip activates Bell
Alarm with Lockout
24
25
26
Energy
Voltage
The voltage displayed by this function depends on
how the Trip Unit was configured during Setup. If
the breaker was configured with phase-to-neutral
connections, the display shows individual phase voltFigure 51. Trip Unit display for aggregate energy.
ages, as in Figure 49. If the breaker was configured
with phase-to-phase connections, the display shows
voltages between the phases, as in Figure 50. Press Total Real Power
VALUE to cycle through the three phase voltages.
The value displayed for total real power, illustrated
in Figure 52, represents the aggregate real power in
watts flowing through all three phases. The value is
displayed from 0 to 999 kW, then automatically
switches units to display 1.00 to 999 MW.
27
Frequency
This display, illustrated in Figure 55, shows the frequency of the line current. Either line voltage or
current must be present for this display to appear.
The frequency is calculated from the current and
voltage signals. If both are present, the voltage frequency is displayed. If neither are present, this display does not appear.
The frequency is displayed in steps of 1 Hz.
Power Demand
Trip Information
When the breaker trips, information about the trip After a short-time trip, the status display appears as
can be displayed in Status mode. Figure 58 illustrates in Figure 60. The information presented is similar to
a typical fault display following a trip.
that in the long-time overcurrent display, with the
short-circuit (I>>) and short-time (ST) targets.
30
Protective Relay
Voltage unbalance
Current unbalance
V<
Undervoltage
V>
Overvoltage
I
I
Power reversal
31
Figure 65. Trip Unit status display for long-time overcurrent trip
counter.
32
Type AKR circuit breakers are shipped from the factory with their Trip Units installed. Removal is necesPower Break II circuit breakers are shipped from the sary only for replacement. Trip Units are separately
factory with their Trip Units installed. Removal is mounted on the breaker structure and are removed
only necessary for replacement or to change the by moving the Trip Unit removal bracket. When a
Trip Unit is replaced, the locking arm snaps back
accessory-configuration switches.
into place to indicate proper engagement. Refer to
To remove the Trip Unit, perform the following
GEH-6303 for detailed instructions on replacing
procedure:
Trip Units in in Type AKR circuit breakers.
33
34
Possible Cause
Corrective Action
35
Code Description
Function
AKR
Breaker Type
2
3
4
2252000 A maximum CT
3200 A maximum CT
4000 A maximum CT
Breaker Frame
(max CT)
01
03
04
06
08
16
20
30
32
40
150 A
225 A
400 A
600 A
800 A
1600 A
2000 A
3000 A
3200 A
4000 A
Installed CT
L
S
H
I
K
Long-time (standard)
Short-time
High instantaneous
Instantaneous
Fixed high instantaneous
Overcurrent Protection
G
GD
W
Ground fault
Defeatable ground fault (not UL listed)
W curve
Ground-Fault
Protection
Z1
Z2
X
Optional Functions
P
M
Communication,
Metering, & Relaying
Replacement
36
Code Description
Function
Power Break
Breaker Type
2
3
4
8002000 A maximum CT
3000 A maximum CT
4000 A maximum CT
Breaker Frame
(max CT)
02
04
08
10
16
20
25
30
40
200 A
400 A
800 A
1000 A
1600 A
2000 A
2500 A
3000 A
4000 A
Installed CT
L
S
H
I
Long-time (standard)
Short-time
High instantaneous
Instantaneous
Overcurrent Protection
G
GD
Ground fault
Defeatable ground fault (not UL listed)
Ground-Fault
Protection
Z1
Z2
Optional Functions
P
M
Communication,
Metering, & Relaying
Replacement
37
Code Description
Function
Power Break II
Breaker Type
2
3
4
2000 A maximum CT
3000/3200 A maximum CT
4000 A maximum CT
Breaker Frame
(max CT)
02
04
08
10
16
20
25
30
40
200 A
400 A
800 A
1000 A
1600 A
2000 A
2500 A
3000 A
4000 A
Installed CT
L
S
H
I
Long-time (standard)
Short-time
High instantaneous
Instantaneous
Overcurrent Protection
G
GD
Ground fault
Defeatable ground fault (not UL listed)
Ground-Fault
Protection
Z1
Z2
Optional Functions
P
M
Communication,
Metering, & Relaying
Replacement
38
Catalog
Number
3B24XA
39
g
GE Electrical Distribution & Control
General Electric Company
41 Woodford Ave., Plainville, CT 06062
GEH6273 R06
1299