Professional Documents
Culture Documents
SUMMARY:
The existing and planned residential construction, accompanying construction and other
constructions require constant and efficient supply of heat. This requirement may be fulfilled
by building a connecting heat pipeline running from the facility to the mini-thermal power
plant. The heat pipeline route is set in the Construction Urban Plan (GUP). The basic reasons
for construction of a connecting heat pipeline are: connecting the facility to the central heating
system, termination of several block boiler rooms and new residential construction.
A new heat pipeline route should be designed from the existing heat pipeline and the initial
manhole to the connection to the mini-thermal power plant. The heat pipeline should be
entirely in compliance with the route determined by the location permit and the prerequisites
determined by special construction conditions. In addition, all existing municipal
infrastructure should be entirely complied with.
According to the project task, the route consists of two parallel laid pipelines and the
accompanying shafts in which the block elements and other elements used for maintenance
and hot medium distribution technology will be situated. The pipelines are pre-insulated by
polyurethane insulation in the exterior plastic pipeline, and are as such laid directly in the
construction pit.
The mechanical engineering part of the project should contain the following calculations: the
strength calculation, and pipeline elasticity calculation and the dilation calculation.
Key words: heat pipeline, route, pre-insulated pipeline
1. UVOD
1.1. Openito
b.
- beavne eline cijevi za promjer cjevovoda do NO 200, dimenzija prema HRN C.B
5.221 materijal .1212 prema HRN C.B 5.021.
- avne eline cijevi uzduno ili spiralno zavarene za promjere cjevovoda iznad NO 200
prema HRN C.B 5.240, materijal .0361 prema HRN C.B 5.026.
- za vrelovod DN 450 koristiti predizolirane eline cijevi koje trebaju biti izraene u
skladu sa zahtjevima propisanim u "Pravilniku osiguranja kvalitete za proizvodnju
predizoliranih cjevovoda za HEP DP Sektor za toplinarstvo" izraen u Ekonerg holding
d.o.o., Zagreb, srpnja 2000. godine.
Lukove cjevovoda u ahtovima i za izradu predizoliranih cijevi koristiti prema HRN M.B
6.821 (R=1,5) iz materijala .1212 prema HRN C.B 5.021.
2. Cjevne armature:
Sva armatura mora biti za nazivni pritisak NP 16. U odnosu na izvedbu koristiti
cilindrine, odnosno kuglaste zaporne slavine.
3. Termika izolacija cijevi:
Cijevi za klasini sistem u ahtovima izolirati jastucima mineralne vune. Obloga je
aluminijski lim. Predizolirane cijevi ve se isporuuju toplinski izolirane.
1.5. Uvjeti za projektiranje
a) Trasa vrelovoda:
Projektom definirati u potpunosti prostorni poloaj vrelovoda na osnovi postojeeg stanja,
prikupljenih posebnih uvjeta graenja komunalnih poduzea, te lokacijske dozvole.
b) Zahtjev za graevinsko projektiranje:
Cjevovod se mora zatititi prikladnim graevnim objektima od planiranih mehanikih
optereenja.
Statiki proraun graevnih elemenata treba raunati za pokretno optereenje, prema
Pravilniku o normativima za odreivanje veliine optereenja na mostovima, Sl. list 1/91.
l. 20. i 21.
2. PODACI O GRAEVINI
2.1. Openito
Na osnovi projektnog zadatka, lokacijske dozvole, izgraenosti prostora unutar i uz pojas
trase vrelovoda, posebnih uvjeta graenja, obraeno je projektiranog spojnog vrelovoda od
naselja do mini toplane. Ova tehnoloka veza omoguava ukljuivanje naselja u jedinstveni
sustav (CTS) grijanja grada Zagreba.
Vrelovod je projektiran od predizoliranih cijevi dimenzija 2 x DN 450 mm.
Na prijelazu magistralne pruge vrelovod se uvlai u prethodno postavljene zatitne cijevi duine
2 x 54,15 m dimenzija 865 x 13 mm.
Proboj tla provodi se postupkom tuneliranja kojim se u punom profilu specijalnim ureajem
freza tlo krunskom glavom, izvlai materijal punicom uz istovremeno utiskivanje zatitnih
cijevi hidraulikom preom.
2.2. Trasa vrelovoda
Trasa vrelovoda iskolena je na terenu na osnovi uvjeta iz lokacijske dozvole uz potivanje
sadranih posebnih uvjeta graenja i uz uvaavanje postojeih vodova komunalne infrastrukture.
Poetna toka vrelovoda je postojei aht u nogostupu, a zavrna toka je uvod u mini toplanu.
2.3. Horizontalni elementi trase
Kosim izvodom iz postojeeg ahta 0 u nogostupu uz dva loma trasa vrelovoda se postavlja u
pravac pruanja u sredinu sjevernog prometnog traka na potezu od 76,68 metara te se nakon
autobusnog ugibalita uvodi u pojas postojeeg parkiralita na sjevernoj strani ulice. U stacionai
3+13,47 trasa ima blagi lom (176-42-17) ime uspostavlja usporednost s novim pravcem
pruanja ulice i ulazi u prvi aht 1 pozicioniran u nogostupu.
U ovom ahtu trasa vrelovoda s blagim lomom (172-45-14) uspostavlja novi pravac do ahta 2
u pojasu postojeeg odnosno nastavno projektiranog pojasa.
Lomom (94-00-14) u ahtu 2 i dvostrukim ortogonalnim zalomom trasa vrelovoda mijenja
smjer pruanja usklaen s planiranom ulicom i to u istonom nogostupu do stacionae 9+47,34
gdje prelazi na paralelnu poziciju sa zapadne regulacijske linije ove ulice prolazei kroz aht 3
5
dionica
0-1
1-2
2-3
3-4
4-5
5-6
6-7
7-8
8-MT
minimalna
2,48 m
2,02 m
0,60 m
2,15 m
2,20 m
1,63 m
1,43 m
1,40 m
1,84 m
srednja
3,06 m
2,44 m
1,83 m
2,91 m
3,09 m
2,14 m
2,44 m
3,30 m
3,21 m
2.5. Okna
Svih osam ahtova projektirano je tipski s unutarnjim netto tlocrtom 4,0 x 4,0 m i svijetle visine
2,80 m. Gornju pokrovnu plou, zidove i temeljnu plou ahtova treba izvoditi iz armiranog
vodonepropusnog betona MB-30 i sve u jednakoj debljini od 25 cm. Ugraivati treba iskljuivo
vodonepropusni beton. U dnu svakog okna projektirana je sabirna jama (talonica) u funkciji
sakupljanja i evakuacije eventualnih procjednih voda, a pokrivrena je s tipskom elinom
reetkom dimenzija 460 x 460 mm. Zidove i pokrovnu plou treba zatititi hidroizolacijom od 2
sloja bitumenske ljepenke uz prethodno premazivanje povrina resitolom. Na svakom ahtu
izvode se dva reviziona okna s tipskim ljevano-eljeznim poklopcima 63 mm nosivosti 250
kN i tipskim penjalicama. Reviziona okna treba izvoditi iznad razine pokrovne ploe u visini od
30 cm do razine okolnog postojeeg ili planiranog povrinskog ureenja. Ova visinska razlika od
30 cm slui za prekrivanje pokrovne ploe okna humusom ili drugim zahtijevanim materijalom.
Takoer se na svakoj pokrovnoj ploi postavlja jedan montaerski otvor dimenzija 73 x 138 mm
u funkciji unoenja ili iznoenja zapornih ventila. Ovaj otvor se pokriva standardiziranim DTK
eljeznim poklopcima nosivosti 150 kN te hidroizolacijskom ljepenkom.
Na oknima 6 i 7 ne izvodi se nadgradnja ulaznih otvora.
U svakom zidu treba ostaviti otvor dimenzija 200 x 100 cm za prolaz vrelovodnih cijevi, te e se
nakon uklanjanja oplate privremeno nekoriteni otvori zazidavati siporeks opekama i obostrano
bukati vodonepropusnim cementnim mortom.
Za razupore dvostrane oplate zidova treba koristiti materijale koji zbog korozije ili na drugi nain
ne mogu dovesti do prodiranja podzemne vode. Temeljenje ploe dna okna treba izvesti na sloju
podlonog betona MB-10 minimalne debljine 5 cm.
Toplinsku izolaciju pokrovne ploe treba izvoditi s unutranje strane vodootpornim materijalima.
Dispozicije svih otvora po svakom oknu daju se u grafikom dijelu elaborata.
2.6. vrste toke
U svrhu preuzimanja osnih sila u vrelovodu koje nastaju iz temperaturnih razloga i koje malim
dijelom preuzima okolno tlo putem trenja, projektiraju se i izvode tzv. vrste toke, tj. pomone
graevine iz armiranog betona MB-30 s funkcijom preuzimanja glavnine temperaturnih sila.
Proraunske dimenzije vrstih toaka na maksimalnu silu su 5,30 x 1,30 x 3,50 m.
2.7. Cjevovod
Za izvoenje predmetnog vrelovoda predvien je sustav predizoliranih cijevi. Odabrana
oprema u potpunosti zadovoljava za radni tlak od maksimalno 16 bar i radnu temperaturu do
130 C. Medijske cijevi su od elinih spiralno zavarivanih cijevi u kvaliteti St.37.0, prema
DIN 1626, a dimenzije odgovaraju propisima ISO 4200 / DIN 2458. Materijal i dimenzije
elinih cijevnih lukova odgovaraju materijalu cijevi i dimenzijama montanih fazonskih
komada. elini lukovi su predvieni kao R = 1,5 d.
2.8. Strojarski elementi trase
Prema projektnom zadatku graevina se sastoji od dva paralelno poloena predizolirana
cjevovoda DN 450 mm, vanjskih dimenzija 630 mm, te 8 komada prateih okana u kojima
se smjetavaju zaporni ili drugi elementi koji slue za odravanje i tehnologiju distribucije
toplog medija. Cjevovodi su predizolirani poliuretanskom izolacijom u plastinom vanjskom
cjevovodu i kao takvi se direktno polau u graevinski rov. Ukupna irina trase koju
zauzimaju cjevovodi (polaz + povrat) iznose minimalno 1560 mm ( 1,56 m) , a maksimalno
2230 mm ( 2,23 m). Prilikom montae potrebno je trasu kopati proireno prema tehnikim
uvjetima za montau i prema pravilima zatite na radu.
Priloena tehnika dokumentacija izraena je na temelju:
- Projektnog zadatka izraenog u HEP-u Sektor za toplinsku djelatnost,
- Lokacijska dozvola,
- Zapisnika o iskolenju trase,
- Vlastitih uvida na terenu,
- Tehnikih mogunosti.
Unutar ahtova postavlja se armatura za zatvaranje, odzraku ili ispust ve prema potrebama.
Pranjenje je predvieno preko armatura 2 DN 40 u oknima, a odzraivanje preko
odzranih slavina 2 DN 40 u oknima. Vrelovod u najniim tokama (ispod prepreka) nee
se moi isprazniti bez ispumpavanja. Na vrelovodu 2 DN 450 u ahtovima su predviene
pregradne slavine 2 DN 400 radi etapne izgradnje i mogunosti sekcijskog iskapanja
cjevovoda iz pogona. Dio zapora ne treba se izvoditi u ovoj fazi. O tome e odluiti investitor
i nadzor tijekom izgradnje.
Na izlasku i ulasku cjevovoda u aht postavljaju se brtveni prstenovi koji spreavaju prodor
vode u aht. Vrelovod se izvodi od predizoliranih elinih cijevi u zatitnom omotau od
polietilena visoke gustoe (PEHD), a polae se u podzemni rov u posteljicu od pijeska.
Dubina polaganja je minimalno 700 mm od vrha cijevi do cestovne povrine.
2.9. Opasnost od poara
Za projektirani predizolirani cjevovod, koji je u potpunosti ukopan u zemlju, nema u toku
eksploatacije opasnosti od poara, pa se i ne predviaju posebne mjere zatite.
U oknima se koristi klasina negoriva izolacija od mineralne vune u zatitnom platu od
aluminijskog lima. U oknima je cjevovod uzemljen.
2.10. Minitoplana
Cjevovod se uvodi u prostor Minitoplane koja nije bila predmet projekta. U prostoru
Minitoplane, te u toplinskoj stanici najblieg objekta ahtu 0 predvia se ugradnja sustava
kontrole proputanja.
Sl 2. vrsta toka
10
11
12
13
Sl 5. PHDE spojnica
3.6.2. Zavrne PE spojnice (zavrna PE-kapa)
Zavrne spojnice upotrebljavaju se na mjestima gdje se privremeno zavrava vrelovod koji e
se u daljnoj fazi izgraditi. Postupak spajanja je identian kao za ravne spojnice.
Sl 6. zavrna PE spojnica
3.6.3. Specijalni brtveni prsten na prodoru kroz atove ili zidove
Na prodoru cijevi kroz stijenke ahtova oko cijevi se postavlja specijalni brtveni prsten koji se
sastoji od sklopa brtvi i ugradbene cijevi u beton. Na ahtovima su ostavljeni vei otvore te e
se nakon postave cijevi ubetonirati u stijenu ugradbena cijev, a nakon toga sklop brtvi.
3.6.4. Kompenzacijski jastuci
Na mjestima lira, L ili Z kompenzatora oko cijevi postavljaju se kompenzacijski
jastuci ili polietilenske pjene. Za predviena pomicanja do 25 mm postavlja se jedan sloj , a
za vea 2 sloja . Za dimenziju predvienih cijevi NO 450 treba predvidjeti ugradnju
kompenzacijskih jastuka 2 x vel. III ( vel. III = 360 x 40/60 x 100).
14
Sl 7. kompenzacijski jastuci
3.6.5. Podloke
Ispod svake cijevi na odreenoj udaljenosti a min 1,0 m od spojnog zavara postavljaju se
Podloke od tvrde pjene dimenzija 100 x 100 x 600mm. Za cijev od 6 metara predvia se 3
podloke, a za cijev 12 m , 5 komada.
3.7. Statika kompenzacija toplinskih dilatacija
Predziolirane cijevi mogu se polagati:
- U hladnom stanju,
- Sa toplim prednaprezanjem.
3.7.1. Nain voenja vrelovoda
Trasa vrelovoda moe se voditi na vie naina, u ovisnosti od strukture vrelovodne mree.
Trasa vrelovoda moe biti ravna, moe biti sa L-, Z- ili U - kompenzatorima, koji preuzimaju
istezanje krajeva vrelovoda. Kod projektiranja trase cjevovoda nastoji da kompenzacioni
elementi imaju kut od 90 .
Predizolirane eline cijevi sistema ine sistem kod kojega unutranja elina cijev, toplinska
izolacija i zatitni PE omota imaju jedinstvenu cjelinu. Iz toga slijedi da se nastala istezanja
unutranje cijevi prenose na toplinsku poliuretansku izolaciju i zatitni HDPE omota.
Toplinska izolacija i PE omota isteu se priblino jednako kao i elina cijev.
Kod polaznih cijevi u zemlju (sloj pijeska) i zatvorenog kanala, pri zagrijavanju medija,
dolazi do istezanja (dilatacije) eline cijevi. S druge strane sile trenje na povrini PE omota
predizoliranih cijevi i sloja pijeska spreavaju istezanje eline cijevi (sprijeeno istezanje).
15
Meusobni utjecaj ovih sila stvaraju naprezanje u sistemu koja se u odreenoj mjeri moraju
neutralizirati pomou kompenzacijskih elemenata na odreenim djelovima trase. Ova
naprezanja ne smiju prekoraiti dozvoljnu vrijednost od 185 N/mm2.Takoer je potrebno
obratiti panju na dozvoljena smina naprezanja izmeu poliuretanske toplinske izolacije i
eline cijevi. Ona ne smiju prekoraiti dozvoljenu vrijednost od 0.4 N/mm2. Faktori koji
utjeu na tangencijalno naprezanje su dubina polaganja cijevi (sila trenja) i veliina eline
cijevi d.
Tangencijalno naprezanje: = Fr' x d / (N/mm2)
Zbog toga se predizolirane cijevi polau na dubini od 0.6 do 2,6 m.
Da ne doe do prekoraenja dozvoljenih naprezanja u predizoliranim cijevima, uvodi se
pojam "maksimalno dozvoljene duine polaganja cijevi" - Lmax, koja odreuje duinu
cjevovoda izmeu dvije toke koje imaju mogunost istezanja. Maksimalna duina polaganja
cijevi zavisi od veliine eline cijevi, dozvoljenog normalnog naprezanja, te sile trenja na
povrini PE-omotaa. Ako nije mogue zadovoljiti kriterij maksimalne dozvoljene duine
polaganja cijevi, Lmax, iz tehnikih razloga (statike) primjenjuje se metoda polaganja
predizoliranih cijevi sa prednaprezanjem (rjeenje koje je usvojeno u ovom projektu).
Napomena: Projektirani cjevovod se treba prije zatrpavanja prednapregnuti.
Postupak prednaprezanja dijela vrelovoda izvodi se na slijedei nain:
Odabere se dio trase vrelovoda koji e se toplinski prednapregnuti. U otvoreni kanal poloe se
predizolirane cijevi iji su krajevi kratko spojeni i povezani na mobilni toplinski izvor
energije. Prije nego se kanal zatvori s pjeskom i zemljom, vri se zagrijavanje vrelovoda na
predvienu temperaturu prednaprezanja, koja u naem sluaju iznosi 70 C. Tada dolazi do
istezanja vrelovoda do odreene veliine, koja nikad nee dostii kritinu veliinu naprezanja
u cijevima.
Kada se postigne konstantna temperatura prednaprezanja, pristupa se zatrpavanju tog dijela
trase s pijeskom i zemljom, pri emu se mora odravati konstantna temperatura
prednaprezanja od 70 C.
Kada se trasa potpuno zatvori i nabije zemljom, iskljuuje se mobilni izvor topline i ostavi da
se vrelovod ohladi. Prilikom hlaenja tretirani se vrelovod skuplja, pri emu nastaju
naprezanja na tlak (negativno naprezanje). Prednaprezanjem istegnuti dio vrelovoda se nikada
ne vraa u svoj prvobitni poloaj, zbog djelovanja sila trenja na vanjskom PE omotau.
Kada se vrelovod pusti u pogon, na radnu tempearturu od cca 130 C, toplinska naprezanja
koja nastaju u njemu su uzrokovana zbog podizanja temperature medija od 70 do 130 C.
Tada dolazi do istezanja vrelovoda do odreene veliine, a naprezanja koja nastaju u cijevima,
nikad nee dostii kritinu veliinu naprezanja u cijevima.
3.7.2. Transport i uskladitenje
Isporuka predizoliranih cijevi, fazonskih elemenata i opreme vri se po pravilu sa kamionima
do gradilita. da bi se izbjegla oteenja pri isporuci preporuuje se da investitor odredi
odgovornu osobu za preuzimanje.
Istovar i skladitenje preuzima investitor. Runo se istovaruju predizolirane cijevi do DN 80,
a za vee dimenzije koriste se dizalice. Cijevi i fazonski elementi ne smiju se pri istovaru
bacati da ne bi dolo do oteenja izolacije. Po mogunosti, cijevi skladititi na suho mjesto i
ne smije leati u vodi. Na krajevima cijevi i fazonskih elemenata i armatura tvorniki su
ugraene zatitne kape, koje tite elemente od prodora vlage i neistoe. Fazonske elemente,
armature i pribor skladititi na drvene palate na suhom mjestu.
16
17
4. PRORAUNI
Proraun je izveden prema kompjuterskom programu za statiku predizoliranih elinih cijevi.
Proraun naprezanja i elastinosti vrelovoda raen je u skladu sa ANSI B31.1 standardom,
primjenom metode konanih elemenata. Na cijeloj trasi koriteni su jednodimenzijski konani
elementi, izuzev cijevnih lukova koji su izloeni veim momentima savijanja, gdje su za
kontrolu naprezanja i pojavu ovalnosti koristili trodimenzionalni elementi.
18
20
21
6. LITERATURA
Prilikom izrade ovog rada sluili smo se slijedeom literaturom:
1. Kohari V. :Uvod u projektiranje cjevovoda, FSB, Zagreb, 1991.
2. Donjerkovi P. :"Osnove i regulacija sustava grijanja, ventilacije i klimatizacije, I i II dio",
Alfa, Zagreb, 1996.
3. Kraut B. :Strojarski prirunik, Tehnika knjiga, Zagreb, 1988.
4. Toplinske tablice, FSB, Zagreb, 1993.
22