STANDARD PARAMETER OF 800 KV CLASS TRANSMIISSION SYSTEM IN INDIA

PREFACE
Earlier in the year 1990 Central Electricity Authority (CEA) brought out a report detailing parameters of the 800 kV class
equipment and transmission line material based on the recommendations of Working Groups constituted following the
decision of Government of India to select 800 kV (with 765 kV as the nominal voltage) as the next higher AC
Transmission voltage in the country. Following this, a good number of lines were identified at this voltage. Though some
of these lines have been installed maintaining 800 kV class parameters, they are being operated at 400 kV level for want
of adequate power development. Accordingly associated substations continue to be at
400 kV level.
But with the initiative taken to have electricity for all by the year 2012, coinciding with the end of 11th five-year plan,
now it is a near-reality to charge the above mentioned lines at 765 kV and construct few more intra-regional and interregional lines at that level with a dozen or so number of substations. Keeping this in mind and the progress that has been
further made and as experienced in few countries that have this class of transmission system, it was felt necessary to
revive the Standing EHV Committee of CEA with representations from leading power utilities and manufacturers in the
country. As per order of Ministry of Power it was reconstituted in the year 2000. A few meetings took place for revising
the salient parameters of 800 kV class of equipment and transmission material and reviewing those for 400 kV level
through separate groups. The present report is an outcome of the deliberations in the meetings and inputs received from
the members concerned. It is expected that the contents would serve power utilities as the basis of design and engineering
of 800 kV transmission system in the country.
New Delhi
December 31, 2002

(Dr. S.Mukhopadhyay)
Chief Engineer (SETD), CEA

BASIC SYSTEM PARAMETERS OF 800 KV SYSTEMS


1.

Rated voltage

kV :

800

2.

Nominal Voltage

kV :

765

3.

Rated frequency

Hz :

50

4. System Neutral Earthing

: Effectively earthed

5.

Rated current

6.

Short circuit current and duration

kA :

2000
40 for one second

7. Creepage distance

Pollution site severity


Low
Medium
Heavy
Very Heavy

Specific creepage distance mm/kV*


16
20
25
31

* These are the values suggested in IEC- 815, 1986, which is applicable to System Voltage of up to 525kV. As the
pollution withstand characteristics is known to be non-linear for higher voltages, requiring increased creepage distance in

proportion to the non-linearity factor. Studies by ENEL, EPRI, CIGRE suggest that this factor may be as high as 20% for
800 kV System. Hence creepage distances presented in the Table are to be appropriately increased. Further, these values
may not be suitable for station insulation since the influence of diameter is considerable on the pollution performance.
8. Insulation Levels
a) Substation equipment
Reactors/ CBs/Isolators/CVTs/CTs

Transformers

Basic Insulation level

kV(peak) 1950

2400

Basic switching level

kV(peak) 1550

1550

Power frequency

kV (rms)

RIV at 508 kV rms

Micro
volts

830

1000(Max.)

b) Transmission lines
Basic Insulation level

kV(peak)

2400

Basic Switching level

kV(peak)

1550

Power frequency

kV(rms)

830

RIV at 508 kV (rms)

Micro volts

500(Max.)

TRANSFORMER
Generator Transformers
1. Ratings:
Three phase rating Voltage
MVA(Generally ratio
Single phase units
are envisaged)
630 MVA,800
21/765
MVA

Maximum flux density in any part


of core and yoke at rated MVA,
voltage and frequency.

Tapping range
percent

Percent
Impedance
Voltage

Cooling

A-off ckt
taps/links
+2
-6
(8 steps)
alternatively
B-On load taps
+2
-6
(16 steps)

15.0
(tolerance
allowed
= + 10%)

ONAN/OFAF
or
OFAF or OFWF
or
ONAN/ODAF or
ODAF/ODWF

tesla

1.9

Withstand capability for 25%


above the rated voltage

minutes

Withstand capability for 40%


above rated voltage

seconds

2. Connections : HV Star, Neutral effectively earthed


LV Delta
3.

Connection symbol

4.

Terminals:

YN, dll (in 3 phase bank)

a) LV Terminals
36 kV, 12500 amps. oil filled type bushing mounted on turrets, suitable for connections to bus bars in isolated phase bus
ducts which shall have spacing of 1500 mm for each 210 MVA single-phase unit of the 630 MVA three phase bank.
For each of 266.6 MVA single phase unit of 800 MVA, 3 phase bank, 2 Nos. 36 kV, 12500 Amp bushings per termination
shall be used (Total 4 Nos. bushings).
b) HV Terminal line end :
800 kV oil filled 1250 amps. condenser bushing with test tap. No arcing horns shall be provided.
Neutral ends : 36 kV porcelain bushing. No arcing horns shall be provided.
Auto Transformers
1.

Ratings
Three phase rating

Voltage

Tapping

HV/IV/LV
MVA

ratio

range percent

315/315/105

765/220/
33

+ 4.5%
-7.5%
24 steps

630/630/210

765/400/33

800/800/266.6
1000/1000/333.3

765/400/
33

+ 4.5 % |
-7.5%
24 steps
-do+4.5%
-7.5%
24 steps

tolerance 10%
Max. flux density in any part of core and

15%

Percent Impedance
Voltage
HV
HV
IV
IV
LV
LV

Cooling

12.5

40

25

ONAN/OFAF
or ONAN/
ODAF or
ODAF

12.5

60

40

-do-

-do-

-do-

-do-

-do-

14.0

65

45

-do-

15%

yoke at rated MVA, voltage and frequency

tesla

: 1.9

Withstand capability for 25% above the


rated voltage

minutes :

Withstand capability for 40% above the


rated voltage.

seconds :

2. Connection : HV/IV Star auto with neutral effectively earthed


: LV-Delta
3. Connection Symbol :

YNa0, dll

4. Short Circuit Level :


800 kV

40 kA (rms) for 1 second

420 kV

40 and 63 kA(rms) for 1 second

245 kV

40 kA (rms) for 1 second

5. Terminals:
a) LV Terminals

52 kV oil filled condenser bushings. The bushings shall be


arranged in a line with 1000 mm spacing to allow mounting of
to phase barriers. No arcing horns shall be provided.
b) IV terminal

245/420 kV oil filled condenser bushings with test tap. No


arcing horns shall be provided.

c) HV Terminal
Line end

800 kV oil filled condenser bushing with test tap. No


arcing horns shall be provided.

Neutral end

36 kV porcelain bushing. No arcing horns shall be provided.

Insulation Levels:
Lightning, switching Impulse and Power frequency voltage level.
Highest voltage
for equipment.
Um kV (rms)

Rated withstand Impulse voltage


lightning
switching (kV peak)

17.5(Neutral)
24(LV of GTs)
52 (LV of Auto Transformer)
245
420
800

95
125
250
950
1300
1950

1050
1550

Rated power frequency


short duration withstand
voltage kV(rms)
kV(peak)
38
50
95
395
-

phase

In the event when transferred surges are higher than 250 (kV peak) the insulation level of tertiary winding and
bushing are to be chosen accordingly.
Partial discharge
At

1.5 x Um kV, pico coloumbs


v3

500 (Max.)

BUSHINGS :
1) The voltage and current ratings, basic insulation level and creepage distance of the
bushings shall be as follows:
Voltage
Ratingk
V(rms)
800

Current
Creepage Distance
Rating
(mm)
(Amp)
1250
16,000
1250
420
10,500
2000
245
1250
6,125
2000
52
1,800
5000
2) RIV at 508 kV (rms)
micro volts
:
3) Corona Extinction voltage kV(rms)
:
4) Partial discharge level pico coloumbs :

Basic Impulse Level kV


(peak)
2100
1425

Type
Installation
No. of poles
No. of trip circuits
Rated short circuit
making current. kA peak
6.
Value of pre-insertion
resistor ohm
7.
Pre- insertion time
ms
8.
Rated operating duty cycle
9.
Rated break time ms
10. Closing time
ms
11. Difference in the instants of opening of
contacts
- within a pole ms
- between poles ms
12. Difference in the instants of
closing of contacts between poles ms
13. Rated line charging current

250

: SF6
: Outdoor
: 3
: 2 (independent)
:

100

450

:
:
:
:

10
0-.3 second-CO-3 min.-CO
40
100

To limit switching surge


over voltage to 1.9 p.u.

:
:

2.5
3.33

10

1025

1025

CIRCUIT BREAKERS
1.
2.
3.
4.
5.

Switching
Impulse
Level kV(peak)
1550

1000 (Max.)
508 (Min.)
500 (Max.)

Sl.No.

1
2
3
4
5
6
14.
15.
16.
17.

18.

Line Length(km)

Typical Line Charging current at bus voltage of


1.4
pu (kA)
No shunt reactor
With one of the two Both shunt reactors
in the line
shunt reactors failed in service
100
0.262
0.197
0.131
150
0.393
0.295
0.197
200
0.542
0.393
0.262
250
0.655
0.491
0.328
300
0.786
0.590
0.393
350
0.917
0.688
0.459
:
0.5 A to 10 A without
Small inductive current
switching over voltage exceeding 1.9 p.u.
:
Pneumatic or hydraulic spring charged
Type of operating mechanism
or
combination of these.
Anti pumping and trip free
First pole to clear factor
:
1.3
Type of auto reclosing
:
Single phase and 3-Phase.
:
10 NO and 10 NC on each pole,
exclusively for purchasers use.Continuous
current 10 A DC. Breaking capacity shall be 2
No. of auxiliary contacts
Amp. min. with circuit time constant not less than
20 ms at 220 V DC. Contacts should be
reversible type at site.
DISCONNECTS/EARTHING SWITCHES

1.
2.
3.
4.
5.
6.

Type of disconnect
No. of poles
Installation
Rated peak withstand current
Rated magnetising current/
capacitive breaking & making
current.
A
Type of operating mechanism

Vertical Break

3
:

kA

Outdoor
100

0.7
:

Electrical/Manual

INSTRUMENT TRANSFORMERS
Current Transformers
1.

Rated primary currents

A :

2000

2.

Rated secondary current

A :

3.

Number of cores

4.

Rated continuous thermal


current.

120%

5.

Parameter

Core I
Line/
Equipment
Protection
Main- I
20001000500/1

Core II
Line/
Equipment
Protection
Main- II
20001000500/1

Accuracy Class

PS

PS

Rated Burden
Min.knee point
voltage
Vk
Maximum Exciting
Current at Rated Vk/2
Maximum Secondary
Winding Resistance.

400020001000 volts
10-50-100
mA
15-5-2.5
ohm

400020001000 volts
25-50-100
mA
10-5-2.5
ohm

Utilistation

Transformation ratio

Core III

Core IV

Core V

Metering

Bus bar
Protection

Bus bar

20001000/1

20001000/1

PS

PS

20001000
volts
25-50
mA
10-5
ohm

20001000
volts
25-50
mA
10-5
ohm

20001000500/1
0.2
ISF <10
15 VA
-

Data for TPY/TPX Core(Alternative to Core I & Core II)


i)
ii)
iii)
iv)
v)

Duty cycle
Ratio applicable
Rated symmetrical short circuit current factor
Rated primary time constant.
ms
Duration for flow of current
Single energistation
ms
Double energisation
ms
vi) Time interval between two successive short
circuit current. ms
vii) Rated burden
ohm

: Single/Double energization CO/CO-t-CO


: 2000/1A
: 20
: 80
:
:

240 for CO duty


100 & 40 for CO-t-CO duty

1000

7.5

Bushing CTs
Not yet finalised.
Capacitor Voltage Transformers
1. Number of secondary windings
:
3
2. Rated secondary voltage, burden, accuracy and utilisation
Winding

Rated Voltage Volt

Rated burden VA

Accuracy

110 /v3

50

3P

II

110 /v3

50

3P

III

110 /v3

50

0.2

3.

Transformation Ratio

Purpose
Main I
Protection
Main II
Protection
Metering.

765 / v3 kV
110 / v3 V

4. Voltage factor
5. Rated Capacitance
pF
6. Stray conductance of the low Voltage terminal over
entire carrier frequency range micro-Siemens
7. Corona extinction voltage
kV(rms)
8. Partial discharge level at 508 kV(rms)
Pico coulombs

1.5 for 30 seconds


4400
50
508(Min.)
Less than 10

Protection Schemes
Line Protection
1) Main I
Carrier aided distance protection suitable for use with different carrier modes.
2)

Main II
Carrier aided protection based on directional comparison using wave detection or
phase comparison principles.

3)

Directional Earth fault Scheme


Two sets of directional earth fault relays, one for each main protection to cover high
resistance faults.

4)

Over-voltage Protection
The relay to have two stages and shall be able to monitor phase to neutral voltage
for all the three phases.

Auto Transformer Protection


1)

Differential Protection
(Percentage Biased)

2)

High impedance differential protection

3)

Over fluxing protection.

4)

Back-up directional over current protection.

5)

Overload protection.

6)

Neutral standby earth protection

7)

Delta circulating current protection.

Shunt Reactor Protection

1)

Differential protection

2)

Restricted earthfault protection

3)

Back-up protection

Bus Bar Protection


High speed differential protection with features for checking the security as required.
Circuit Breaker Failure Protection
In the event of circuit breaker failure, all circuit breakers connected to the Bus Section to which the fault circuit breaker is
connected shall be tripped with minimum possible time delay.
Other Equipments
a) Distance to Fault Locator
Distance to Fault Locator shall be installed for identifying the location of faults and for taking preventive measures
against fault prone areas.
b) Disturbance Recording Equipment
i)

Disturbance Recorder
Disturbance Recorder shall be micro-processor based and shall be used to record the
graphic form of instantaneous value of voltage and current in all three phases, open
delta voltage and neutral current, open or closed positions of relay contacts and
breaker during the system disturbance condition.

ii) Event Logging Equipment


The Event Logger is recommended to record the status of 800 kV Switchyard
equipment and relays and occurances of alarms. It shall be possible to accommodate
about upto 500 points. Whenever input status change occurs, an immediate printed
record would be provided by the equipment.
POWER LINE CARRIER COMMUNICATION
A.

Coupling Devices.
1.
2.
3.
4.
B.

Method of coupling
Nominal line side Impedance ohms
Nominal equipment side
Impedance ohms
Bandwidth
kHz
Line Traps

Phase to phase/3-phase coupling


: 480 (phase to phase)
: 150 (balanced)
:
75(unbalanced)
:
50-150

1.

Rated inductance at system


frequency mH
2.
Blocking resistance
ohms
3.
Rated Bandwidth
kHz
4.
Radio Interference Voltage at 508
kV(rms) Micro volts
5.
Nominal discharge current
of protective device connected
across main coil kA
C.
1.
2.
3.
4.
5.
6.
7.

:
:
:

430
50-150
500(Max.)

10

:
:

50-500
4.0/2.5 or integral multiple thereof

75 (unbalanced)

Not less than 10

PLC Terminal
Carrier frequency range kHz
Carrier frequency band
Nominal Impedance at carrier
frequency output ohms
Return loss within the nominal
carrier frequency band.
db
Peak envelope power W
Speech frequency band
Hz
Speech levels
Four wire transmit
Four wire receive
Two wire transmit
Two wire receive

kHz

:
Upto 80
: 300-2000 or 300-2400
:
:
:

+8 dB
0 dB
7 dB

-3.5 dB

D. VF Protection Signalling
1.
2.

Transmission time
PLC Channel No.1

3.

PLC Channel No.2

4.
5.

PLC Channel No.3


PLC Channel No.4

msec

20 (max.)
Speech + data
: Protection 1 +
Express speech
: Protection 2
: Protection 3

E. Coupling Capacitors
1.
2.
3.
4.
5.

6.

Installation
Rated capacitance
Pico Farad
Switching Impulse
withstand voltage
kV(peak)
Voltage factor
Equivalent series resistance
over the entire carrier
frequency range.
Ohms
Radio Interference
voltage at

:
:

Outdoor
8800

1550

1.5 for 30 secs.

less than 40
2500 (max.)

7.
8.

508 kV(rms)
Micro volts
Partial discharge
level
Pico Couloumbs
Corona extinction
voltage
kV(rms)

Less than 10
:

508 (Min.)

SURGE ARRESTERS
1.

Type Arrester

2.
3.
4.
5.

Nominal discharge current


kA
Rated Arrester voltage
kV(rms)
Continuous operating voltage
kV(rms)
Maximum residual voltage
at lighting impulse
current of 20 KA
kV(peak)
6. Maximum switching impulse
residual voltage at 2 kA
kV(peak)
7.
Maximum steep current
impulse residual voltage
at 20 kA
kV(peak)
8.
Dynamic over voltage
withstand capability
for 3 peaks
0.3 sec.
kV(peak)
|
0.1 sec.
kV(peak)
1.0 sec.
kV(peak)
10.0 sec.
kV(peak)
9. Discharge capability
A- Transmission line class
B- Minimum energy capability kj/kV
NOTE:- This energy takes into account
occurence of two successive
line discharges followed by
TOV profile as given at
Sl.No.(8).
10. Maximum radio interference/
partial discharge at 508 kV (rms) micro volts/
picocoloumbs

: Gapless (Metal
Oxide)
:
20
:
624
:
485
:

1430

1280

1630

:
:
:

1240
1045
920
865

:
:

4
28

250/50

SWITCHYARD LAYOUT

1.

Switching Scheme

: Double bus Double breaker. Depending on the


requirement of purchaser, one and a half breaker scheme can
also be adopted.However, the bays arrangements shall be so
selected that the rated current of 2000 A for different
equipments is not exceeded under any contingency.

2.

3.

Clearance (Minimum)
Phase to earth
m
Phase to Phase
m
Section clearance
m
Bay details
i) Bay width
m
ii) Bus size (Tentative)
a) Rigid bus/equipment
Inter connecting bus
b) Strung bus/Crossover bus
iii)

:
:

6.4
10.0
10.0

45

6" IPS tubular Aluminium pipe

Quad All Aluminium Tarantulla

Bay Dimensions

Bus level
Equipment Interconnecting level
Crossover bus level
Span length

Low level
(Above ground)
(Meters)
12
12
27
15
(Rigid bus)
TRANSMISSION LINE

High level
(Above ground)
(Meters)
27
12
39
90

Conductor:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.

Code Name
Number of sub-conductor /phase
Spacing between conductors
mm
Bundle arrangement
Nominal Aluminium area
sq.mm
Stranding and Wire Diameter
Overall Diameter
mm
Approximate mass
kg /km
Ultimate Tensile strength
kN
D.C. Resistance at 20 C ohms/km
Corona extinction
kV(rms)
voltage phase to ground
12. Modulus of Elasticity
kg/cm2
13. Coefficient of linear expansion per degree C
14 Maximum allowable temperature
degree C

: ACSR Bersimis
: 4
: 450
: Horizontal Square
: 690
: 42/4.57 mm Al + 7/2.54 mm St.
: 35.04
: 2187
: 146.87
: 0.04242
:

560

: 0.6320 x 106
: 21.5 x 10 -6
: 95

Earthwire :
1. Size
2. Number of earthwire
3. Overall Diameter
4. Quality of groundwire
5. Ultimate Tensile strength

mm
kgf/sq.mm
kgs.

: 7/3.66 mm G.S.S. wire of 95 Kgf/ sq.mm ( 1GPa) quality


: 2
: 10.98
: 95
: 6972

6.

D.C. Resistance at 20 C

7.

Shield angle for towers


(i) Outer phase
(ii) Middle phase

ohms/km

8. Modulus of Elasticity
kg/cm2
9. Coefficient of linear expansion per degree C
10. Maximum allowable temperature
degree C

2.5

: 15
: The middle phase shall fall below the circle drawn with
twoground wire points as diameter.
: 1.933 x 106
: 11.5 x 10 -6
: 53

Disc Insulators and Insulator Strings:


Insulator strings
1. Configuration
2. Number of discs
per
string(Size
280x170 mm,
EMS=210 KN
creepage distance=
370 mm)
3. No deformation load
(67% of mechanical
failing load of 210 KN)
4. Maximum voltage
across any disc
across any disc
phase to ground
voltage of 462 kV(rms)

Suspension string
V-90

Tension string
Quadruple 4 strings
in parallel

Pilot string
Single I

2 x 35
(Each limb
35 discs)

4 x 35
(Each limb
35 discs)

1 x 35
(35 discs)

2 x 140 KN

1 x 140 KN

x 140 KN

Not more than 25 kV(rms)

Towers :
1.
2.
3.
4.
5.

Number of circuit
Configuration
Normal span
m
Wind span
Weight span :
i) Suspension tower, max.
min.
ii) Angle tower, Downward
Upward

6.
7.
8.

Maximum temperature of
current carrying power
conductor exposed to sun
Maximum temperature of
groundwire exposed to sun
Clearances:

: Single circuit
: Horizontal
: 400
: 1.0 x normal span (For plain terrain)
:
:
:
:

1.5 x Normal span


0.8 x Normal span (for plain terrain)
(For hilly terrain, the minimum
weight span be fixed suitably).
2 x Normal span
200 m Net span
95 C

53 C

i) Minimum ground
clearances as per Indian
Electricity rules.
ii)
As per interference
limitations
iii)
Live conductor to
grounded metal

mm
12,400
15,500

mm

'V' Suspension string (V- 90)


I Suspension string
Zone I & II

Zone III & IV

Zone V & VI

Swing
Nil

Clearance
5,000 mm

Nil
22
45
Nil
27
55
Nil
30
60

5,100
4,400
1,300
5,100
4,400
1,300
5,100
4,400
1,300

mm
mm
mm
mm
mm
mm
mm
mm
mm

Quadruple tension string


Jumper
Zone I & II

Nil
15
30

5,100 mm
4,400 mm
1,300 mm

Zone III & IV

Nil
20
40

5,100 mm
4,400 mm
1,300 mm

Zone V & VI

Nil
22
45

5,100 mm
4,400 mm
1,300 mm

Pilot

string

Nil
20

iv)
v)

Mid span separation


For ground undulation,
extra over ground
clearance

mm
mm

12,400
:

300

5,100
4,400

mm

mm

vi)

Creep compensation for


conductor through
tensioning at the time of
stringing

Height of tower may be increased


instead of considering reduction in
temperature

over

9) Loadings :
Loadings shall be determined for the
two loading combinations including
wind on tower as given below :
- Combination I
As per IS: 802 -Part I-1995
- Combination II

SHUNT REACTORS
1.
2.
3.

Rating (single phase)


Winding connection
Neutral earthing

MVAR

4.

Magnetisation characteristic

: 50, 80, 110 in three phase banks.


: Star
: Earthed through Neutral Grounding Reactor.
: Linear upto 1.4 p.u.
: Slope of the characteristic in the saturated region
shall be 0.3 to 0.5.

5.

Permissible unbalance current %


among single phase reactors of a
three phase bank.
6. Ratio of zero sequence reactance
to positive sequence reactance.

: 2
: 1.0 (single phase)

7.

Noise level at rated voltage


and frequency

dB

8.

Clearances of terminals in
air (phase to earth)
Type of cooling

mm

9.
10.
11.

5800

ONAN
Mineral oil to IS:335 (and as standardised for
800kV Power Transformers)

Type of cooling medium


Terminals
Line Terminals

81 for 50 MVAR
83 for 80 MVAR
85 for 110 MVAR

:
800 kV oil filled condenser bushing with test
tap. No arcing horns shall be provided
:
145 kV oil filled condenser oil/ SF6 bushing

Neutral Terminal

145 kV NEUTRAL GROUNDING REACTOR FOR GROUNDING SHUNT REACTOR.


1. Number of phases
2. Maximum continuous current
3. Short time current Rating

A(rms)
A(rms) )

:
1
:
15
To be specified by purchaser after system studies.

4. Rated Impedance
5. Magnetisation characteristics
6. Terminals
a) Line end

ohms )

b) Earth end
7. Type of cooling
8.

Type of cooling Medium

Phase to earth air clearances


a) Line end
mm
b) Neutral end
mm
10. Insulation levels
a) Lightning impulse
kV(peak)
voltage withstand of the
line terminal

To be specified by purchaser after system studies.


: Linear upto short time current.
: 145 kV condenser bushing (as standardised for
neutral of 800 kV shunt reactor)
: 36 kV porcelain bushing
:
ONAN
:
Mineral oil to IS:335 (and asstandardized for
"800 kV Power Transformers")

9.

b) One minute power frequency kV(rms)


voltage withstand of the
earth terminals.
11. Whether full or graded insulation.

:
:

1050
230

550

38
:

Graded insulation

SHUNT REACTOR
(Connected to tertiary of power transformer to provide back-up reactive compensation)
1.
2.
3.
4.
5.
6.

Rated voltage
kV
Number of phases
Rating (three phase)
MVAR
Winding connection
Whether full or graded insulation
Basic insulation level (for line
and neutral end of winding and
bushings)

a) 1.2/50 microsecond
lightning impulse
withstand voltage
kV(peak)
b) One minute power frequency
withstand voltage
kV(rms)
7. Magnetisation characteristic
8. Minimum clearance in air
Phase-phase
mm
Phase-earth
mm
9.

Noise level at rated


voltage and frequency.

10. Terminals

dB

:
:
:

36
3
31.5, 50, 63, 80
: Star with neutral left inside.
: Full insulation

250
:

95

: Linear upto 1.3 p.u. voltage


:
:

530
480
:
74 for 31.5 MVAR
75 for 50 MVAR
77 for 63 MVAR
77 for 80 MVAR
:
52 kV, 800/2000 A oil filled condenser bushing with

a) Line Terminals

test tap. No arcing horn shall be provided.


:
ONAN with tank mounted or separately mounted
radiator bank.
:
Mineral oil to IS:335(and as standardised for"800
kV Power Transformers").

11. Type of cooling


12. Type of cooling medium

INTERFERENCE LEVELS
Transmission Lines
1.

RI should not exceed 50 dB for 80% of the time duration during the year.

2.

TVI- The minimum signal to noise ratio should be 30.

3.

Audio noise level for 800 kV system should be less than 55 dB(A).

4.

Electrostatic field should be less that 10 kV/m below the outermost phase
(2 m above the ground) and less than 2 kV/m at the edge of the right of way(45 m).

PTCC:
1.

Maximum value of induced


electromagnetic voltage for
fault duration of equal to or
less than 200 ms.

2.

Maximum value of induced


noise(noise interference)
to be taken cognizance if
noise is persistent).

volts

Micro volts -

- 650

2000 (measured) |