5 Installation and Connection
(continued)
89521-302/-303-401/-402-602 / AFSV.12.06470 EN
95
99 Connecting steady-state ground fault direction determination devices to Holmg
reen-configuration and window-type transformers
5 Installation and Connection
(continued)96
89521-302/-303-401/-402-602 / AFSV.12.06470 EN
Connecting the Auxiliary Voltage
Before connecting the auxiliary voltage V
A
for thePD 521 power supply, make sure that the nominal value of the auxiliary de
vice voltage agrees with the nominal valueof the auxiliary system voltage.Polari
ty reversal protection is provided in the form of arectifier bridge. To preserve
uniformity with other protection devices (L+ on terminal with smaller number),L
+ should therefore be connected to terminal 13. ThePD 521 has an auxiliary volta
ge supply that can beswitched between ranges and is factory-set for the voltager
ange of V
A,nom
= 110 to 250 V DC or 100 to 230 V AC.Before changing the auxiliary voltagerange,
turn off any connected auxiliaryvoltage. The components locatedbehind the front
panel are energized!The voltage range is switched by repositioning plug-in jump
ers on the I / O (input / output) module. After loosening four bolts on the fron
t side of the front panel, thelocal control module (front panel and processor mo
dule)can be removed once the following plugs have beenremoved first:
The ribbon cable connecting the local control module(front panel and processor m
odule) with the I/O module
The ribbon cable connecting the local control modulewith the optional ILSA inter
face (to fiber optics or towire)Where possible, disconnection of theribbon cable
between the processor module and the I/O module should beavoided. Should discon
nection haveoccurred, however, then the deviceneeds to be re-initialized by way
of acold restart.In the upper portion of the I / O module, between outputrelay a
nd current input transformers, are plug-in jumpers,which are plugged in as shown
as follows, depending onthe desired auxiliary voltage range.
100 Plug-in jumpers positioned for an auxiliary voltage of 110 to 250 V DC or 10
0 to 230 V AC (view from component side)101 Plug-in jumpers positioned for an au
xiliary voltage of 24 to 60 V DC (view from component side)
!!
5 Installation and Connection
(continued)
89521-302/-303-401/-402-602 / AFSV.12.06470 EN
97
5.6.2 Binary Control Inputs
Before connecting the control voltage V
in,nom
for the binaryinputs in the PD 521, check to see whether the controlvoltage V
in,nom
Resetting of the parallel display (LEDs) and other control functions for testing
and startupControl is also possible from the PC interface. In that casethe FPC
control program is required, along with a specialconnection cable (see chapter 1
3 Accessories and SpareParts ) and a suitable PC.
6.1 Display and Keyboard
The local control panel consists of two 4-digit, 7-segmentdisplays, six function
keys and 12 LED indicators.
FxyER
0 3 1 00
ValueAddressEnter KeyReset Key"Up" Key"Down" Key
102 View of the local control panel
The settings, signals and measured values are numerical-ly coded. This code is c
alled the address and is displayedin the lower of the two 7-segment displays on
the localcontrol panel. The value associated with the address isdisplayed in the
upper 7-segment display.
Value
Address
The address of the information or parameter justselected is displayed.
Enter
To enter the input mode, press enter key (E). Press asecond time to leave the in
put mode. Activation of theinput mode is signaled by the red LED indicator on th
eenter key (E).
6 Control
89521-302/-303-401/-402-602 / AFSV.12.06470 EN
6Control
(continued)
89521-302/-303-401/-402-602 / AFSV.12.06470 EN
99
Reset
The LED indicators can be reset by pressing the resetkey (R). The event records
are not affected and remainin the event memories. Other functions of the reset k
eyinclude deactivation of the input mode (with no further consequences) and keyb
oard locking.The following diagrams of the individual control stepsindicate whic
h specific display can be changed bypressing the up or down keys. A solid black dot
in theupper left corner of the enter key indicates that the redLED indicator is
lit up. The addresses used in theexamples below are not necessarily valid for th
e PD 521;they serve to illustrate the principles of local control.
6.2 Address Selection
Addresses are selected by pressing the two pairs of up and down keys. As long as the
keys are being pressed,the value display remains dark. Approximately 1 secondaft
er the keys are released the value associated with theselected address will appe
ar in the value display. Inprinciple, any address in the entire address range fr
om00 00 to 99 99 can be selected. If, however, an address isselected that is not
used in the PD 521, the value displaywill remain dark. The existence of entries
in the signal or monitoring signal memories is indicated during operation.This
is indicated by the fact that while the up and down keys are being pressed the value
display does not remaindark; instead, the following messages are displayed:
"...E" if there is information in the monitoring signalmemoryIf L and/or E still rem
ain in the value display 1 secondafter the up and down keys have been released, then
there is no information stored for that particular address.Example:Information i
nSignal MemoryInformation inMonitoring SignalMemoryInformation inSignal andMonit
oring SignalMemories
Fxy
4 7 1 1L
Fxy
4 7 1 1E
Fxy
4 7 1 1EL
6.3 Change-Enabling Function
Although it is possible to select any address and read theassociated value by pr
essing the up and down keys, itis not possible to switch directly to the input mode.
Thissafeguard prevents unwanted changes in the protectivesetting. If the protec
tive setting is to be changed, thechange-enabling function (address 03 10) must
first beactivated. The change-enabling function is naturally theonly parameter t
hat can be changed when the change-enabling function itself is not activated.
Control Step or DescriptionActionDisplay
0
Select the address for the change-enabling function by pressing the
FxyER
00310
1
up and
down keys.
Press the enter key (E). The redLED indicator on the enter key willlight up. The
value can now bechanged by pressing the up or down keys.
E
FxyER
00310
2
Set the value to 1
FxyER
03101
3
up
keys.
Press the enter key (E). The redLED indicator on the enter key will goout. The c
hange-enabling function isactive.
E
FxyER
03101
Similar to alstom pd521
DTH31
Composite+Distribution+Relays+Brochure
33.DUOBIAS-M Relay Testing
MX3IPG2A-Rotor Ground Fault
Stability Testing of Tansformer REF Protection Scheme
7sd522 Siemens Test Procedures
NI 40-41_Technical Reference Manual
Power Protection Relays
Calculation for the Value of Stabilizing Resistor& REF Setting
61457757 Testing of Distnce Relay Rel 670
Transmission Line Protection
LBB & BUSBAR
Substation Automation
How to Test Distance Relay 7SA522