Neutral Grounding Calculation For Generator 7 MW PLTU ENDE

Data :
Rating MW = 8,1 MW diambil amannya 8,4 MW
kVA = 8,4 MW / 0,8 (pf) = 10,5 kVA
Vgen = 6,3 kV
Speed gen = 3000rpm

Capacitance of generator :
Cg

3 x [ ( Vg x 1000 ) +3600 )
0.75
40 x kVA
0.333

+3000
Cg

3 x [ ( 6300 x 1000 ) +3600 )


0.75
40 x 10500
0.333

+ 3000 Cg

4 1490,815
18910814.38

= 0.00219403 F
C surge Arrester
C cable to trafo gen
C trafo generator

= 0.3

= 0.0 F
= 0.0013 F

Maka total capacitance = 0.30349403 F


Estimasi capacitance pada sirkit generator
Ifc =

3 x 2 f x Ctot x kV x 103

Ifc =

3 x 2 50 x 0.30349403 x 6.3 x 103 =1.0408 Ampere

Pt = E x Ifc = 6.3 x 1.0408 = 6.5571 kVA


Kapasitas NGR = Pt/k = (6.5571 /2,8) x 1.1 = 2.576 kVA (diambil 3kVA)
Resistansi resistor Sekunder

Pr Ifc x
Ir=

E
3

= 1,0408 x

3.8 kW

Pr x 103
=3800/ 132.787 =28.5
E 2/ 3

Maka R =

230 / 3
=4.64
28.50