TROUBLESHOOTING FENWALNET 6000
Ba INTRODUCTION
This chapter lists all the error messages, their probable causes, and suggested procedures to return
the FENWALNET 6000 System to proper operating condition.
WARNING
Do not attempt any of the corrective actions listed in this chapter until you have:
+ Physically disconnected the wiring to initiator assemblies (if used) from the release-
circuit terminals, shorted the leads together, and wrapped the leads in insulating tape
+ Physically disconnected all control heads (if used) from their associated agent storage
container discharge valves
+ Physically disconnected the wiring to solenoid valves (if used) for pre-action/deluge-
sprinkler systems
+ Ensured that emergency operations controlled by this system such as facility power
shutoff are bypassed
+ Notified personnel in the facility and at off-premises monitoring locations that
you are working on the system and that you will inform them when system
servicing has ended.
‘Table 5-1. General System Events
‘AC Supply Fault on
TLoss or degradation of primary power
from commercial light and power company of loss of service.
company, Message will appear if AC Check connections to main circuit board
supply voltage drops to 85% or less of | TB13. Use voltmeter to check for nominal
the normal operating voltage 120/240 Vac at TBI.
Accompanied by message "System Check for proper setting of printed-ctreutt-
Changed Over to Battery Power" if seralats Beier Smee
standby battery used.
Notify commercial light and power
* Remove secondary and primary power.
Label and disconnect all field wiring.
Caution:
Disconnect all electrical control heads and
short together and tape wiring to initiators
Uf applicable)
Ensure AC Selector Switch on power
supply is correctly set for line voltage.
Re-install printed-circuit board, connect
field wiring, and apply primary and
secondary power if incorrect AC Selector-
‘Switch setting, Perform functional tests as
necessary‘Table 5-1. General System Events (Continued)
General System Events
Exror Message
Battery charging Fault on
Probable Cause
Fallure of the battery supervision
etreultry
Corrective Action
7 Check battery connections to main crcalt
Doard TBS,
+ Disconnect battery leads from main circuit
board TBS and use digital voit-ohm meter
to measure battery open-cireult voltage.
Replace batteries if open-circuit voltage 1s.
less than 19.5 Vde.
Replace the power supply assembly.
Replace printed-circutt board,
Battery Disconnected
Fault on
Faulty battery connection
Note: Rattery disconnected-fault
‘messages do not disappear immediately
when corrected. The control unit only
rechecks the battery connection once
per minute,
‘Check battery connections to main circuit
board TES.
Disconnect battery leads from main circuit
board TBS and use digital volt-ohm meter
to measure battery open-circuit voltage.
Replace battertes if open-circuit voltage is,
less than 19.5 Vde.
‘Configuration Memory
Checksum Failure
Tnternal software fault
‘Re-upload applications program
Re-test the system for proper functionality
‘configuration Memory
write Failure
Faulty upload of applications program
‘or improper execution of a configuration
change via the menu system
‘Re-upload applications program if
‘message occurs after configuration upload
Re-execute configuration change via menu
operation if message appears afler menut
operation
‘Control unit Ground Fault
=vde ON
‘Low impedance path between negative
fleld conductor and earth ground.
Normal earth-ground offset voltage is
6.6 Ve (nom.) relative to system
common (e.g. main circult board TB2-1
or TB2-3).
* Continuously monitor DC vollage between
carth-ground stud on left side of back box
and main circuit board TB2-1, Voltage
‘should be 6.6 (nom.) Vac. Earth ground is
positive relative to system common,
Remove field circuits one at a time until
carth-ground offset voltage restores to 6.6
(nom.) Vae,
‘Check for connections to earth ground on
feld eireutt whose removal restored
proper earth-ground offset voltage.
Control unit Ground Fault
+vde on
Low impedance path between positive
ficid conductor and earth ground.
Normal earth-ground offset voltage 1s
6.6 (nom.) Vde relative to system
common (e.g, main circutt board TB2-1
or TB2-3)
Continuously monitor DC vollage between
carth-ground stud on left side of back box
‘and main circuit board TB2-1. Voltage
should be 6.6 (nom) Vde. Earth ground is,
positive relative (o system common.
Remove field circuits one ata time until
earth-ground offset voltage restores to 6.6
(nom,) Vae,
Cheek for connections to earth ground on
field circuit whose removal restored
Proper earth-ground offset voltage.Table 5-1. General System Events (Continued)
General System Events
‘Error Message
‘control unit PSU Trouble
on
Probable Cause
“The power-supply output is too Tow
Corrective Action
* Check the power-supply connector, JT2.
from the power supply to the main
printed-cireuit board
+ Check for proper setting of printed-cireult-
board AC Selection Switch.
+ Remove secondary and primary power.
Label and disconnect all feld wiring.
Caution:
Disconnect all electrical control heads and
short together and tape wiring to initiators
(if applicabte)
Remove main printed-circutt board
Inspect connections of power-supply-
connector flying leads to power supply.
‘Tighten if necessary.
+ Ensure AC Selector Switch on power
supply Is correctly set for line voltage.
+ Re-install printed-circuit board, connect,
eld wiring, and apply primary and
secondary power if loose connection(s} or
‘meorreet AC Selector-Switch setting,
Perform functional tests as necessary
+ Replace power supply if no loose
connections or AC Seleclor-Switch
problem.
Event Memory Checksum
Failure on
Internal software fault
+ Use the control unit configuration
program to download the event log and
forward an electronic copy to Fenwal
‘Technical Services. Refer to the
configuration program user's guide.
+ Re-initialize the control unit by first,
moving, and then re-applying, primary
and secondary power sources
+ Functionally test the system
Event Memory write
Failure on
Internal software fault
+ Use the control unit configuration
program to download the event log and
forward an electronte copy to Fenwal
‘Technical Services.
+ Re-initialize the control unit by first
removing, and then re-applying, primary
and secondary power sources
+ Functionally test the system.Table 5-1. General System Events (Continued)
General System Events
Error Message
Tow Battery Fault on
Probable Cause
Discharged battery: Open-circult voltage
of two series-wired batteries must be
greater than 19.5 Vde.
Note: Low-battery fault messages do not
disappear immediately when corrected.
‘The control unit only rechecks the
battery voltage once per minute,
‘Corrective Action
* Disconnect battery leads Irom main circuit
board TBS and use digital volt-ohm meter
to measure battery open-circuit voltage.
Replace batteries if open-circutt voltage 1s
less than 19.5 Vee.
+ Reconnect batteries to TBS if open-cireutt
voltage ts greater than 19.5 Vde. Let,
batteries re-charge for 48 hours. Re-place
batteries if fault remains after 48 hours,
Main Board voltage
Reference Fault On
“The control unit has detected aystem-
common reference fault
* Check the power-supply connector. J12,
{from the power supply to the main
printed-cireuit board
+ Check for proper setting of printed-circutt-
board AC Selection Switch.
+ Remove secondary and primary power,
Label and disconnect all eld witing
Caution:
Disconnect all electrical contro! heads and
short together and tape wiring to initiators
(if applicable)
Remove main printed-ctrcult board. Inspe
connections of power-supply connector
fying leads to power supply. Tighten if
necessary.
+ Ensure AC Selector Switch on power
supply is correetly set for line voltage.
+ Re-install printed-ctreutt board, connect,
field wiring, and apply primary and
secondary power if loose connection(s) or
incorrect AC Selector-Switch setting,
Perform functional tests as necessary
+ Replace power supply if no loose
‘connections or AC Selector-Switeh
problem,
+ Replace printed-circuit board if fault
remains after replacement of the power
supply,
|
Printer Supervision Fault
‘Communications problem between
printer and the control unit or printer
port enabled but no printer ts connected
+ Check RS-232 cable between main printed
cireuit board and printer
‘+ Make sure printer 1s powered and
connected
+ Verily that the RS-232 port assigned to the
printer via the menu is correct. Refer to
+ Disable printer port if no printer 1s usedTable 5-1. General System Events (Continued)
General System Events
Error Message
Program Wenory Corrupt On
Probable Cause
Program memory seltest failure
‘Corrective Action
‘Use the control unit configuration
program to download the event log and
forward an electronte copy to Fenwal
‘Technical Services,
+ Re-initialize the control unit by frst
removing, and then re-applying, primary
and secondary power sources
+ Functionally test the system
‘SLC Communications Fault
on
‘This indicates that there has been a
‘communication problem between the
‘two processors on the control unit and
the SLC Is not being monitored.
* Use the control unit configuration
‘program to download the event log and.
forward an electronic copy to Fenwal
‘Technical Services,
+ Re-inttialize the control unt by frst
removing, and then re-applying, primary
‘and secondary power sources
+ Functionally test the system.
‘SLC Open Circuit on
‘Open cireuit in the feld wiring
connected to main circult board TBI.
Applies to Class-A wiring only
* Look for discontinuity in SLC wiring,
SLC Short Circuit on
‘Short circuit in the field wiring
connected to main circuit board TB1
+ Troubleshoot SLC wiring by breaking up
Circuit to isolate short circuit (0 specific
branch or leg,
Date/Time Must Be Set
Trouble on
‘Message appears each time the control
unit is re-iniualized by applying AC and
then DC power.
+ Set the date and time as instructed in‘Table 5-2. Control-Unit-Based-Output Events
‘Control-Unit-Based-Output Events
Error Messoge
"ART Open Circuit Trouble On
‘Probable Cause
‘Open circuit in eld wiring connected to
main clreult board TB12
Corrective Action
TLook for discontinuity in Release
feld wiring
‘ARI Short Circuit Trouble On
‘Short circuit in field wiring connected
to main eireutt board TB12
* Troubleshoot Release-1 wiring by
brealeing-up circuit to isolate short
treutt to specific leg
‘AR2 Open Circuit Trouble On
‘Open circuit in eld wiring connected to
‘main circult board TBI
| Look for discontinuity in Release-2
feld wiring,
‘AR2 Short Circuit Trouble On
‘Short circuit im feld wiring connected
to main cireutt board TBI
* Troubleshoot Release-2 wiring by
breaking.up elreult to isolate short
ctreutt to specific leg
‘ARS Open Circuit Trouble On
‘Open elreult in field wiring connected to
‘main clreult board TB7. Combo-1
Circuit is configured as a release
circuit.
* Look for discontinuity in Combo-1
field wiring, Refer to
‘ARS Short Cireuit Trouble On
|
L
Short circuit m feld wiring connected
to main circuit board TB7. Combo-1
CCireutt 1s configured as a release
cetreult,
+ Troubleshoot Combo-1 wiring by
breaking-up circuit to tsolate short
ctreult to specific leg
[AR4 Open Circuit Trouble On
I
‘Open circuit infield wiring connected to
main circuit board TB6, Combo-2
Circuit is configured as a release
atreutt,
* Look for discontinuity in Combo-2
field wiring,
'AR4 Short Circuit Trouble On
Short circuit mn Meld wiring connected
(o main etreuit board TB6. Combo-2
CCireutt ts configured as a release
etreutt
+ Troubleshoot Combo-2 wiring by
breaking-up circult to isolate short
ctreutt to specific leg
‘SGI Open Circuit Trouble On
‘Open circuit i field wiring connected to
main circuit board TBS
> Check for missing 10k end-ofline
resistor,
+ Look for discontinulty in NACI fleld
wiring
‘SGI Short Cireuit Trouble On
‘Short cireuit in Neld wiring connected
to main circuit board TBS
+ Troubleshoot NACI wiring by
breaking-up circuit to isolate short
Circuit to specific leg
‘SG2 Open Circuit Trouble On
(Open circuit infield wiring connected to
‘main circult board TB14
* Check for missing 10k end-of line |
resistor.
+ Look for discontinuity in NAC2 field
wiring
'SG2 Short Circult Trouble On
‘Open circuit in field wiring connected to
‘main circuit board TB14
> Troubleshoot NAC2 wiring by
brealeing-up circu to isolate short
etreutt to specific leg
‘SG8 Open Circuit Trouble On
‘Open circuit in field wiring connected to
‘main circuit board TB7, Combo-1
Circuit is configured as a NAC.
+ Check for missing 10k end-of.line
resistor.
+ Look for discontinuity in Combo-1
field wiring
‘SG Short Circuit Trouble On
‘Short circuit in Neld wiring connected
to main circuit board TB7. Combo-1
CCireutt is configured as a NAC.
+ Troubleshoot Combo-1 wiring by
breaking.up circuit to isolate short
treult to specific legTable 5-3. SLC Events (Continued)
SLC Events
Error Message
Fault
Signal/Sounder
Probable Cause
"The ASM at address Addr failed to
activate upon receipt of an activation
‘command
Corrective Action
“Check SLC wiring,
Ensure that wiring-
resistance and capacitance
limitations have not been exceeded,
+ Visually inspect the ASM to ensure
that its red LED is flashing. Use
Handheld Programmer to test the
device # the LED is not flashing.
Refer fo Appendix D. Replace the
‘ASM if i fails the Handheld-
Programmer test.
+ Functionally test the existing or
replaced ASM
Replace the
‘ASM if It falls the functional test.
+ Functionally re-test the ASM for all
‘configured actuation scenarios.
‘Addr Outpat Trouble On
‘Signal/Scunder
‘Open oF short circuit in notufication-
appliance circuit for ASM at address
+ Refer (o ASM Installation
+ Look for discontinulty in NAC wiring
to find open circutt.
* Check for missing 4,7k end-ofline
resistor.
+ Troubleshoot NAC wiring by
breaking-up circuit to isolate short
ctreult to specific leg
‘Addr Overheai On Alarmline Module
‘An AlarmLine cable being monitored by
fan AM and configured for overheat
detection is reporting an overheat
condition. This ts not an error message.
‘The control unit's buzzer will sound but
no LED on the membrane will
iMluminate, Notification will ony occur if
programmed via an EOC statement.
+ Check the monitored area for
excessively-high temperature,
+ Start air-conditioning units to lower
temperature in monitored area.
‘Addr PSU Open Circuit On
Signa/Sounder
‘Loss of 24 Vde signal to power input
‘circuit of ASM at address Addr.
> Refer to ASM Installation
+ Check 24 Vde power connections to
ASM.
+ Ensure that the ASM's Jumper P1
land Switch SI are set for 24 Vde
operation
+ Check auxiliary power supply for
faults.
‘Adar PSU Short Cireult On
‘Signal/Sounder
“Appearance of O Vae signal at power:
‘mput circuit of ASM at address "Addr
> Refer to ASM Installation
+ Check 24 Vde power connections to
ASM.
+ Ensure that the ASM's Jumper Pl
and Switch SI are set for 24 Vde
operation
* Check auxiliary power supply for
faults,. SLC Events (Continued)
‘SLC Events
Error Message
“Addr RAM Fault ON
‘Probable Cause
"The device at address Addr Is Feporting
fan internal software fault
Corrective Action
~ Replace the device
‘Addr Sensor Fault On AlarmLine
Module
‘A problem in the AlarmLine cable being
‘monitored by an AM.
+ Check the AlarmlLine wiring
connections to the AM.
+ Refer to AlarmLine Installation,
‘Addr Trouble Open On Device Type
‘Loss of communications to device at
address Addr
> Check device connections to SLC
wiring
+ Ensure that device has not been
removed
+ Check SLC wiring for excessive
capacitance and/or resistance if the
device LED is blinking.
Rewire SLC using
recommended wire in Appendix B.
‘Addr Type Error On Device Type
“The device at address Addr ts reporting
1a device type that is different from the
Iype of device that is configured for that
address
+ Ensure that the device installed at
address Addr matches the device type
configured for that address, Install
corrected device or correct
configuration fle and re-upload
application,
+ Use Handheld Programmer (o lest the
device ifthe device type matches the
entry in the configuration fle. Refer to
Appendix D. Replace the device if it
falls the test or if the error message
relurns when the device is re-
installed.
+ Intermittent type errors could be a
symptom of SLC wiring problems
Check SLC wiring ifrandom errors
are reported.
Ensure that wiring-reststance and -
‘capacitance limitations have not been,
exceeded,Table 5-5. Remmote-Display/Annunciator Events
‘Remote-Display/Annunciator Events
RDCMAddr Communication Fault On
‘A communteations fault between the
‘main printed cireutt board and the
RDCM at address Addr.
‘Error Message Probable Cause Corrective Action
* Check the RS-485 wiring from main
printed ctreuit board Terminal Block
‘TRIS to RDCM Terminal Block TB1.
Check for a discontinuity in the RS-
485 fleld wiring to RDCM (TBI.
‘Terminals 5 and 6 and 7 and 8)
‘Troubleshoot wiring to RDCM TBI.
Terminals 5 and 6 and 7 and 8, by
breaking-up the cireuits to isolate
short circuit to specific leg or legs.
‘Check for 24 Vde power at RDCM
‘TBI, Terminals 1 and 2.
+ Ensure that the RDCM's RS-485
‘Termination Jumper W2 is set
correctly.
Ensure that the RDCM Address
‘Switch SI is set correctly,
+ Check for duplicate addressed
RDCMs,
RDCMAddr Noi Registered On
‘The control unit has not been set up 10
expect the RDCM at RDCM RS-485
ctreuit address Addr.
Register the RDCM if part of system
configuration. See Paragraph
De-register the RDCM If not part of
system configuration,
(Check the 24 Vde power (TBI.
‘Terminals 1 and 2) and RS-485
‘communications wiring (TB1.
‘Terminals 5 and 6 and 7 and 8) from
the control unit to the RDCM.
Ensure that the RDCM Address
‘Switch SI 1s set correctly.
RDCMAdar PSU Faull On
‘Aloss of 24 Vae power ai TBI,
‘Terminals 1 and 2 or an open circuit in
the RDCM's monitoring circuit from
‘TBI, Terminals 3 and 4 to the
normally-closed trouble contacts of its
associated remote power supply
‘Check for 24 Vde power at RDCM
‘Terminals 1 and 2.
Look for discontinuity in wiring from
‘Terminals 3 and 4 to remote-power-
supply trouble contacts. Jumper
these terminals if you are using the
FENWALNET 6000 Control Unit to
power the RDCM,
Check for trouble with third-party
remote power supplyFENWALNET 6000 Menu Functions and Top-Level Displays,
ee
scutieates | 3 Oc ant
>) eta a bet arenas