ESTIMATED ELECTRICAL POWER PARAMETERS

DC MACHINES
2300XPC
50

TON CLASS

AC MACHINES

4100C
4100C BOSS
90

2800XPC
70

4100XPC
115
also 4100XPB

4100C BOSS
90

4100XPC
120

DC NOMINAL COMPENSATION
@ 600 VAC, 50/60 HZ
Steps
IDLE kW
IDLE kVARS

+5250 / 4725 kVAR


6/7

+5250 / 4725 kVAR


6/7

+5250 / 4725 kVAR


6/7

+6000 / 4725 kVAR


8/7

200 kW
-150 kVAR

200 kW
-150 kVAR

225 kW
-200 kVAR

250 kW
-200 kVAR

225 kW
-200 kVAR

250 kW
-200 kVAR

PEAK kW CONSUMED
APPROX.
DURATION OF PEAK
> 1 SEC.
1 SEC.
< 1 SEC.

2250 kW
2800 kW
3150 kW

2600 kW
2300 kW
3600 kW

3100 kW
3700 kW
4125 kW

3225 kW
3850 kW
4300 kW

3100 kW
3700 kW
4125 kW

3225 kW
3850 kW
4300 kW

POTENTIAL MAX.
CALCULATED

3650 kW

4100 kW

4800 kW

5000 kW

4800 kW

5000 kW

CONSERVATIVE EST.
QUOTE

2800 kW

3300 kW

3700 kW

3850 kW

3700 kW

3850 kW

REGENERATED POWER
TYPICAL

1400 kW

1700 kW

1800 kW

1900 kW

1800 kW

1900 kW

PEAK

1600 kW

1800 kW

2000 kW

2100 kW

2000 kW

2100 kW

400 - 800 kW

600 - 1000 kW

800 - 1250 kW

920 - 1450 kW

800 - 1250 kW

920 - 1450 kW

600 kW

800 kW

975 kW

1150 kW

975 kW

1150 kW

AVERAGE kW CONSUMED
AVERAGE RANGE
TYPICAL

POWER FACTOR ESTIMATES


AVERAGE
EST. @ PEAK kW

0.85 - 1.0 LAG

0.85 - 1.0 LAG

0.85 - 1.0 LAG

0.85 - 1.0 LAG

.996 LAG

.996 LAG

-0.95

-0.95

-0.95

-0.95

-0.98

-0.98

2000 KVA

2750 KVA

3300 KVA

3750 KVA

3300 KVA

3750 KVA

16 MVA

22 MVA

25 MVA

30 MVA

25 MVA

30 MVA

RECOMMENDATIONS
SUB-STATION
MINIMUM SHORT
CIRCUIT AVAILABLE
@ SHOVEL

NOTES:
The numbers are conservative estimates based on calculation and field data.
All numbers should be considered approximate with a tolerance of +/- 10%
Power parameters greatly depend on digging conditions, operator techniques and proficiency and general pit operating conditions.
DEFINITIONS:
POTENTIAL MAX. CALCULATED
HOIST + CROWD + SWING OPERATING @ THEIR POTENTIAL PEAK POWER.
This condition will not likely occur in a truck loading situation. The maximum potential peak power for a loading situation is based on the HOIST +
CROWD operating at peak power + Swing @ 1/2 MAX. speed. The occurrence is momentary; > 1 SEC.
AVERAGE kW CONSUMED
AVERAGE RANGE
The range is given because of the wide range of operational and digging conditions.
TYPICAL
The typical value is most likely to be encountered.
Demand values are based on the highest average kW, for a set interval of time, over a longer period of time.
Source: ER 39.05.05.10

15 min. Demand

est. 1.15 x TYPICAL AVE. kW CONSUMED

30 min. Demand

est. 1.1 X TYPICAL AVE. kW CONSUMED

This is proprietary and confidential information of P&H Mining Equipment

Revised: 12/10/08