Here is the prelim spec. and no. of ckt.

for AC cables:
BSS(consumer):
1. 132kV cable from TNB BSS to BSS (consumer) = 132kV cable, 630sq.mm cable XLPE cable
- pls. follow TNB standard 132kV XLPE cable specification
2. 132kV cable from GIS to 90MVA Power Tx. - 132kV, XLPE, 630sq.mm TNB
standard 132kV XLPE cable specification
3. 33kV cable from 60MVA Power Tx to 33kV GIS incomer - 33kV, XLPE, 630sq.mm
cable 2nos per phase.
4. 33kV cable from 60MVA Power Tx to Earthing Tx. cable box - 33kV, XLPE,
630sq.mm cable 1no per phase.
5. 33kV cable from Earthing Tx. cable box to NER DS - 33kV, XLPE, 630sq.mm
cable 1no.
TPSS:
To follow tender specification for the type of cables.
6. 33kV Cable from 33kV Sw.Gr. to Rectifier Tx. - 33kV, XLPE, Cu.185sq.mm
cable 2nos. per phase
7. 33kV Cable from 33kV Sw.Gr. to Stn.ser.Tx. - 33kV, XLPE, Cu.185sq.mm cable 2nos.
per phase
8. 33kV Interconnecting Cable from TPSS 33kV Sw.Gr. to TPSS/STN 33kV
Sw.Gr. - 33kV, XLPE, 185sq.mm Cu.cable 2nos. per phase
9. 0.6/1kV Cable from Rectifier Tx LV-1 to Rectifier panel-1 - 0.6/1kV,300sq.mm
Cu.EPR/EVA/SWA/EVA cable 3nos per phase.
10. 0.6/1kV Cable from Rectifier Tx LV-2 to Rectifier panel-1 - 0.6/1kV,300sq.mm
Cu.EPR/EVA/SWA/EVA cable 3nos per phase.