For some new conductors** the resistance data (in /km) for Zebra equivalent size

is given in following Table. The reactance(X) and susceptance (B) values of line

mainly depend on the tower configuration, and therefore the X and B values (in per

unit / km / circuit) may be taken from Table I(a) above for similar configuration.

DC

Resistance AC Resistance values at different temperatures (in /km)

Name of

Conductor

20 o C 20o C 75 o C 85 o C 95 o C 120 o C 150 o C 175 o C 200 o C

ACSR 0.06868 0.6868 0.08479 0.0875 NA NA NA NA NA

AAAC 0.06921 0.0704 0.08541 0.08814 0.09093 NA NA NA NA

TACSR 0.07560 0.07668 0.09315 0.09613 0.09912 0.10662 0.11565 NA NA

AL59 0.07805 0.0791 0.09610 0.09918 0.10230 NA NA NA NA

ACSS 0.08430 0.08527 0.10366 0.1070 0.11034 0.11872 0.12878 0.13718 0.14557

STACIR 0.08000 0.08105 0.09847 0.10163 0.10479 0.11274 0.12229 0.13025 0.13822

ACCC 0.05510 0.05656 0.06844 0.07062 0.07279 0.07821 0.08475 0.09021 NA