A.BASIC DATA
1. Item No. :
2. Rated Voltage : 33,000 Volt
3. Desired Power Factor (P.F) to Improve ( Cos 2) : 0.900
B. FORMULA
Active power (kW)
(*1) kvar1 = kW x tan1 = kW x sqrt [ ( 1 / cos12 ) - 1 ]
kvar2 = kW x tan2 = kW x sqrt [ ( 1 / cos22 ) - 1 ] 2
(*2) ckvar = kW x ( tan 1 - tan2 ) KVAnew
kvar2
= kW x {sqrt [( 1 / cos 12 ) - 1 ] - sqrt [( 1 / cos22 ) - 1 ] } 1
kvar1
2 2
(*3) Expected power factor (P.F) : cos = kW / sqrt { kW + (kvar1- ckvar ) }
ckvar
Apparent Power (KVAold)
D. RESULT
D.1. Conclusion
Required capacity of the capacitor = 5,000 kvar to improve the power factor to 0.905 , is enough.
So, in consideration for the possibility of the changeable load characteristic,
Power capacitor, 33 kV, 9,000 kvar, (4500kvar x 2 sets) will be provided.
Load Status
1 At Demad Load 85,605 45,220 96,815 9,000 36,220 92,952 0.921 Lagging
2 At 70% Operation Load 59,924 31,654 67,770 9,000 22,654 64,063 0.935 Lagging
3 At 50% Operation Load 42,803 22,610 48,407 9,000 13,610 44,914 0.953 Lagging