48
Reference data
442 Capacity, K
Most valve manufacturers and damper manufacturers
{quote the performance of their components in terms of
‘capacity, K; defined in the following relationship
= KVEB (413)
‘This implies that K has units, usually of m*-h-Lbar-*S for
liquids, or m*-s"LPa- for gases, Some manufacturers may
quote values of K with different units so care is needed.
‘There is a relation between Kand &, but it is not really
necessary {0 convert one to the other. Pressure drops are
‘more simply calculated separately for those components
Tor which Kis given,
Kis also useful when dealing with the authority of a valve,
and in the prediction of flows in complex circus, Further
{information can be obtained from Appendix 4.43.
45 Water flow in pipes
4.5.1 Pipe sizing: desirable velocities
There are no rules concerning pipe sizing. The most cost
effective will be the design based on life-cycle costing
including the pumping costs. The smaller the pipework,
the greater the pumping power and energy consumption.
Increasing the pipe diameter by one size can have a large
effect in decreasing pumping power: smaller friction
pressure drops of the basic circuit will require smaller
pressure drops through control valves, forthe same value
of valve authority. The optimum sizing from the point of
view of life-cycle costing must consider the length of the
system, the capital cost, the mean pressure drop, the
running time at full and partial flow, the efficiency of the
pump-motor combination, and anticipated electrical
tariffs (Le ‘on-peak’ or ‘off-peak’ operation)
“To give a starting point in selecting pipe sizes, rule of
thumb water velocities are reproduced from BSRIA)
(1995) in Table 46. An alternative starting point might be
to consider a typical pressure drop per unit length of
360 Pam) or 250 Pam, but this is arbitrary.
Ultimately sizing ought to be based on life-cycle costing,
“Table 46 ‘ypical water velocities for pipework BSRIA
Velocity Thal presse
me seop kPa
Srallboe =i =
Diam. > 50 mm 125.20 -
eatingleooing coils 8
452 Noise
‘With small pipes, excessive velocities can lead to noise
generation where, with hot water, cavitation may occur at
elbows, valves, pumps and especially orifice plates. Some
information has been provided by Ball and Webster")
and Rogers!™, In this respect larger pipes should be able
to tolerate higher velocities without a noise problem,
Similarly higher velocities are possible with polymer
piping due to the noise absorption effet of such piping.
Noise problems are more likely to occur if entrained air is
not separated and vented. Arrangements should be made
so that this is achieved easily. An upstand and air vent at
the top of each vertical run of pipe is recommended,
during pump-off periods, entrained air will separate out
into the higher position. This will simultaneously reduce
corrasion by eliminating oxygen as soon as possible.
45.3 Allowances for ageing
Corrosion and scaling of the internal diameter of pipework
‘will occur with age depending on the chemical composi
tion of the water. This will increase the surface roughness
of the pipe and decrease the internal diameter, both of
which Will increase the friction pressure drop. No firm
recommendation can be made on the allowance to be
made. A large allowance is more justifiable with small
diameter pipes. Open systems will suffer more than closed
systems. ASHRAE" reports others finding an increase of
15 to 20% in the friction factor 4, compared with new
pipework. This was for closed systems, For open systems,
there could be a 75% increase. ASHRAE also reports that
‘work of the Plastic Plastic Pipe Institute (1971) shows that
there is little corrosion with plastic pipe.
45.4 Water hammer
Large pressures can arise when the fluid flow és stopped
abruptly by the sudden closure of a valve. This pressure
wave then reverberates within the pipework. The
magnitude of the pressure wave is in proportion to the
‘momentum of the flowing fluid and thus to its velocity.
45.5 Water expansion
Between a heating system being cold (usually under the
fill’ situation), and warm under the design running
condition, the water contained in the system will expand
‘The expansion, as a percentage, has been calculated with
reference to a cold situation of 4°C using
ay)
The volumetric expansion of the pipework may be
deduced from the volumetric expansion of the water, if
desired. Values of the density of water are given in Table
47. Pre-calculated values for the expansion of water are
given in Table 48,
45.6 Buoyancy; thermosyphon
In any closed system, when one vertical section of the
pipework is at a different temperature from another, a
pressure difference will exist and create a driving pressure
difference so as to cause a natural thermosyphon. Using
equation 49, some pre-calculated values for hot water are
given in ‘Table 49.