Qu debe cubrir?
Choque elctrico - Por qu tener ICFTs?
Cmo funcionan los ICFTs
Instalacin correcta de un ICFT
Errores de cableado
Deteccin del neutro puesto a tierra
Comprobacin de los ICFTs
The Association of Electrical and
Medical Imaging Equipment Manufacturers
Electrocuciones
# de ICFTs # de
Electrocuciones
The Association of Electrical and
Medical Imaging Equipment Manufacturers
10A Fibrilacin de 50 mA a 4 A
4A
50mA
30mA Dificultad para respirar normas de RCD de IEC,
Fibrilacin en nios
15mA "Congelacin" muscular en el 50 % de la poblacin
10mA Umbral de soltar
4-6 mA UL 943 Nivel de disparo del ICFT Clase A de 4-6
1mA Nivel de percepcin
The Association of Electrical and
Medical Imaging Equipment Manufacturers
N 6A
EGC 5.94 A
Falla a tierra
0.06 A
The Association of Electrical and
Medical Imaging Equipment Manufacturers
0.1 A
The Association of Electrical and
Medical Imaging Equipment Manufacturers
IEntrada
L1 Carga
N
L2 120/240 V
ISalida
N Carga
Qu hay en el ICFT?
(Receptculo)
Botn de restablecimiento
Botn de prueba
Cubierta
Mecanismo de resistente a la
manipulacin (Opcional)
Puente
Contactos de la cara
Barrera en medio
Terminales Terminales
Circuito impreso
Base
The Association of Electrical and
Medical Imaging Equipment Manufacturers
Qu hay en el ICFT?
(Receptculo)
Cara
Lnea
Carga
viva
Lnea
viva Cara
Terminales de carga
Terminales de lnea
Carga
Neutro Neutro
EGC
Qu hay en el ICFT?
(Interruptor automtico)
Botn presionar
Disparo de sobrecorriente para probar Solenoide de disparo
Cable del
Mecanismo
neutro del
de disparo
tablero
Terminal de
"Energa de la
Contactos
carga"
conductores de
corriente del Bobina de
primario deteccin
Qu hay en el ICFT?
(Interruptor automtico)
Circuito electrnico Botn presionar para probar
con deteccin del
Solenoide de disparo neutro puesto a tierra
Resistencia de prueba
Mecanismo
de Disparo Bobina de deteccin
Terminal de Terminal de
la "Lnea" "Energa de la
carga"
Qu hay en el ICFT?
(Conexin directa)
Dispositivo de
bloqueo
electromecnico
Sensores del
neutro puesto
a tierra y
desequilibrio
de la corriente
The Association of Electrical and
Medical Imaging Equipment Manufacturers
Qu hay en el ICFT?
(Conexin directa)
Botn presionar para probar
Dispositivo de
bloqueo Sensor del neutro
electromecnico puesto a tierra y
desequilibrio de la
Resistencia
corriente de 15 k
Lnea viva
de la carga
Neutro de
la carga
EGC
Circuitos con
deteccin del
neutro puesto
a tierra y
abierto
The Association of Electrical and
Medical Imaging Equipment Manufacturers
INTERRUPTOR
120 AUTOMTICO 120
MONOPOLAR
120 CON ICFT
240
NEUTRO
N
TIERRA DEL EQUIPO
TIERRA
The Association of Electrical and
Medical Imaging Equipment Manufacturers
Terminales
de lnea Terminales
de carga
N
The Association of Electrical and
Medical Imaging Equipment Manufacturers
INTERRUPTOR
120 AUTOMTICO 240
BIPOLAR CON ICFT
120
240
LNEA VIVA A
N
TIERRA DEL EQUIPO
TIERRA
The Association of Electrical and
Medical Imaging Equipment Manufacturers
Carga de 120/240 V
Fuente de 120/240V c.a.
N L1 L2
LNEA VIVA B
LNEA VIVA A
NEUTRO
INTERRUPTOR
120 AUTOMTICO CARGA DE
BIPOLAR CON ICFT 120/240 V a.c.
120
240
N
TIERRA DEL EQUIPO
TIERRA
The Association of Electrical and
Medical Imaging Equipment Manufacturers
1A
L
120 V
N
1A
The Association of Electrical and
Medical Imaging Equipment Manufacturers
Circuitos multi-cables
Una parte del circuito multi-cables en uso
1A
120 V 1A
120 V
0A
Interruptor abierto
The Association of Electrical and
Medical Imaging Equipment Manufacturers
Circuitos multi-cables
Ambas partes del circuito multi-cables en uso
1A
120 V 0A
120 V
1A
120
INTERRUPTOR
120 AUTOMTICO NEUTRO
BIPOLAR CON ICFT
120 LNEA
VIVA A
240 120
N NEUTRO RECEPTCULO
DOBLE
TIERRA DEL EQUIPO
TIERRA
The Association of Electrical and
Medical Imaging Equipment Manufacturers
Neutros separados
T R
R T
Receptculos con ICFT
Receptculos Receptculos
inferiores inferiores
The Association of Electrical and
Medical Imaging Equipment Manufacturers
N
?
6A
L2
Al tablero
de control
Al receptculo
inferior
En el caso de cableado
incorrecto no habr energa
en la cara o inferior.
The Association of Electrical and
Medical Imaging Equipment Manufacturers
INTERRUPTOR
120 AUTOMTICO
UNIPOLAR CON ICFT
120
RECEPTCULO
240
DOBLE
N NEUTRO
TIERRA DEL EQUIPO
TIERRA
The Association of Electrical and
Medical Imaging Equipment Manufacturers
EGC ?
Equipo
Pruebas de UL al ICFT
Cada ICFT debe pasar las pruebas siguientes al
final de la lnea de fabricacin:
1. no dispara por debajo de 4mA (sin carga)
2. debe disparar a 6mA (sin carga)
3. no dispara por debajo de 4mA (con carga) en la tensin
asignada
4. debe disparar a 6mA (con carga) en la tensin asignada
5. debe disparar con neutro puesto a tierra de 2
6. debe disparar dentro de 25 ms con falla de 500
7. debe disparar con el botn de prueba al +10/-15 % de la
tensin asignada
8. no debe disparar con la prueba de ruido de la Norma del
ICFT
9. prueba de calibracin al +10/-15 % de la tensin
asignada
The Association of Electrical and
Medical Imaging Equipment Manufacturers
Botn de restablecimiento
The Association of Electrical and
Medical Imaging Equipment Manufacturers
Resumen
Los ICFTs han contribuido significativamente a la
reduccin en el nmero de muertes debidas al choque
elctrico
Los ICFTs ven la corriente que sale y la comparan con la
corriente que regresa
Recuerde que los ICFTs detectan las conexiones de tierra
al neutro inferior
Probar el ICFT utilizando el botn de prueba y una carga
Los ICFTs no protegern entre lnea y neutro
Slo los ICFTs Clase A (6 mA) protegen de electrocucin