PG-CA-1109
For 5kV-35kV
Distribution Systems
Loadbreak & Deadbreak
Separable Connectors
Cable Joints
Cable Terminations
PG-CA-1109 Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com 1
CABLE ACCESSORIES
Ratings
Elastimold Separable Connectors, Cable Joints, IEEE 592 Standard For Exposed
Certified Tests and
applicable portions of IEEE, ANSI and other and Aluminum Conductor Connectors
industry standards including: AEIC CS8 Standards For XLP
IEEE 386 Standard For Separable Connectors and EPR Insulated Cables
IEEE 404 Standard For Cable Joints and Splices ICEA S-94-649-2004 and S-97-682-2000 Standard
IEEE 48 Standard For Cable Terminations for Cables Rated 5,000 46,000 Volts
TABLE 1 15kV Class Ratings 25kV Class Ratings 35kV Class Ratings
OPERATING VOLTAGE 8.3kV 15.2kV 21.1kV
Maximum line-to-ground
(See Application Info Note 1)
BIL Impulse withstand 1.2 x 50 microsecond wave 95kV 125kV 150kV
WITHSTAND VOLTAGE
AC One Minute 34kV 40kV 50kV
DC Fifteen Minute 53kV 78kV 103kV
CORONA EXTINCTION LEVEL @ 3pC Sensitivity 11kV 19kV 26kV
200 AMP Products
Continuous Current: 200 AMP*
Symmetrical Momentary Current: 10kA sym, 10 cycle duration
600 Series Products
Continuous Current: 600 and 900 AMP*
Symmetrical Momentary Current: 25kA sym, 10 cycle duration
* Designed for 90 C maximum continuous operating temperature
25kV 1 and 3 circuits 15.2kV line to ground, 26.3kV 1 fault close operation at 15.2kV or 26.3kV; 10,000
Class Ratings max. across open contacts. Amps, rms, sym. 10 cycles (0.17 sec.) 1.3 max.
10 loadmake/break operations at 200 Amps max. asym factor applies to new or used mating parts
with 70 to 80% lagging power factor. (up to maximum designated switching operations.)
35kV 1 and 3 circuits 21.1kV line to ground, 36.6kV 1 fault close operation at 21.1kV or 36.6kV; 10,000
Class Ratings max. across open contacts. Amps, rms, sym. 10 cycles (0.17 sec.) 1.3 max.
10 loadmake/break operations at 200 Amps max. asym factor applies to new or used mating parts
with 70 to 80% lagging power factor. (up to maximum designated switching operations.)
Application Information:
1. Loadbreak connectors are designed and rated for use on grounded WYE systems. For application on ungrounded WYE or delta systems, the
next higher voltage class product is recommended. Examples: 5kV ungrounded: use 15kV class products; 15kV ungrounded: use 25kV class
products; 25kV ungrounded: use 35kV class products.
2. Products are designed and constructed for all applications including padmount, subsurface, vault, indoor, outdoor, direct sunlight, direct buried
and continuously submerged in water.
3. Products are designed and rated for ambient temperatures of -40 C to +65 C. It is recommended that loadbreak connectors be hotstick
operated at -20 C to +65 C ambient temperature range and at altitudes not exceeding 6000 feet.
2 Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com PG-CA-1109
CABLE ACCESSORIES
Standard Interfaces
Connector Interfaces
Components and Equipment Bushings
Separable
ANSI/IEEE Standard 386 defines the specific inter- interchangeability. The table below provides infor-
face dimensions that 200 Amp and 600 Series mation concerning the types of interfaces supplied
elbows, inserts, junctions, equipment bushings and by Elastimold for various applications and is useful
any mating components must conform to insure to assure proper matching of components.
200 AMP DEADBREAK INSERT 15kV and 25kV 200 AMP Deadbreak IEEE
8.3kV and 15.2kV E 386-2001
E Fig. 4
600 SERIES EQUIPMENT BUSHING 15kV and 25kV 600 AMP Deadbreak IEEE
Interface No.1
F 386-2001
F 8.3kV and 15.2kV Fig.11
NOTES:
1. Elastimold uses Fig. 7 interface for both 25 and 35kV applications.
PG-CA-1109 Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com 3
CABLE ACCESSORIES
200 Amp Loadbreak
RATINGS OVERVIEW
200 AMP LOADBREAK SEPARABLE CONNECTOR COMPONENTS
See page 2 for complete information
including switching and fault close
ratings. CABLE TO EQUIPMENT
CONNECTIONS
LOADBREAK
BUSHING INSERT
15kV Class
SEE CABLE NOTES
8.3kV Phase-to-Ground
14.4kV Phase-to-Phase BUSHING WELL
LOADBREAK
FEED-THRU INSERT
95kV BIL PLUG
REPLACEMENT
34kV AC Withstand ELBOW
40kV AC Withstand
78kV DC Withstand
19kV Corona Extinction GROUNDING
PARKING PLUG
35kV Class STAND
FUSED ELBOW
21.1kV Phase-to-Ground
36.6kV Phase-to-Phase INSULATED CAP
150kV BIL
50kV AC Withstand FEED THRU
SEE PRODUCT
103kV DC Withstand GUIDE PG-PC-H
TEST ROD
ASSEMBLY TOOL
4 Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com PG-CA-1109
CABLE ACCESSORIES
200 Amp Loadbreak
Illustration Description Voltage ELASTIMOLD Notes Illustration Description Voltage ELASTIMOLD Notes
(not to scale) Class Part Number (not to scale) Class Part Number
Elbow 15kV 165LR-W5X N2,3,4,5 Insulated Cap 15kV 168DRG N7
Connector Use Tables W1 and X1 w/ Ground and 25kV 274DRG N7
25kV 275LR-W5X N2,3,4,5 Test Point 35kV 376DRG N7
Use Tables W16 and X1 Grounding Plug 15kV 161GP
35kV 375LR-W5X N2,3,5 (1/0 AWG x 6 25kV 272GP
Use Tables W3 and X2 Ground Lead)
Elbow 15kV 166LR-W5X N2,3,4,5, Grounding 15kV 160GLR
Connector Use Tables W1 and X1 24 Elbow 25/35kV 370GLR N12
w/ Test Point 25kV 276LR-W5X N2,3,4,5, (1/0 AWG x 6
Use Tables W16 and X1 24 Ground Lead)
35kV 376LR-W5X N2,3,5,24 Feed-Thru 15kV 164FT
Use Tables W3 and X2 25kV 274FT
Jacket Seal 15kV 165LRJS-W5X N2,19 35kV 371FT N6
Separable Connectors
Elbow Use Tables W1 and X1 35kV 373FT
Connector Feed-Thru 15kV 164FTV
200A Loadbreak
Vertical 25kV 274FTV
25kV 275LRJS-W5X N2,19 35kV 373FTV
Use Tables W16 and X1 Adjustable Bracket 15kV 164FT2-AB N23
2-point Feed-Thru 25kV 274FT2-AB N23
Jacket Seal 15kV 166LRJS-W5X N2,19,24 35kV 373FT2-AB N23
Elbow Use Tables W1 and X1 Adjustable Bracket 15kV 164FT3-AB N23
Connector 3-point Feed-Thru 25kV 274FT3-AB N23
35kV 373FT3-AB N23
w/ Test Point 25kV 276LRJS-W5X N2,19,24 Adjustable Bracket 15kV 164FT4-AB N23
Use Tables W16 and X1 4-point Feed-Thru 25kV 274FT4-AB N23
35kV 373FT4-AB N23
Repair Elbow 15kV 167ELR-W5X N5,10,18 Feed-Thru 15/25kV K1601WFT
Connector Use Tables W5 and X1 Well
25kV 273ELR-W5X N5,10,18 Feed-Thru 15/25kV K1601WFTV
Use Tables W5 and X1
Well Vertical
Repair Elbow 15kV 168ELR-W5X N5,10,18, Insulated 15kV 161SOP N20
Connector Use Tables W5 and X1 24 Parking Bushing 25kV 272SOP N20
w/ Test Point 25kV 274ELR-W5X N5,10,18, 35kV 372SOP N21
Use Tables W5 and X1 24
15kV 164SOP N20,23
Replacement 15kV 167RLR-W5X N5,11,13 25kV 274SOP N20,23
Elbow Use Tables W4 and X1
25kV 273RLR-W5X N5,11,13 Test Rod ALL 370TR
Use Tables W2 and X1 Bushing Well 15/25kV 276BWP
Replacement 15kV 168RLR-W5X N5,11,13, Plug 35kV M276BWP
Elbow Use Tables W4 and X1 24 Assembly Tool ALL 200AT N8
w/ Test Point 25kV 274RLR-W5X N5,11,13,
Use Tables W2 and X1 24
Direct Test 15kV 167DLR-W5X N2,5,22 N1. Copper lug for use on COPPER CONDUCTOR ONLY.
Elbow Use Tables W4 and X1 N2. W5X indicates that the part number includes 02500X long bi-metal compression lug as standard.
For an all-copper lug, replace W5X with W2X in Table X1 to specify the all-copper 02702X lug.
Connector 25kV 273DLR-W5X N2,5,22
N3. Also available as housing only. Specify: 165BLR-W; 275BLR-W;
Use Tables W2 and X1
375BLR-W; 166BLR-W; 276BLR-W; 376BLR-W.
Direct Test 15kV 167DELR-W5X N5,10,18,22 N4. Also available as elbow/insert combination. Specify: 165A4-WX;
Repair Elbow Use Tables W5 and X1 275A4-WX; 166A4-WX; 276A4-WX.
Connector 25kV 273DELR-W5X N5,10,18,22 N5. Also available with 200ECS jacket seal included. Add - S suffix to part number.
Use Tables W5 and X1 N6. Rated for single-phase applications only.
Direct Test 15kV 168DELR-W5X N5,10,18,22, N7. Equipped with insulated cuff.
Repair Elbow Use Tables W5 and X1 24 N8. Includes internal torquing feature using 200AT Assembly Tool.
Connector 25kV 274DELR-W5X N5,10,18,22, N9. Also available without probe. Specify A suffix - Example: 273DRGA.
w/Test Point Use Tables W5 and X1 24 N10. Repair elbow has extended length contact and elbow housing resulting in a net gain
Fused Elbow 15kV 168FLR H-W0X of 3-1/4" in length.
(Full Range 25kV 274FLR H-W0X N11. Replacement elbow has extended length contact and elbow housing resulting
in a net gain of 8-7/8" in length.
Current Limiting) See Product Guide
N12. Rated for 25kV thru 35kV applications.
PG-PC-H
N13. Includes long bi-metal contact 00400X.
Bolted Elbow 15kV 167LRT-W5X N17 N14. 160CA Cable Size Adapter can only be used with elbow part numbers 165LR/166LR C size only.
w/ Tap Use Tables W4 and X1
N16. Fully rotatable for 360 positioning. Includes bail assembly to secure feed-thru insert to bushing well.
N17. Includes 02800X bi-metal contact.
N18. Includes 02509X long bi-metal contact.
Bushing Insert 15kV 1601A4 N4,8,20 N19. Includes built-in jacket seal. Also available as housing only specify: 165BLRJS-W,
25kV 2701A4 N4,8,20 166BLRJS-W, 275BLRJS-W or 276LRJS-W. Also available as elbow/insert combination
35kV 3701A4 N6,21 specify: 165JSA4-W5X, 166JSA4-W5X, 275JSA4-W5X or 276JSA4-W5X.
35kV 3701A3 N8,21 N20. Includes a yellow seating indicator and vent ring.
Extended 15kV 1601EA4 N8,20 N21. Includes a black vent ring.
Bushing 25kV 2701EA4 N8,20 N22. Direct Test Connectors, along with a 200TC-X series meter adapter, a properly rated
Insert voltage meter and Hot-line Stick provides a means for direct conductor voltage testing.
Feed-Thru 15kV 1602A3R N16 N23. With stainless steel bracket.
N24. Test Point Cap Cat# 156-7
Insert 25kV 2702A1 N16
35kV 3702A1 N6,16
CONTACTS, PROBES, PLUGS,
Insulated Cap 15kV 160DR N9
CABLE ADAPTERS AND JUNCTIONS
Insulated Cap 15kV 160DRG N9 CONTINUED ON PAGE 7.
w/ Ground 15kV 167DRG N7,9
25kV 273DRG N7,9
35kV 375DRG N7,9 Refer to the W and X tables on pages 38 and 39 for sizing to cable
insulation diameter and conductor size.
For cable shield adapters and jacket seals, see page 28.
PG-CA-1109 Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com 5
CABLE ACCESSORIES
200 Amp Loadbreak
RATINGS OVERVIEW
See page 2 for complete information 25kV Class
including switching and fault close ratings. 15.2kV Phase-to-Ground
CURRENT RATINGS 26.3kV Phase-to-Phase
200A Continuous 125kV BIL
10kA sym. 10 Cycles 40kV AC Withstand
78kV DC Withstand
VOLTAGE RATINGS 19kV Corona Extinction
Separable Connectors
15kV Class
35kV Class
200A Loadbreak
8.3kV Phase-to-Ground
14.4kV Phase-to-Phase 21.1kV Phase-to-Ground
95kV BIL 36.6kV Phase-to-Phase
34kV AC Withstand 150kV BIL
53kV DC Withstand 50kV AC Withstand
11kV Corona Extinction 103kV DC Withstand
26kV Corona Extinction
2 POINT WELL
JUNCTION
6 Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com PG-CA-1109
CABLE ACCESSORIES
200 Amp Loadbreak
N1. Repair elbow has extended length contact and elbow housing
Illustration Description Voltage ELASTIMOLD Notes
(not to scale) Class Part Number resulting in a net gain of 3" in length.
Contacts: Use Table X1
N2. Copper lug for use on COPPER CONDUCTOR ONLY.
Long Bi-Metal ALL 02500X N3. Replacement elbow has extended length contact and elbow
ELR Bi-Metal 15/25kV 02509X N1 housing resulting in a net gain of 8" in length.
Copper ALL 02702X N2 N4. 160CA Cable Size Adapter can only be used with elbow part
LRT Contact 15kV 02800X numbers 165LR/166LR C size only.
RLR Contact 15/25kV 00400X N3
N5. Also available as rubber only, without straps. Specify suffix -4
Elbow Probe 15kV 166LRF in place of -5 in the part number.
25kV 274LRF
35kV 375LRF N6. Supplied with replaceable stud. Replacement stud available
separately. Specify 1000-150.
Elbow ALL 10EPW
Cable Entrance N7. Hardware packages, consisting of brackets & straps only,
Separable Connectors
Use Table W6
Insulating Plug may be ordered separately by specifying -6 in the part number.
Example 164J4-6
200A Loadbreak
Cable Size 15kV 160CA-W N4
Adapter Use Table W6 N8. Hardware package, consists of U-straps and back plate only,
EB-FA Only may be ordered separately by specifying 1601US-J2.
Direct Voltage Test N9. Hardware package, consists of U-straps and back plate only,
Meter Adapter for: may be ordered separately by specifying 1601US-J3.
HD Electric Meters 200TC-1 N14 N10. Hardware package, consists of U-straps and back plate only,
may be ordered separately by specifying 1601US-J4.
Ross Meters ALL 200TC-2 N14
N11. Hardware package, consists of U-straps and back plate only,
Chance Meters 200TC-4 N14 may be ordered separately by specifying 271-68.
2-Way Well 15/25kV K1601WJ2 N6 N12. Hardware package, consists of U-straps and back plate only,
Junction w/ may be ordered separately by specifying 271-61.
s.s. Bracket
N13. Hardware package, consists of U-straps and back plate only,
2-Way Well 15/25kV K1601WJ2-5 N5, 6, 11 may be ordered separately by specifying 271-70.
Junction w/
U Straps N14. For use with Direct Test Connectors.
3-Way Well 15/25kV K1601WJ3 N6
Junction w/
s.s. Bracket
3-Way Well 15/25kV K1601WJ3-5 N5, 6, 12
Junction w/
U Straps
4-Way Well 15/25kV K1601WJ4 N6
Junction w/
s.s. Bracket
4-Way Well 15/25kV K1601WJ4-5 N5, 6, 13
Junction w/
U Straps
2-Point Junction 15kV 164J2 N7
with/stainless 25kV 274J2 N7
steel bracket 35kV 373J2 N7
2-Point Junction 15kV 164J2-5 N5, 8
w/U-straps 25kV 274J2-5 N5, 11
35kV 373J2-5 N5, 11
3-Point Junction 15kV 164J3 N7
with/stainless 25kV 274J3 N7
steel bracket 35kV 373J3 N7
3-Point Junction 15kV 164J3-5 N5, 9
w/U-straps 25kV 274J3-5 N5, 12
35kV 373J3-5 N5, 12
4-Point Junction 15kV 164J4 N7
with/stainless 25kV 274J4 N7
steel bracket 35kV 373J4 N7
4-Point Junction 15kV 164J4-5 N5, 10
w/U-straps 25kV 274J4-5 N5, 13
35kV 373J4-5 N5, 13
PG-CA-1109 Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com 7
CABLE ACCESSORIES
200 Amp Deadbreak
RATINGS OVERVIEW
See page 2 for complete information.
200 AMP DEADBREAK SEPARABLE CONNECTOR COMPONENTS
CURRENT RATINGS
200A Continuous
10kA sym. 10 Cycles
VOLTAGE RATINGS
15kV Class
8.3kV Phase-to-Ground
14.4kV Phase-to-Phase
95kV BIL
34kV AC Withstand
53kV DC Withstand INTEGRAL BUSHING
11kV Corona Extinction
25kV Class
15.2kV Phase-to-Ground
26.3kV Phase-to-Phase
125kV BIL
40kV AC Withstand
78kV DC Withstand
19kV Corona Extinction
EXCEPT FOR LOCKING
SPLICES ALL 200 A DEADBREAK
PRODUCTS MUST BE
MECHANICALLY SECURED
WITH A BAIL WHEN CONNECTED
8 Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com PG-CA-1109
CABLE ACCESSORIES
200 Amp Deadbreak
Illustration Description Voltage ELASTIMOLD Notes Illustration Description Voltage ELASTIMOLD Notes
( not to scale) Class Part Number (not to scale) Class Part Number
Elbow Connector 15/25kV 156LR-W5X N1,2 BAIL 15/25kV 150TB4 N5
w/ Test Point Use Tables W4 and X1
Contacts:
Bail Assembly 15/25kV 150BA Long Bi-Metal 15/25kV 02500X
for 156LR Elbow Copper 15/25kV 02702X N7
Elbow 15/25kV 10EP-W N10
Bushing Insert 15/25kV K1501A1 N3 Cable Entrance Use Table W6
Separable Connectors
Insulating Plug
200A Loadbreak
Cable Entrance 15/25kV 152EA-W N11
Insulating Plug Use Table W6
Feed-thru Insert 15/25kV K1502A1 N3,4
Cable Size 15/25KV 160CA-W N14
Adapter Use Table W6
Insulated Plug 15/25kV K150DP N3 EB-FA Only
N1. Includes bail assembly.
Insulated Cap 15/25kV K150DR N3 N2. W5X indicates that the part number includes a 02500X bi-metal com-
pression lug, which is rated for either aluminum or copper conductor,
as standard. For an all-copper lug, replace W5X with W2X in Table
X1 to specify the all-copper 02702X lug.
Insulated Parking 15/25kV K151SOP N3 N3. Bails are required but not included. Order separately.
Bushing Consult factory for bails not listed for a specific application.
N4. Fully rotatable for 360 positioning. Includes bail assembly to secure
Grounding Plug 15/25kV 151GP N3 feed-thru insert to bushing well. Elbows bail assemblies are required
but not included with the feed-thru insert.
N5. Refer to factory for application details.
N6. Center-to-center spacing equals 4 inches.
Feed-Thru 15/25kV K1501FT N3,6 N7. Copper lug for copper cable only.
N8. To order cable legs for different cable sizes, list each leg size W
and X. Example: K151LY-A1240-A1240-B1220. See Tables W1
2-Point Junction 15/25kV K1501J2-U N3,6 and X1 for sizes.
N9. To order locking contacts for K151LS and K151LY, order 01401X
(Al) or 01402X (Cu) for plug contact. Order 01301X (Al) or 01302X
(Cu) for receptacle. See Table X1 for sizes.
3-Point Junction 15/25kV K1501J3-U N3,6 N10. For use with 156LR elbows.
N11. For use with K151SR, K151SP, K151LS, K151LY receptacles, plugs
and splices.
4-Point Junction 15/25kV K1501J4-U N3,6 N12. Also available as housing only. Specify K151BSP-W or K151BSR-W.
N13. Also available in EB-FA sizes per table W6 by using 160CA cable
adapter with C size plugs & receptacles.
Elbow Probe 15/25kV 156LRF N14. 160CA cable adapter can only be used with C size plugs &
receptacles.
N15. Bails are not required for locking splices.
Straight 15/25kV K151SR-W0X N3,12,13, N16. When used as a repair splice, the assembled length allows 4"
Receptacle Use Tables W1 and X1 17,18 for cablereplacement/repair.
Straight Plug 15/25kV K151SP-W0X N3,12,13, N17. Straight receptacles are also available with test point. Specify
Use Tables W1 and X1 19 K152SR-W0X part number.
N18. W0X indicates that the part number includes a 01500X universal
Tee Splice 15/25kV K150T N3 aluminum compression lug, which is rated for either aluminum or
copper, as standard. For an all-copper lug, replace W0X with W2X
in Table X1 to specify the all-copper 01502X lug.
In-Line Junction 15/25kV K150S N3 N19. W0X indicates that the part number includes a 01600X universal
aluminum compression lug, which is rated for either aluminum or
copper, as standard. For an all-copper lug, replace W0X with W2X
in Table X1 to specify the all-copper 01602X lug.
Locking Splice/ 15/25kV K151LS-W0X N8,9,13, N20. W0X indicates that the part number includes a 01400X universal
Repair Splice Use Tables W1A and X1 15,16,17, aluminum compression lug, which is rated for either aluminum or
20,23 copper, as standard. For an all-copper lug, replace W0X with W2X
in Table X1 to specify the all-copper 01402X lug.
Locking Y 15/25kV K151LY-W0X N8,9,13,
N21. W0X indicates that the part number includes a 01300X universal
Splice Use Tables W1A and X1 15,17,21
aluminum compression lug, which is rated for either aluminum or
copper, as standard. For an all-copper lug, replace W0X with W2X
BAIL 15/25kV 150TB1 N5 in Table X1 to specify the all-copper 01302X lug.
N22. Direct Test Connectors, along with a 200TC-X series meter adapter,
a properly rated voltage meter and Hot-line Stick provides a means
for direct conductor voltage testing. See page 7 for meter adapters.
BAIL 15/25kV 150TB2 N5 N23. Gains approximately 4" of repair length.
PG-CA-1109 Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com 9
CABLE ACCESSORIES
600 Series Deadbreak
ELBOW CONNECTOR
CURRENT RATINGS 200A TAPS
200A DEADBREAK
(Prefixes: 650, K650, K655, K656, THREADED
SEE PAGES 8 & 9
2 PT JUNCTION
25kA sym., 10 cycles
3 PT JUNCTION
NOTE: 900 Amp ratings require copper cable L-4
and copper current-carrying components. 4 PT JUNCTION
THREADED
STUD BUSHING
L-2
28kV Phase-to Phase
140kV BIL CABLE
CABLE TO CABLE
UTILIZING L-KITS
45kV AC Withstand
ADAPTER SEE PGS 12 & 13
L-1
INSULATED
84kV DC Withstand
PARKING BUSHING
150kV BIL
THREADED
COMPRESSION
LUG
50kV AC Withstand
THREADED
STUD
LINK-OP
Standard Production and Design Test levels CABLE TO CABLE UTILIZING VS4
10 Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com PG-CA-1109
CABLE ACCESSORIES
600 Series Deadbreak
Illustration Description Voltage ELASTIMOLD Notes
(not to scale) Class Part Number
600 Series Elbow 15/25kV K655LR-W0X N1,2,12
(w/ Insul. Plug, Cap, Stud, Use Tables W7 and X6 Illustration Description Voltage ELASTIMOLD Notes
Lug and Cable Adapter) 35kV 755LR-W0X N1,2,12 (not to scale) Class Part Number
Use Tables W9 and X6 Insulating Plug 15/25kV K650BIP N1,7,8
600 Series Direct 15/25kV K655DLR-W0X N1,2,12,14 (w/ Cap) 35kV 750BIP N1,7,8
Test Elbow Grounding Plug 15/25kV 650GP N1,7,8
(w/ Insul. Plug, Cap, Stud 35kV 755DLR-W0X N1,2,12,14 (Ground Lead 35kV 750GP N1,7,8
Lug and Cable Adapter) 2/0 AWG x 30")
600 Series Elbow 15/25kV K656LR-W0X N1,2,12 Insulated 15/25kV K650SOP N7,8
w/ Test Point Use Tables W7 and X6 Parking Bushing 35kV 750SOP N7,8
(w/ Insul. Plug, Cap, Stud, 35kV 756LR-W0X N1,2,12 Connecting Plug 15/25kV K650CP N1,7,8,9,13
Lug and Cable Adapter) Use Tables W9 and X6
15/25kV K651CP N1,7,8,10
600 Series Direct 15/25kV K656DLR-W0X N1,2,12,14
35kV 750CP N1,7,8,10
Test Elbow w/Test Point Use Tables W7 and X6
Separable Connectors
(w/ Insul. Plug, Cap, Stud, 35kV 756DLR-W0X N1,2,12,14 Deadbreak 15/25kV K650RTP N1,7,8,9
Lug and Cable Adapter) Use Tables W9 and X6 Reducing
200A Loadbreak
600 Series Elbow 15/25kV K655BLR N1,3 Tap Plug
Housing only 35kV 755BLR N1,3 Reducing Tap 15/25kV K650RTW N1,7,8,9
(w/ Stud) Well
600 Series Elbow 15/25kV K656BLR N1,3 Loadbreak 15kV 650ETP N1,7,8,10,12
w/ Test Point 35kV 756BLR N1,3 Elbow 25kV K650ETP N1,7,8,10,12
Housing only Tap Plug 35kV 750ETP N1,7,8,10,12
(w/ Stud) Vault Stretcher 15/25kV 650VSA N1
600 Series 15/25kV K655BRLR N16 Threaded Stud 35kV 750VSA N1
Replacement Elbow
600 Series Elbow 15/25kV 650SA N1
Housing only
Threaded Stud 35kV 750SA N1
w/o Test Point
600 Series 15/25kV K656BRLR N16 Assembly Tool ALL 600ATM N12
Replacement Elbow (Window-Op)
Housing only Spanner Wrench ALL 600SW N9
w/ Test Point
600 Series Straight 15/25kV K655SR-W0X N1,2,11 Direct Voltage Test
Receptacle Use Tables W7 and X6 Meter Adapter for:
(w/ Cable HD Electric Meters 200TC-1 N14
Adapter, Lug &
Retaining Ring) Ross Meters ALL 200TC-2 N14
600 Series Direct 15/25kV K655DSR-W0X N1,2,11,14 Chance Meters 200TC-4 N14
Test Straight Use Tables W7 and X6
Receptacle
Elbow
600 Series Straight 15/25kV K655BSR N1,11 N1. For 900 Amp ratings, substitute 675 for 650 and 655; 676 for 656;
Receptacle Housing K671 for K651; K675 for K650 and K655; K676 for K656; 775 for 750
(Lug & Cable and 755; 776 for 756 and 2X for 0X in the part number. The 900 Amp
Adapter not included) rating requires copper current-carrying connector components and
Straight Receptacle 15/25kV K650SRA N1,4 copper conductor cable.
Adapter N2. Add suffix symbol from page 29 to include cable shield grounding kit
600 Series 15/25kV K655BVS N1,9 and/or cable jacket sealing kit.
Vault Stretcher N3. Available without the stud by adding N to the part number.
(Housing only 35kV 755BVS N1,9 N4. Straight Receptacle Adapter is used to connect Straight Receptacles
w/ Stud) K655YBSR and K655YSR-W0X (Pg.19) to equipment bushings.
Cable Size 15/25kV 655CA-W N5. Aluminum lug for use on aluminum or copper conductors.
Adapter Use Table W7 DO NOT substitute threaded 03600X lug.
35kV 755CA-W N6. Copper lug for use on COPPER CONDUCTOR ONLY.
Use Table W9 Do not substitute threaded 03602X lug.
Compression ALL 03700X N5 N7. Available with the stud factory-assembled by adding SP to the part
Lug Use Table X6 number. 675ETP, K675ETP and 775ETP are available as -SP only.
ALL 03702X N6 The stud is not field removable.
Use Table X6 N8. Available with a loose stud by adding suffix S to the part number.
600 Series Elbow 15/25kV 655CK-W0X N2 N9. 600SW spanner wrench is recommended for installation of K650CP
& Vault Stretcher Use Tables W7 and X6 connecting plug, deadbreak reducing tap plugs and reducing tap
Size Sensitive Kit wells.
(Cable Adapter 35kV 755CK-W0X N2 N10. Use 600ATM Assembly Tool.
& Lug) Use Tables W9 and X6 N11. 600 Series Elbows and Straight Receptacles with IEEE Std. 386
Adapter ALL 650ARR-X capacitive test points are available by substituting 656 for 655; K656
Retaining Ring Use Table X6
for K655; K676 for K675; 756 for 755; 676 for 675; K676 for K675
and 776 for 775 in the part number.
600 Series Straight 15/25kV 655CK-W0X-ARR N2
N12. See page 17 for Window-Op Connector Kit.
Receptacle Size Use Tables W7 and X6
Sensitive Kit (Cable N13. Superseded by K651CP.
Adapter, Retaining N14. Direct Test Connectors, along with a 200TC-X series meter adapter,
Ring & Lug) a properly rated voltage meter and Hot-line Stick; provides a means
for direct conductor voltage testing.
Bushing 15/25kV K655BE N1,3
Extender 35kV 755BE N1,3 N15. With stainless steel bracket.
(w/ Stud) N16. Replacement Elbow includes an I-Adapter, and Straight Receptacle,
resulting in a net gain of 20".
Insulated Cap 15/25kV K656DR N3,7
w/ Test Point
(w/ Stud) Refer to the W and X tables on pages 38 and 39 for sizing to cable
Insulated Cap 15/25kV K656DRG N3,7 insulation diameter and conductor size.
w/ Test Point For cable shield adapters and jacket seals, see page 28.
(w/ Stud & Ground)
PG-CA-1109 Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com 11
CABLE ACCESSORIES
600 Series Deadbreak
versatility.
200A Loadbreak
2 PT JUNCTION
15/25kV Class (5kV thru 28kV)
16.2kV Phase-to-Ground 3 PT JUNCTION
28kV Phase-to-Phase
L-4
4 PT JUNCTION
THREADED
140kV BIL STUD BUSHING
EXTENDER
36.6kV Phase-to-Phase
L-1
INSULATED
PARKING BUSHING
STRETCHER
LINK-OP
RETAINER LINK CONNECTOR
SLEEVES LINK-OP
COMPRESSION
LUG
12 Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com PG-CA-1109
CABLE ACCESSORIES
600 Series Deadbreak
Illustration Description Voltage ELASTIMOLD Notes N1. For 900 Amp ratings, substitute 675 for 650 and 655; 676 for 656;
(not to scale) Class Part Number K675 for K650 and K655; K676 for K656; 775 for 750 and 755;
776 for 756 and 2X for 0X in the part number. The 900 Amp rating
2-Point Junction 15/25kV K650J2 N1,9,10 requires copper current-carrying connector components and copper
35kV 750J2 N1,9,10 conductor cable.
3-Point Junction 15/25kV K650J3 N1,9,10
N2. 600SW spanner wrench is recommended for installation
35kV 750J3 N1,9,10
of K650CP connecting plug, deadbreak reducing tap plugs
and reducing tap wells.
4-Point Junction 15/25kV K650J4 N1,9,10
35kV 750J4 N1,9,10 N3. L-Kits and VS-Kits do not include cable adapters or compression
lugs. These items must be ordered separately.
N4. 600 Series Elbows and Straight Receptacles with IEEE Std. 386
1-way 15/25kV K655L1 N1,2,3,4 capacitive test points are available by substituting 656 for 655;
L-Kit 35kV 755L1 N1,2,3,4 K656 for K655; K676 for K675; 756 for 755; 676 for 675; K676
Separable Connectors
for K675 and 776 for 775 in the part number.
200A Loadbreak
N5. 600ATM is recommended for installing K651CP and 750CP.
2-way 15/25kV K655L2 N1,2,3,4,5,6,7 N6. Can be used as a repair joint. (Gains 3" of repair length)
L-Kit 35kV 755L2 N1,2,3,4,5,6,7
N7. Can be used as a reducing joint for different size cables.
2-way 15/25kV K655VSL2 N1,2,3 N8. See page 17 for Window-Op Connector Kit.
VS-Kit N9. Rubber junction with stainless steel mounting plate and back plate.
35kV 755VSL2 N1,2,3 Add -U for rubber junction with stainless steel mounting plate,
3-way 15/25kV K655L3 N1,2,3,4,5 back plate and adjustable mounting bracket.
L-Kit 35kV 755L3 N1,2,3,4,5 Add -4 for rubber junction only.
Add -5 for rubber junction, stainless steel U-straps and back plate.
3-Way 15/25kV K655VSL3 N1,2,3,5,6,7 N10. Two - six-position multi-point junctions shown on pages 20 and 21.
VS Kit
35kV 755VSL3 N1,2,3,5,6,7
4-Way 15/25kV K655L4 N1,2,3,4,5
L-Kit 35kV 755L4 N1,2,3,4,5
VAULT STRETCHER
Provides an alternate method of splicing and joining
various types and styles of cables using standard
600 Series components.
PG-CA-1109 Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com 13
CABLE ACCESSORIES
600 Series Deadbreak Cam-Op, Link-Op
CURRENT RATINGS
PROVISIONS FOR MOUNTABLE
CAM-OP INSULATED BUSHING
EQUIPMENT
BUSHING
INSULATED
LINK-OP
PARKING
NOTE: 900 Amp ratings require copper cable CABLE TO EQUIPMENT
BUSHING
Continuous
BUSHING CAM-OP CAP
Voltage ratings
RETAINER
SLEEVES
OR ALIGNMENT OR OR LINK CONNECTOR
BRACKET
15kV Class
8.3kV Phase-to-Ground LINK-OP LOADBREAK
MOUNTABLE INSULATED 600 SERIES ELBOW CONNECTOR
PARKING BUSHING LINK-OP
ELBOW
14.4kV Phase-to-Phase
95kV BIL LOADBREAK
ELBOW CONNECTOR
ELBOW
ARRESTER
53kV DC Withstand
ARRESTER
CABLE
25kV Class
15.2kV Phase-to-Ground LINK
CONNECTOR
26.3kV Phase-to-Phase
OPERATING TOOL
LINK-OP
40kV AC Withstand OR
LOADBREEAK
REDUCING TAP PLUG
ELBOW
35kV Class
SLEEVES
OR
14 Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com PG-CA-1109
CABLE ACCESSORIES
600 Series Deadbreak Cam-Op, Link-Op
Illustration Description Voltage ELASTIMOLD Notes
(not to scale) Class Part Number
Illustration Description Voltage ELASTIMOLD Notes
CAM-OP 15kV 655LINK-C-LR-W0X-B-DRG N1,3,11, (not to scale) Class Part Number
CONNECTOR Use Tables W7 and X6 13,14,18 Grounding 15kV 160GLR
KIT 25kV K655LINK-C-LR-W0X-B-DRG N1,3,11, Elbow 25kV 370GLR N19
Use Tables W7 and X6 13,14,18 (1/0 AWG x 6 35kV 370GLR N19
35kV 755LINK-C-LR-W0X-B-DRG N1,3,11, Ground Lead)
Use Tables W9 and X6 13,14,18
LINK-OP 15kV 655LINK-B-LR-W0X-B-DRG N2,3,11,12 Test Rod ALL 370TR
CONNECTOR Use Tables W7 and X6 13,14,18
KIT 25kV K655LINK-B-LR-W0X-B-DRG N2,3,11,
Assembly Tool ALL 600AT N11
Use Tables W7 and X6 13,14,18
35kV 755LINK-B-LR-W0X-B-DRG N2,3,11,
Use Tables W9 and X6 13,14,18 Cam-Op 15kV 650CAM-OK N16
Separable Connectors
Operating 25kV K650CAM-OK N16
Mountable 25kV K650LBM-3 N3
Kit 35kV 750CAM-OK N16
200A Loadbreak
Insulated 35kV 750LBM-3 N3
Bushing Link-Op 15kV 650LINK-OK N17
RETROFIT 15kV 655LINK-C-LR-W0X-A-DRG N5,11,13 Operating 25kV K650LINK-OK N17
CAM-OP Use Tables W7 and X6 14,18 Kit 35kV 750LINK-OK N17
CONNECTOR 25kV K655LINK-C-LR-W0X-A-DRG N5,11,13 N1. Cam-Op connector kit includes: 1- Cam-Op link; 1- elbow housing;
KIT Use Tables W7 and X6 14,18 1- cable adapter; 1-0370 style lug; 1- bushing extender; 2- retainer
35kV 755LINK-C-LR-W0X-A-DRG N5,11,13 sleeves; 1- insulated cap; 1- mountable insulated bushing and
Use Tables W9 and X6 14,18 1- alignment bracket.
RETROFIT 15kV 655LINK-B-LR-W0X-A-DRG N6,11,12, N2. Link-Op connector kit includes: 1- Link-Op link; 1- elbow housing;
LINK-OP Use Tables W7 and X6 13,14,18 1- cable adapter; 1-0370 style lug; 1- bushing extender; 2- retainer
sleeves; 2- insulated caps; and 1- mountable insulated bushing.
CONNECTOR 25kV K655LINK-B-LR-W0X-A-DRG N6,11,12,
N3. Mountable insulated bushing included with Cam-Op and Link-Op
KIT Use Tables W7 and X6 13,14,18 connector kit. Requires 3 threaded studs on equipment faceplate
35kV 755LINK-B-LR-W0X-A-DRG N6,11,12, for installation.
Use Tables W9 and X6 13,14,18 N4. Use with the Retrofit Cam-Op and Retrofit Link-Op connector kit.
Insulating 25kV K650LB N4 N5. Retrofit Cam-Op connector kit includes: 1- link; 1- elbow housing;
Plug 35kV 750LB N4 1- cable adapter; 1-0370 style lug; 1- bushing extender; 2- retainer
sleeves; 1- insulated cap; 1- insulating plug; and 1- alignment
CAM-OP 15kV 650CAB bracket.
Alignment 25kV K650CAB N6. Retrofit Link-Op connector kit includes: 1- link; 1- elbow housing;
Bracket 35kV 750CAB 1- cable adapter; 1-0370 style lug; 1- bushing extender; 2- retainer
AB ABV LINK-OP ALL 650AB N15 sleeves; 2- insulated caps; 1- insulating plug; and 1- alignment
bracket.
Alignment ALL 650ABV N15
N7. Aluminum lug for use on aluminum or copper conductors.
Bracket (Retrofit
DO NOT substitute threaded 03600X lug.
LINK-OP Only)
N8. Copper lug for use on COPPER CONDUCTOR ONLY.
Compression ALL 03700X N7 DO NOT substitute 03602X threaded lug.
Lug Use Table X6 N8 N9. Cam-Op Cable Joint Kit includes: 1- Cam-Op link; 1- Cam-Op
ALL 03702X BI-SOP; 2- elbow housings; 2- cable adapters; 2- 0370 style lugs;
Use Table X6 2- retainer sleeves; 1- insulated cap.
N10. Link-Op Cable Joint Kit includes: 1- Link-Op link; 1- Link-Op BI-SOP;
CAM-OP & 15/25kV 655CK-W0X N13 2- elbow housings; 2- cable adapters; 2- 0370 style lugs; 2- retainer
LINK-OP Size Use Tables W7 and X6 sleeves; 2- insulated caps.
Sensitive Kit 35kV 755CK-W0X N13 N11. 600AT assembly tool required for operation and/or installation of
(Cable Adapter Use Tables W9 and X6 Link-Op. 600ATM is recommended for installing Link-Op/Cam-Op
& Lug) retaining sleeves.
N12. For 900 Amp ratings, substitute 675 for 650 and 655; 676 for 656;
CAM-OP Re- ALL 650RSC N11 K675 for K650 and K655; K676 for K656; 775 for 750 and 755;
taining Sleeve 776 for 756 and 2X for 0X in the part number. The 900 Amp rating
LINK-OP ALL 650RS N11 requires copper current-carrying connector components and copper
Retaining conductor cable.
Sleeve N13. Add suffix symbol from page 29 to include cable shield grounding kit
and/or cable jacket sealing kit.
CAM-OP 15kV 655BI-LINK-C-LR-WOX-DRG N9,11,13 N14. To add elbows or arresters instead of insulating caps, replace the
CABLE JOINT Use Tables W7 and X6 14,18 DRG with LR-WX for elbows (with test point) or ESA for elbow
KIT 25kV K655BI-LINK-C-LR-WOX-DRG N9,11,13 arresters.
Use Tables W7 and X6 14,18 N15. The 650ABV is required when the bushing horizontal spacing on the
35kV 755BI-LINK-C-LR-WOX-DRG N9,11,13 equipment or junctions is less than 5".
Use Tables W9 and X6 14,18 N16. Cam-Op operating kit includes accessories that enable visible break,
testing, isolation and grounding functions to be performed. Kit in-
LINK-OP 15kV 655BI-LINK-B-LR-WOX-DRG N10,11,12, cludes: 3- Cam-Op loadbreak reducing tap plugs; 3- grounding
CABLE JOINT Use Tables W7 and X6 13,14,18 elbows; 1- assembly tool; 1- test rod; 1- carry case; 1- lubricant;
KIT 25kV K655BI-LINK-B-LR-WOX-DRG N10,11,12, 1- instructions.
Use Tables W7 and X6 13,14,18 N17. Link-Op operating kit includes accessories that enable visible break,
35kV 755BI-LINK-B-LR-WOX-DRG N10,11,12, testing, isolation and grounding functions to be performed. Kit
Use Tables W9 and X6 13,14,18 includes: 6- Link-Op loadbreak reducing tap plugs; 3- grounding
elbows; 1- assembly tool; 1- test rod; 1- carry case; 1- lubricant;
CAM-OP 15kV 650LK-C-VB 1- instructions.
Loadbreak 25kV K650LK-C-VB N18. 600 Series Elbows and Straight Receptacles with IEEE Std. 386
Reducing 35kV 750LK-C-VB capacitive test points are available by substituting 656 for 655; K656
Tap Plugs for K655; K676 for K675; 756 for 755; 676 for 675; K676 for K675
(Visi-Break) and 776 for 775 in the part number.
CAM-OP 15kV 650LK-C N19. Rated for both 25kV and 35kV applications.
LINK 25kV K650LK-C
35kV 750LK-C
LINK-OP 15kV 650LT-B N11 Refer to the W and X tables on pages 38 and 39 for sizing
Loadbreak 25kV K650LT-B to cable insulation diameter and conductor size.
Reducing 35kV 750LT-B For cable shield adapters and jacket seals, see page 28.
Tap Plug
PG-CA-1109 Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com 15
CABLE ACCESSORIES
600 Series Deadbreak Stick-Op, Window-Op
16 Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com PG-CA-1109
CABLE ACCESSORIES
600 Series Deadbreak Stick-Op, Window-Op
Separable Connectors
N5. Add suffix symbol from page 29 to include cable shield
Connector Kit Use Tables W7 and X6 8,13
grounding kit and/or cable jacket sealing kit.
200A Loadbreak
25kV K655LRTP-W0X-DRG
Use Tables W7 and X6 N6. Aluminum lug for use on aluminum or copper conductors.
35kV 755LRTP-W0X-DRG DO NOT substitute threaded 03600X lug.
Use Tables W9 and X6 N7. Copper lug for use on COPPER CONDUCTOR ONLY.
STICK-OP 15kV 655RLRTP N3,4,5 DO NOT substitute 03602X threaded lug.
Replacement 8,13,16 N8. Threaded aluminum lug (Stick-Op only) for use on copper or
Connector Kit 25kV K655RLRTP aluminum conductors. DO NOT substitute unthreaded 03700X
lugs. DO NOT use with 675, 676, K675, K676, 775 or 776 part
numbers.
WINDOW-OP 15kV 650ETP N4,15
Loadbreak 25kV K650ETP N4,15 N9. Threaded copper lug (Stick-Op only) for use on copper
Elbow 35kV 750ETP N4,15 conductors only. DO NOT substitute unthreaded 03702X lugs.
Tap Plug N10. Required to disassemble Stick-Op loadbreak reducing tap plug
STICK-OP 15kV 650LRTPA3 N3,4 from the threaded compression lug and 600 Series elbow after
Loadbreak 25kV K650LRTPA2 the shear-pin is broken during assembly.
Reducing 35kV 750LRTPA2 N11. Stick-Op Operating Kit includes accessories that enable visible
Tap Plug break direct testing, isolation, and grounding functions to
STICK-OP 15kV 655BEA3 N3,4 be performed. Kit includes: 3-insulated parking bushings;
Bushing 25kV K655BEA2 3-grounding elbows; 3-600DB/200LB bushing/elbow adapters;
Adapter 35kV 755BEA2 1-assembly tool; 1-test rod; 1-carry case; 1-lubricant;
1-instructions.
Compression
ALL 03700X N6 N12. Window-Op Operating Kit includes accessories that enable
Lug Use Tables X6
visible grounding and direct testing functions to be performed.
WINDOW-OP ALL 03702X N7 Kit includes: 3-grounding elbows; 1-test rod; 1-carry case;
Use Tables X6
1-lubricant; 1-instructions.
N13. 600 Series Elbows and Straight Receptacles with IEEE Std. 386
Threaded ALL 03600X N8
capacitive test points are available by substituting 656 for 655;
Compression Use Tables X6
K656 for K655; K676 for K675; 756 for 755; 676 for 675; K676
Lug ALL 03602X N9
for K675 and 776 for 775 in the part number.
STICK-OP Use Tables X6
N14. Rated for both 25kV and 35kV applications.
WINDOW-OP 15/25kV 655CK-W0X N5
Size Sensitive Kit Use Tables W7 and X6 N15. 600ATM assembly tool required for Window-Op assembly.
(Cable Adapter 35kV 755CK-W0X N5 50 60 ft/lbs torque wrench required but not included.
& Lug) Use Tables W9 and X6 N16. Replacement Elbow includes: insulated cap; reducing tap plug;
STICK-OP 15/25kV 655TCK-W0X N5 600 series elbow housing; I-Adapter; straight receptacle,
Size Sensitive Kit Use Tables W7 and X6
resulting in a net gain of 20" in length vs. a standard elbow kit.
Compression lugs and cable adapters are ordered separately.
(Cable Adapter 35kV 755TCK-W0X N5
& Threaded Lug) Use Tables W9 and X6
Extraction Tool ALL 650ET N10
PG-CA-1109 Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com 17
CABLE ACCESSORIES
600 Series Deadbreak Cable Joints
RATINGS OVERVIEW
See page 2 for complete information Separable Cable Joints 600 Series Deadbreak
CURRENT RATINGS
B
(Prefixes: 650, K650, K655, K656
& 03700)
600 Amp Continuous A
SEPARABLE
H-JOINT
25kA sym., 10 cycles (4-WAY)
Voltage ratings
4-WAY INSULATED BUS BAR
15/25kV Class (5kV thru 28kV) W/ TEST POINT
16.2kV Phase-to-Ground
28kV Phase-to-Phase
140kV BIL
45kV AC Withstand A
C
84kV DC Withstand SEPARABLE
WYE-JOINT
21.5kV Corona Extinction (3-WAY)
Note: Elastimold has increased the IEEE 3-WAY INSULATED BUS BAR
W/TEST POINT
Standard Production and Design Test levels
for 25kV Class products to include 27kV
and 28kV systems.
BOLT &
RETAINING WASHERS
RING STRAIGHT RECEPTACLE HOUSING
SEPARABLE
D STRAIGHT JOINT
(2-WAY)
CABLE ADAPTER
2-WAY INSULATED BUS BAR
COMPRESSION LUG W/TEST POINT
OPERATING ACCESSORIES
18 Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com PG-CA-1109
CABLE ACCESSORIES
600 Series Deadbreak Cable Joints
Illustration Description Voltage ELASTIMOLD Notes Illustration Description Voltage ELASTIMOLD Notes
(not to scale) Class Part Number (not to scale) Class Part Number
Separable 15/25kV K656I-W0X N1,8 Insulating Plug w/ 15/25kV K650YBIP
Straight Joint Pkg. Use Tables W7 and X6 Test Point & Cap
(2-way)
w/ Test Point
Grounding Plug 15/25kV 650YGP
Basic Housing Pkg. 15/25kV K656I-HP N2 (4/0 AWG x 6
Straight Joint Ground Lead)
w/ Test Point
Separable 15/25kV K656CY-W0X N1,8
Wye Joint Pkg. Use Tables W7 and X6 Grounding Cap 15/25kV 650GYDR
(3-Way) (4/0 AWG x 6
Separable Connectors
w/ Test Point Ground Lead)
200A Loadbreak
Basic Housing Pkg. 15/25kV K656CY-HP N2
Wye Joint Stainless Steel 15/25kV 650BAW
w/ Test point Bolt & Washers
Separable 15/25kV K656CH-W0X N1,8 Assembly/ ALL 600YADT-1 N6
H Joint Pkg. Use Tables W7 and X6 Disassembly
(4-Way) Tool
w/ Test Point
Basic Housing Pkg. 15/25kV K656CH-HP N2 Assembly/ ALL 600RRT N6
H Joint Disassembly
w/ Test Point Tool
PG-CA-1109 Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com 19
CABLE ACCESSORIES
Molded Multi-Point Junctions
RATINGS OVERVIEW
See page 2 for complete information
CURRENT RATINGS
600 Amp Continuous
25kA sym., 10 cycles
Figure 2: MultiPoint Junctions with 6 " Interface Spacings.
or with 200 Amp Bushing Well versions
200 Amp Continuous
10kA sym., 10 cycles
Voltage ratings
15kV Class
8.3kV Phase-to-Ground
95kV BIL
34kV AC Withstand
53kV DC Withstand
11kV Corona Extinction
25kV Class
16.2kV Phase-to-Ground
140kV BIL
45kV AC Withstand
84kV DC Withstand
21.5kV Corona Extinction Type of Figure 1 Figure 2
number of number of
35kV Class Junction A B C
mounting holes A B C mounting holes
21.1kV Phase-to-Ground J2 15 7 6 6 19 10 8 6
150kV BIL
J3 19 11 8 6 26 10 11 6
50kV AC Withstand
103kV DC Withstand J4 24 15 10 6 32 23 9 8
26kV Corona Extinction J5 27 19 12 6 39 10 12 8
Optional
J6 31 23 9 8 45 36 8 10 Tilt Mounting Adapter
20 Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com PG-CA-1109
CABLE ACCESSORIES
Molded Multi-Point Junctions
Separable Connectors
35kV J2 - __ __ - 35 J2 - __ __ - 35-SV
200A Loadbreak
(J2-26-15 shown)
ORDERING INFORMATION
To specify and order Elastimold Multi-Point Junctions:
1. Use Table 1 to construct a catalog number describing the required junction.
PG-CA-1109 Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com 21
CABLE ACCESSORIES
PCJ Cable Joints
will be installed.
200A Loadbreak
22 Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com PG-CA-1109
CABLE ACCESSORIES
PCJ Cable Joints
Separable Connectors
200A Loadbreak
Voltage
Class
Power
Cable
Joint
Style
Insulation
Conductor
Conductor
Size Code
Diameter
PCJ Style 2
with universal housing and separate cable adapters 1- Aluminum
that can be varied with the cable application. 1- Style 1 2- Copper
2- Style 2
DIMENSIONAL DATA
A B Description Voltage ELASTIMOLD Notes
STYLE 1
PART NUMBER inches inches Class Part Number
15PCJ1FX 10 1/4" 1 3/4" Power Cable 15kV 15PCJ1W1X N1
15PCJ1GX 10 1/4" 1 3/4" Joint 15kV 15PCJ1W2X N2
25kV 25PCJ1W1X N1
25PCJ1GX 14 3/8" 2 7/16" Style 1 25kV 25PCJ1W2X N2
15/25/35PCJ1HX 14 3/8" 2 7/16" 35kV 35PCJ1W1X N1
15/25/35PCJ1JX 14 3/8" 2 7/16" 35kV 35PCJ1W2X N2
15/25/35PCJ1KX 14 3/8" 2 25/32" Power Cable 15kV 15PCJ2W1X N1
Joint 15kV 15PCJ2W2X N2
15/25/35PCJ1LX 14 3/8" 2 25/32"
25kV 25PCJ2W1X N1
15/25PCJ1LMX 14 3/8" 2 25/32" Style 2 25kV 25PCJ2W2X N2
15/25/35PCJ1MX 14 3/8" 2 25/32" 35kV 35PCJ2W1X N1
15/25/35PCJ1NX 15 3/4" 3 3/16" 35kV 35PCJ2W2X N2
15/25/35PCJ1PX 15 3/4" 3 3/16"
15/25/35PCJ1QX 15 3/4" 3 3/16"
PG-CA-1109 Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com 23
CABLE ACCESSORIES
Cable Terminations
ELECTRICAL RATINGS
Terminations
SUMMARY
The following ratings summary is based
on IEEE Std. 48 and applies to all the SINGLE PIECE TERMINATORS STRESS CONE MODULAR TERMINATORS
terminations on page 24 thru 27. Elastimold
terminations are designed for use on three-
phase systems, either 3-wire or 4-wire and
the single-phase laterals of these systems.
VOLTAGE RATINGS
15kV Class
9.5kV Phase-to-Ground
110kV BIL 1.2 x 50 microsecond wave
AC Withstand:
50kV 1 min. dry
35kV 6 hr. dry
45kV 10 sec. wet
PCT-1 PCT-2 16THG 16THGS 35MSC 35MSCI 35MTGI 35MTG
13kV Corona Extinction
25kV Class
BRACKETS
16kV Phase-to-Ground
150kV BIL 1.2 x 50 microsecond wave
AC Withstand:
65kV 1 min. dry
55kV 6 hr. dry
60kV 10 sec. wet
21.5kV Corona Extinction
35kV Class
22kV Phase-to-Ground
200kV BIL 1.2 x 50 microsecond wave
AC Withstand:
90kV 1 min. dry
75kV 6 hr. dry
80kV 10 sec. wet
30kV Corona Extinction
24 Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com PG-CA-1109
CABLE ACCESSORIES
Cable Terminations
Separable Connectors
Single-Piece 15/25kV 16THG-WX-4 N2,14
for two-hole spade lug. Specify suffix -5 in place of -4 for one-
Terminator Use Tables W12 and X8 15
200A Loadbreak
hole spade lug.
(Class 1)
N13. Specify suffix -3 or -5 in place of -4 for two-hole spade lug
Housing 15/25kV 16THGH-W housing or one- hole spade style housing.
only Use Table W12 N14. Use 1X for an aluminum rod contact for aluminum conductors only.
N15. Substitute 0X for 1X for a universal aluminum rod contact for
Single-Piece 15/25kV 16THGS-WX N3 aluminum or copper conductors.
Terminator Use Tables W12 and X4 N16. Available in sizes from GA thru PB & are supplied qty.
for solid 2 per package.
conductor only N17. Available in sizes EB thru PB.
(Class 1) N18. For conductors from 1/0 thru 350 kcmil.
Stress Cone ALL 35MSC-W N17 N19. For conductors from 400 kcmil thru 1000 kcmil.
(Class 3) Use Table W11 N20. For conductors from #2 to 1000 kcmil.
N21. For conductors from #6 thru 4/0.
Stress Cone ALL 35MSCI-W N17
w/Grd. Strap Use Table W11 N22. Use for insulation dia. range from .640" thru 1.070".
N23. Use for insulation dia. range from .830" thru 1.180".
Modules ALL 35MG-W N11,16
N24. Select symbol for A from aerial lug ordering information
only Use Table W13
on page 26.
Modular 15kV 35MTG-WX-4-CA N2,11 N25. W13 Table provides sizing for rain cap.
Terminator Use Tables W13 and X3 X10 Table provides sizing for connectors.
(Class 1) 25kV 35MTG-WX-8-CA N2,5,11
Use Tables W13 and X3
35kV 35MTG-WX-10-CA N2,6,11
Use Tables W13 and X3
PG-CA-1109 Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com 25
CABLE ACCESSORIES
Cable Terminations
35MTG - W X - N - C A
I =Indoor
Blank = Outdoor
NOTE: Applicable table and available sizes depend Sizes Type Connector Symbol
upon connector style. Reference Connector
200A Loadbreak
NOTES:
A. Available for 1/0 through 350 conductor sizes only. Use Table X3 for size selection.
B. Available for 400 through 1000 conductor sizes only. Use Table X3A for size selection.
C. Available for #2 through 1000 conductor sizes only. Use Table X3 for size selection.
D. Available for #6 through 4/0 conductor sizes only. Use Table X3 for size selection.
26 Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com PG-CA-1109
CABLE ACCESSORIES
Cable Terminations
Separable Connectors
16THG
N13. Fits overall cable O.D. from .750" to 2.000".
200A Loadbreak
Bracket ALL 16TB-4 N6
for riser pole
mounting
16THG
Bracket ALL 16TB-5 N6
for tri-mounting
16THG
KELLUMS ALL 35MTB1-A N1,2,6,7
GRIP ALL 35MTB1-B N1,3,6,7
Bracket ALL 35MTB1-C N1,4,6,7
ALL 35MTB1-D N1,5,6,7
KELLUMS ALL 35MTB3-A N1,2,6,7
Bracket ALL 35MTB3-B N1,3,6,7
for crossarm ALL 35MTB3-C N1,4,6,7
mounting ALL 35MTB3-D N1,5,6,7
Bracket ALL 35MTB4-A N1,2,6,7
(for riser pole ALL 35MTB4-B N1,3,6,7
mounting) ALL 35MTB4-C N1,4,6,7
ALL 35MTB4-D N1,5,6,7
KELLUMS ALL 35MTB5-A N1,2,6,7
Bracket ALL 35MTB5-B N1,3,6,7
for tri-mounting ALL 35MTB5-C N1,4,6,7
ALL 35MTB5-D N1,5,6,7
ALUMAFORM ALL 1535AFB-1 N1,6,7,13
Bracket
PG-CA-1109 Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com 27
CABLE ACCESSORIES
Shield Adapters, Sealing & Grounding
NONE
REQUIRED
EXTRUDED SHIELD EXTRUDED SHIELD EXTRUDED SHIELD EXTRUDED SHIELD EXTRUDED SHIELD EXTRUDED
CONDUCTIVE
JACKET
CONCENTRIC CONCENTRIC
NEUTRAL WIRES NEUTRAL WIRES COPPER SHIELD
DRAIN WIRES
DRAIN WIRES
OUTER JACKET OUTER JACKET OUTER JACKET OUTER JACKET
28 Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com PG-CA-1109
CABLE ACCESSORIES
Shield Adapters, Sealing & Grounding
N1. To order the kits as separate items, use the part numbers shown in
Illustration Description ELASTIMOLD Suffix Notes
(not to scale) Part Number the table. Example: To order a cold shrinkable tube as a separate
item, use the part number 200ECS.
Cold Shrinkable 200ECS -S N1,3
To order the kits as components of other items, add the suffix to the
Jacket Seal
end of the part number. Example: To order a cold shrinkable jacket
seal as a component of an elbow kit, use the part number 166LR-
Cold Shrinkable 600ECS -S N1,4 A5200-S.
Jacket Seal
N2. Only use this suffix with part numbers that designate a W housing
size. Sizing the main component will also size the suffix adapter.
Metallic Tape 20MA-W -0MA N1,2,5,6
N3. Size range .80" to 1.50" jacket diameters. Maximum installed
Shield Adapter Use Table W14
diameter is approx. 2".
for sizing
N4. Size range 1.28" to 2.30" jacket diameters. Maximum installed
Wire Shield 21MA-W -1MA N1,2,5,6
diameter is approx. 2.75".
Separable Connectors
Adapter Use Table W14
for sizing N5. Voltage rating equal to Elastimold product being used.
200A Loadbreak
Shield 10TL-W -TL N1,2 N6. Copper rod size is no. 6 for sizes FA thru HA and no. 2 for sizes
Adapter Use Table W15 HAB thru JB.
for sizing N7. Braid is equivalent to no. 6 copper rod for sizes FA thru HA
Cold Shrinkable Seal 200ECSG1-2 -SG1 N1,3,5,6 and no. 2 copper rod for sizes HAB thru JB.
w/ Copper Rod &
Crimp Connector
Cold Shrinkable Seal 600ECSG1-2 -SG1 N1,4,5,6
w/ Copper Rod &
Crimp Connector
Cold Shrinkable Seal 200ECSG2-2 -SG2 N1,3,5,6
w/ Copper Rod &
Constant Force
Spring
Cold Shrinkable Seal 600ECSG2-2 -SG2 N1,4,5,6
w/ Copper Rod &
Constant Force
Spring
Cold Shrinkable Seal 200ECSG3 -SG3 N1,3,5,7
w/ Copper Braid &
Constant Force
Spring
Cold Shrinkable Seal 600ECSG3 -SG3 N1,4,5,7
w/ Copper Braid &
Constant Force
Spring
Insulation Insulation
Table W14
Inches Symbol Table W15
Inches Symbol
MIN. MAX. for W MIN. MAX.
USEFOR
for W
USEFOR
20MA .530 .680 E 10TL .495 .585 EB
21MA .640 .820 F .525 .635 EF
.760 .950 G .575 .585 FA
.850 1.050 H .625 .735 FAB
.980 1.180 J .675 .785 FB
1.090 1.310 K .725 .835 FG
1.180 1.465 L .775 .885 GA
1.370 1.630 M .825 .935 GAB
1.515 1.780 N .875 .985 GB
.930 1.040 GH
.980 1.115 HA
1.040 1.175 HAB
1.095 1.240 HB
1.160 1.305 HJ
1.220 1.375 JA
1.285 1.395 JAB
1.355 1.520 JB
1.485 1.595 KA
1.530 1.640 KAB
1.575 1.685 KB
1.755 1.875 PB
PG-CA-1109 Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com 29
CABLE ACCESSORIES
Equipment Bushings
The Thomas & Betts Elastimold brand manufactures K1601PCC series bushings are provided with a
a complete line of 200 Amp deepwell and 600 Series molded epoxy flange for gasketed clamp mounting
apparatus bushings for use on transformers, only. Bushings are available for use on AIR, OIL
switchgear and other equipment applications. or SF6 insulated equipment. Units are rated for
The bushings incorporate IEEE 386 standard submersible, padmount, indoor, outdoor and other
interfaces (shown on page 3) and are constructed applications. Options include hold-down bail tabs and
of molded epoxy with stainless steel flanges for replaceable studs for 200 Amp deepwell bushings.
mounting by welding or gasketed clamp.
N1. Replacement stud available separately. Specify 1601RS. N11. Includes 650PPC shipping cap.
N2. Equipped with standard aluminum conductor rod. N12. Includes 750PPC1 shipping cap.
N3. Equipped with copper conductor rod. N13. Parking stands for 200A deadbreak applications are available as
N4. Includes 5/8-11 threaded stud at elbow end. separate items. Specify 151PS.
N5. Includes 5/8-11 threaded hole at elbow end. N14. Parking stands for 200A loadbreak and 600A deadbreak applications
N6. Provides increased creep and strike. are available as separate items. Specify 160PS.
N7. Includes 1601PPC1 shipping cap. N15. Aluminum stud available separately. Specify 650SA.
N8. Includes 1601APC1 shipping cap. N16. Aluminum stud available separately. Specify 750SA.
N9. Includes 2701-41 shipping cap.
N10. Includes 180PPC shipping cap.
30 Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com PG-CA-1109
CABLE ACCESSORIES
Reference
Separable Connectors
200A Loadbreak
REFERENCE SECTION
Index................................................................................ 40-41
PG-CA-1109 Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com 31
CABLE ACCESSORIES
How to Specify Size-Sensitive Products
W W
Separable Connectors
INSULATION
CABLE
200A Loadbreak
DIAMETER
INSULATION
DIAMETER
Ordering Examples
AEIC ICEA
To complete the information required to order a K655LR-W0X elbow To complete the information required to order a K655LR-W0X elbow
for use on standard AEIC 1000 kcmil compressed stranding for use on standard ICEA 1000 kcmil compressed stranding
aluminum 25kV cable with .260 inch thick insulation wall: aluminum 25kV cable with .260 inch thick insulation wall:
A. Determine that the insulation diameter (for AEIC cable in the A. Determine that the insulation diameter (for ICEA cable in the
table on pages 34-36) is 1.645 1.770 inches. table on pages 34-36) is 1.645 1.740 inches.
B. For this elbow, the part number selection chart on page 11 B. For this elbow, the part number selection chart on page 11
indicates to use table W7 for elbow sizing and table X6 for indicates to use table W7 for elbow sizing and table X6 for
connector sizing. connector sizing.
C. From table W7 the symbol for W is N. C. From table W7 the symbol for W is N.
D. From table X6 the symbol for X is 410. D. From table X6 the symbol for X is 410.
E. The completed part number therefore is K655LR-N0410. E. The completed part number therefore is K655LR-N0410.
32 Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com PG-CA-1109
CABLE ACCESSORIES
How to Specify Size-Sensitive Products
Separable Connectors
200A Loadbreak
Cable Shield Adaptors
Cable Grounding Kits
Cable Jacket Seal
PG-CA-1109 Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com 33
CABLE ACCESSORIES
AEIC & ICEA Cable Insulation Diameter
AEIC CS8-06
Specification for Extruded Dielectric,
15kV 100% 175 mil Insulation (.175") Shielded Power Cable Rated 5 - 46kV
15kV 133% 220 mil Insulation (.220") AEIC-Calulated Diameters - Solid and Compressed Stranding from
25kV 100% 260 mil Insulation (.260") Tables C-4 & C-6 and Compact Stranding from Tables C-5 & C-7
35kV 100% 345 mil Insulation (.345")
ANSI/ICEA S-94-649-2004 & S-97-682-2000
Separable Connectors
ICEA NOTE: Diameters specified in the above table are different than specified by AEIC CS8-00. Consult Accessory
Manufacturer for proper selection of accessories. Diameters to be measured in accordance with 9.6.
34 Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com PG-CA-1109
CABLE ACCESSORIES
AEIC & ICEA Cable Insulation Diameter
Separable Connectors
1/0
ICEA 0.770 0.855 0.815 0.905 0.805 0.895 0.780 0.865
200A Loadbreak
AEIC 0.850 0.940 0.820 0.905
2/0
ICEA 0.865 0.950 0.850 0.935 0.820 0.905
AEIC 0.900 0.990 0.865 0.955
3/0
ICEA 0.915 1.000 0.900 0.985 0.865 0.955
AEIC 0.955 1.045 0.920 1.005
4/0
ICEA 0.970 1.060 0.955 1.045 0.920 1.005
AEIC
250
ICEA 1.025 1.115 1.010 1.100 0.970 1.060
AEIC 1.115 1.205 1.070 1.155
350
ICEA 1.135 1.220 1.115 1.200 1.070 1.155
AEIC 1.240 1.335 1.190 1.275
500
ICEA 1.265 1.355 1.240 1.330 1.190 1.275
AEIC 1.430 1.530 1.370 1.460
750
ICEA 1.460 1.550 1.430 1.520 1.370 1.460
AEIC 1.575 1.680 1.520 1.610
1000
ICEA 1.610 1.705 1.575 1.670 1.520 1.610
ICEA NOTE: Diameters specified in the above tables are different than specified by AEIC CS8-00. Consult Accessory
Manufacturer for proper selection of accessories. Diameters to be measured in accordance with 9.6.
PG-CA-1109 Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com 35
CABLE ACCESSORIES
AEIC & ICEA Cable Insulation Diameter
ICEA NOTE: Diameters specified in the above table are different than specified by AEIC CS8-00. Consult Accessory Manufacturer
for proper selection of accessories. Diameters to be measured in accordance with 9.6.
36 Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com PG-CA-1109
CABLE ACCESSORIES
Cable Conductor Diameter
Separable Connectors
200A Loadbreak
CABLE
CONDUCTOR
PG-CA-1109 Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com 37
CABLE ACCESSORIES
WX Size Tables
.850 1.050 H
Table W11
Cable Insulation
.980 1.180 J Diameter in Inches Symbol
1.090 1.310 K
Table W7
Cable Insulation
Diameter in Inches Symbol
USEFOR FOLLOWING
MIN. MAX.
PRODUCTS
for W
USEFOR FOLLOWING
MIN. MAX. for W
PRODUCTS 35MSC .495 .585 EB
K656I/CY/CH .640 .820 F 35MSCI .525 .635 EF
K655/656LR
.575 .685 FA
Table W3
Cable Insulation K655/656SR .760 .950 G
Diameter in Inches Symbol
USEFOR FOLLOWING for W 655/656LINK .850 1.050 H .625 .735 FAB
MIN. MAX.
PRODUCTS K655/656LINK .675 .785 FB
375RLR .850 1.050 H 655/656ETP .980 1.180 J
.725 .835 FG
376RLR .980 1.180 J K655/656ETP 1.090 1.310 K
655/656RTP .775 .885 GA
1.090 1.310 K K655/656LRTP 1.180 1.465 L .825 .935 GAB
1.235 1.465 L 655/656BI-LINK 1.280 1.430 LM .875 .985 GB
K655/656BI-LINK
655CA/CK/TCK 1.370 1.630 M .930 1.040 GH
1.515 1.780 N .980 1.115 HA
Table W4
Cable Insulation
Diameter in Inches Symbol 1.040 1.175 HAB
1.725 1.935 P
USEFOR FOLLOWING
MIN. MAX.
PRODUCTS
for W 1.095 1.240 HB
156LR .640 .820 F 1.160 1.305 HJ
167/168RLR .760 .950 G 1.220 1.375 JA
Table W8
Cable Insulation
167LRT .850 1.050 H Diameter in Inches Symbol 1.285 1.395 JAB
USEFOR FOLLOWING
MIN. MAX. for W 1.355 1.520 JB
.980 1.180 J PRODUCTS
38 Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com PG-CA-1109
CABLE ACCESSORIES
WX Size Tables
Separable Connectors
02500
02509 4/0 270 260
200A Loadbreak
02702 Riser Conductor Size. Symbol 250 280 270
02800 Table X4 AWG Solid for X 300 290 280
USEFOR FOLLOWING
K151SP/SR PRODUCTS #2 2 350 300 290
K151LS/LY 16THGS #1 2 400 310 300
16CAS 1/0 10 450 320 310
Conductor Symbol for X 2/0 20 500 330 310
Table X2 Size AWG Strand./ Compt./ 3/0 30 550 340 320
USEFOR FOLLOWING or kcmil Compr. Solid. 4/0 30 600 350 330
PRODUCTS
375/376LR 1/0 240 230 650 360 340
2/0 250 240 Conductor Symbol for X 700 380 350
3/0 260 250 Table X6 Size AWG Strand./ Compt./ 750 380 360
4/0 270 260 USEFOR FOLLOWING or kcmil Compr. Solid. 800 390 380
PRODUCTS
655/656LRTP #2 220 210 900 400 380
Conductor Symbol for X K655/656LRTP #1 230 220 1000 410 400
Table X3 Size AWG Strand./ Compt./ 755/756LRTP 1/0 240 230 1250 440 420
USEFOR FOLLOWING or kcmil Compr. Solid. K656I/Y/H 2/0 250 240
PRODUCTS
35MTG #6 5 K655/656LR 3/0 260 250
Conductor Symbol for X
755/756LR
#5 4 5 4/0 270 260
Table X8 Size AWG Strand./ Compt./
K655/656SR
NOTE:
SEE PAGE 24 #4 3 4 250 280 270 USEFOR FOLLOWING or kcmil Compr. Solid.
FOR DETAILED
APPLICATION #3 2 3 655/656LINK PRODUCTS
300 290 280 16THG #6 180
K655/656LINK
INFORMATION #2 1 2 350 300 290
755/756LINK 16TCA #5 190 180
#1 0 1 655/656ETP 400 310 300 #4 200 190
1/0 10 0 K655/656ETP 450 320 310 #3 210 200
2/0 20 10 755/756ETP 500 330 320 #2 220 210
3/0 30 20 655/656BI-LINK 550 340 320 #1 230 220
4/0 40 30 K655/656BI-LINK 600 350 330 1/0 240 230
250 250 40 755BI-LINK 650 360 340 2/0 250 240
300 300 250 655CK 700 380 350 3/0 260 250
350 350 300 755CK
750 380 360 4/0 270 260
655TCK
400 400 350 800 390 360
03600
450 450 03602 900 400 380
500 500 400 03700 1000 410 400 Conductor Symbol for X
550 550 450 03702 1250 440 420
Table X9 Size AWG Strand./ Compt./
USEFOR FOLLOWING or kcmil Compr. Solid.
600 600 500 PRODUCTS
PCT1 #2 220 210
650 650 550
PCT2 #1 230 220
700 750 600
01000 1/0 240 230
750 750 650
01010 2/0 250 240
800 800 750
3/0 260 250
900 900 800
4/0 270 260
1000 1000 900
PG-CA-1109 Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com 39
CABLE ACCESSORIES
Index
40 Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com PG-CA-1109
CABLE ACCESSORIES
Index
Separable Connectors
600SW. . . . . . . . . . . . . . . . . . . . . . 11,13 750STICK-OK. . . . . . . . . . . . . . . . . . 17 K1601PC-T2. . . . . . . . . . . . . . . . . . . 30 K655RETP . . . . . . . . . . . . . . . . . . . . 17
200A Loadbreak
600YADT-1. . . . . . . . . . . . . . . . . . . . 19 750T1 . . . . . . . . . . . . . . . . . . . . . . . . 30 K1601PC-T2-R. . . . . . . . . . . . . . . . . 30 K655RLRTP . . . . . . . . . . . . . . . . . . . 17
650AB. . . . . . . . . . . . . . . . . . . . . . . . 15 750VSA. . . . . . . . . . . . . . . . . . . . . . . 11 K1601WFT . . . . . . . . . . . . . . . . . . . . . 5 K655SR-W0X . . . . . . . . . . . . . . . . . . 11
650ABV. . . . . . . . . . . . . . . . . . . . . . . 15 750WINDOW-OK . . . . . . . . . . . . . . . 17 K1601WFTV. . . . . . . . . . . . . . . . . . . . 5 K655VSL2. . . . . . . . . . . . . . . . . . . . . 13
650ARR-X. . . . . . . . . . . . . . . . . . . 11,19 755BE. . . . . . . . . . . . . . . . . . . . . . . . 11 K1601WJ2. . . . . . . . . . . . . . . . . . . . . . 7 K655VSL3. . . . . . . . . . . . . . . . . . . . . 13
650BA. . . . . . . . . . . . . . . . . . . . . . . . 19 755BEA2. . . . . . . . . . . . . . . . . . . . . . 17 K1601WJ2-5. . . . . . . . . . . . . . . . . . . . 7 K655VSL4. . . . . . . . . . . . . . . . . . . . . 13
650BAW . . . . . . . . . . . . . . . . . . . . . . 19 755BI-LINK-B-LR-W0X-DRG . . . . . . 15 K1601WJ3. . . . . . . . . . . . . . . . . . . . . . 7 K655YBSR . . . . . . . . . . . . . . . . . . . . 19
650CAB. . . . . . . . . . . . . . . . . . . . . . . 15 755BI-LINK-C-LR-W0X-DRG . . . . . . 15 K1601WJ3-5. . . . . . . . . . . . . . . . . . . . 7 K655YDR . . . . . . . . . . . . . . . . . . . . . 19
650CAM-OK . . . . . . . . . . . . . . . . . . . 15 755BLR. . . . . . . . . . . . . . . . . . . . . . . 11 K1601WJ4. . . . . . . . . . . . . . . . . . . . . . 7 K655YDSR-W0X. . . . . . . . . . . . . . . . 19
650ET. . . . . . . . . . . . . . . . . . . . . . . . 17 755BVS. . . . . . . . . . . . . . . . . . . . . . . 11 K1601WJ4-5. . . . . . . . . . . . . . . . . . . . 7 K655YSR-W0X. . . . . . . . . . . . . . . . . 19
650ETP. . . . . . . . . . . . . . . . . . . . . 11,17 755CA-W. . . . . . . . . . . . . . . . . . . . . . 11 K180C4. . . . . . . . . . . . . . . . . . . . . . . 30 K656BLR. . . . . . . . . . . . . . . . . . . . . . 11
650GP. . . . . . . . . . . . . . . . . . . . . . . . 11 755CK-W0X . . . . . . . . . . . . . . 11,15,17 K180S4. . . . . . . . . . . . . . . . . . . . . . . 30 K656BRLR . . . . . . . . . . . . . . . . . . . . 11
650GYDR . . . . . . . . . . . . . . . . . . . . . 19 755CK-W0X-ARR. . . . . . . . . . . . . . . 11 K180T4. . . . . . . . . . . . . . . . . . . . . . . 30 K656CH-BUS . . . . . . . . . . . . . . . . . . 19
650LINK-OK . . . . . . . . . . . . . . . . . . . 15 755DLR-W0X . . . . . . . . . . . . . . . . . . 11 K650BIP . . . . . . . . . . . . . . . . . . . . . . 11 K656CH-HP. . . . . . . . . . . . . . . . . . . . 19
650LK-C . . . . . . . . . . . . . . . . . . . . . . 15 755ETP-W0X-DRG. . . . . . . . . . . . . . 17 K650CAB. . . . . . . . . . . . . . . . . . . . . . 15 K656CH-W0X. . . . . . . . . . . . . . . . . . 19
650LK-C-VB . . . . . . . . . . . . . . . . . . . 15 755L1 . . . . . . . . . . . . . . . . . . . . . . . . 13 K650CAM-OK. . . . . . . . . . . . . . . . . . 15 K656DLR-W0X. . . . . . . . . . . . . . . . . 11
650LRTPA3. . . . . . . . . . . . . . . . . . . . 17 755L2 . . . . . . . . . . . . . . . . . . . . . . . . 13 K650CP. . . . . . . . . . . . . . . . . . . . . . . 11 K656CY-BUS . . . . . . . . . . . . . . . . . . 19
650LT-B. . . . . . . . . . . . . . . . . . . . . . . 15 755L3 . . . . . . . . . . . . . . . . . . . . . . . . 13 K650ETP. . . . . . . . . . . . . . . . . . . . 11,17 K656CY-HP. . . . . . . . . . . . . . . . . . . . 19
650RS. . . . . . . . . . . . . . . . . . . . . . . . 15 755L4 . . . . . . . . . . . . . . . . . . . . . . . . 13 K650J2 . . . . . . . . . . . . . . . . . . . . . . . 13 K656CY-W0X . . . . . . . . . . . . . . . . . . 19
650RSC. . . . . . . . . . . . . . . . . . . . . . . 15 755LINK-B-LR-W0X-A-DRG. . . . . . . 15 K650J3 . . . . . . . . . . . . . . . . . . . . . . . 13 K656DLR-W0X. . . . . . . . . . . . . . . . . 11
650SA. . . . . . . . . . . . . . . . . . . . . . . . 11 755LINK-B-LR-W0X-B-DRG. . . . . . . 15 K650J4 . . . . . . . . . . . . . . . . . . . . . . . 13 K656DR. . . . . . . . . . . . . . . . . . . . . . . 11
650STICK-OK. . . . . . . . . . . . . . . . . . 17 755LINK-C-LR-W0X-A-DRG. . . . . . . 15 K650LB. . . . . . . . . . . . . . . . . . . . . . . 15 K656DRG . . . . . . . . . . . . . . . . . . . . . 11
650VSA. . . . . . . . . . . . . . . . . . . . . . . 11 755LINK-C-LR-W0X-B-DRG. . . . . . . 15 K650LBM-3. . . . . . . . . . . . . . . . . . . . 15 K656I-BUS . . . . . . . . . . . . . . . . . . . . 19
650WINDOW-OK . . . . . . . . . . . . . . . 17 755LRTP-W0X-DRG. . . . . . . . . . . . . 17 K650LINK-OK. . . . . . . . . . . . . . . . . . 15 K656I-HP. . . . . . . . . . . . . . . . . . . . . . 19
650YGP. . . . . . . . . . . . . . . . . . . . . . . 19 755LR-W0X. . . . . . . . . . . . . . . . . . . . 11 K650LK-C. . . . . . . . . . . . . . . . . . . . . 15 K656I-W0X . . . . . . . . . . . . . . . . . . . . 19
655BEA3. . . . . . . . . . . . . . . . . . . . . . 17 755TCK-W0X . . . . . . . . . . . . . . . . . . 17 K650LK-C-VB. . . . . . . . . . . . . . . . . . 15 K656LR-W0X . . . . . . . . . . . . . . . . . . 11
655BI-LINK-B-LR-W0X-DRG . . . . . . 15 755VSL2. . . . . . . . . . . . . . . . . . . . . . 13 K650LRTPA2 . . . . . . . . . . . . . . . . . . 17 K656YDSR-W0X. . . . . . . . . . . . . . . . 19
655BI-LINK-C-LR-W0X-DRG . . . . . . 15 755VSL3. . . . . . . . . . . . . . . . . . . . . . 13 K650LT-B . . . . . . . . . . . . . . . . . . . . . 15 K675S1. . . . . . . . . . . . . . . . . . . . . . . 30
655CA-W. . . . . . . . . . . . . . . . . . . . 11,19 755VSL4. . . . . . . . . . . . . . . . . . . . . . 13 K650RTP. . . . . . . . . . . . . . . . . . . . . . 11 K675T1. . . . . . . . . . . . . . . . . . . . . . . 30
655CK-W0X . . . . . . . . . . . . . . 11,15,17 756BLR. . . . . . . . . . . . . . . . . . . . . . . 11 K650RTW. . . . . . . . . . . . . . . . . . . . . 11 K675TBC. . . . . . . . . . . . . . . . . . . . . . 30
655CK-W0X-ARR. . . . . . . . . . . . 11, 19 756DLR-W0X . . . . . . . . . . . . . . . . . . 11 K650S1. . . . . . . . . . . . . . . . . . . . . . . 30 L1601PC-S1. . . . . . . . . . . . . . . . . . . 30
655ETP-W0X-DRG. . . . . . . . . . . . . . 17 756LR-W0X. . . . . . . . . . . . . . . . . . . . 11 K650SOP . . . . . . . . . . . . . . . . . . . . . 11 L1601PC-S1-R . . . . . . . . . . . . . . . . . 30
655LINK-B-LR-W0X-A-DRG. . . . . . . 15 J2-. . . . . . . . . . . . . . . . . . . . . . . . . . . 21 K650SRA. . . . . . . . . . . . . . . . . . . . . . 11 L1601PC-S2. . . . . . . . . . . . . . . . . . . 30
655LINK-B-LR-W0X-B-DRG. . . . . . . 15 J3-. . . . . . . . . . . . . . . . . . . . . . . . . . . 21 K650STICK-OK. . . . . . . . . . . . . . . . . 17 L1601PC-S2-R . . . . . . . . . . . . . . . . . 30
655LINK-C-LR-W0X-A-DRG. . . . . . . 15 J4-. . . . . . . . . . . . . . . . . . . . . . . . . . . 21 K650T1. . . . . . . . . . . . . . . . . . . . . . . 30 L1601PC-T1 . . . . . . . . . . . . . . . . . . . 30
655LINK-C-LR-W0X-B-DRG. . . . . . . 15 J5-. . . . . . . . . . . . . . . . . . . . . . . . . . . 21 K650TBC. . . . . . . . . . . . . . . . . . . . . . 30 L1601PC-T1-R . . . . . . . . . . . . . . . . . 30
655LRTP-W0X-DRG. . . . . . . . . . . . . 17 J6-. . . . . . . . . . . . . . . . . . . . . . . . . . . 21 K650WINDOW-OK. . . . . . . . . . . . . . 17 L1601PC-T2 . . . . . . . . . . . . . . . . . . . 30
655RETP. . . . . . . . . . . . . . . . . . . . . . 17 K1501A1. . . . . . . . . . . . . . . . . . . . . . . 9 K650YBIP. . . . . . . . . . . . . . . . . . . . . 19 L1601PC-T2-R . . . . . . . . . . . . . . . . . 30
655RLRTP. . . . . . . . . . . . . . . . . . . . . 17 K1501FT. . . . . . . . . . . . . . . . . . . . . . . 9 K651CP. . . . . . . . . . . . . . . . . . . . . . . 11 M276BWP. . . . . . . . . . . . . . . . . . . . . . 5
655TCK-W0X . . . . . . . . . . . . . . . . . . 17 K1501J2-U . . . . . . . . . . . . . . . . . . . . . 9 K655BE. . . . . . . . . . . . . . . . . . . . . . . 11 PB-1 . . . . . . . . . . . . . . . . . . . . . . . . . 27
750BIP. . . . . . . . . . . . . . . . . . . . . . . . 11 K1501J3-U . . . . . . . . . . . . . . . . . . . . . 9 K655BEA2. . . . . . . . . . . . . . . . . . . . . 17 PCT1-1X-4 . . . . . . . . . . . . . . . . . . . . 25
750CAB. . . . . . . . . . . . . . . . . . . . . . . 15 K1501J4-U . . . . . . . . . . . . . . . . . . . . . 9 K655BI-LINK-B-LR-W0X-DRG. . . . . 15 PCT1-4 . . . . . . . . . . . . . . . . . . . . . . . 25
750CAM-OK . . . . . . . . . . . . . . . . . . . 15 K1502A1. . . . . . . . . . . . . . . . . . . . . . . 9 K655BI-LINK-C-LR-W0X-DRG. . . . . 15 PCT2-1X-4 . . . . . . . . . . . . . . . . . . . . 25
750CP. . . . . . . . . . . . . . . . . . . . . . . . 11 K150DP. . . . . . . . . . . . . . . . . . . . . . . . 9 K655BLR. . . . . . . . . . . . . . . . . . . . . . 11 PCT2-4 . . . . . . . . . . . . . . . . . . . . . . . 25
750ETP. . . . . . . . . . . . . . . . . . . . . 11,17 K150DR. . . . . . . . . . . . . . . . . . . . . . . . 9 K655BRLR . . . . . . . . . . . . . . . . . . . . 11
750GP. . . . . . . . . . . . . . . . . . . . . . . . 11 K150S. . . . . . . . . . . . . . . . . . . . . . . . . 9 K655BSR. . . . . . . . . . . . . . . . . . . . . . 11
750J2. . . . . . . . . . . . . . . . . . . . . . . . . 13 K150SOP . . . . . . . . . . . . . . . . . . . . . . 9 K655BVS. . . . . . . . . . . . . . . . . . . . . . 11
750J3. . . . . . . . . . . . . . . . . . . . . . . . . 13 K150T. . . . . . . . . . . . . . . . . . . . . . . . . 9 K655DLR-W0X. . . . . . . . . . . . . . . . . 11
750J4. . . . . . . . . . . . . . . . . . . . . . . . . 13 K151LS-W1X. . . . . . . . . . . . . . . . . . . . 9 K655DSR-W0X. . . . . . . . . . . . . . . . . 11
750L12 . . . . . . . . . . . . . . . . . . . . . . . 30 K151LY-W1X. . . . . . . . . . . . . . . . . . . . 9 K655ETP-W0X-DRG. . . . . . . . . . . . . 17
750LB . . . . . . . . . . . . . . . . . . . . . . . . 15 K151S0P. . . . . . . . . . . . . . . . . . . . . . . 9 K655L1 . . . . . . . . . . . . . . . . . . . . . . . 13
PG-CA-1109 Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com 41
Thomas & Betts Corporation
8155 T&B Blvd.
Memphis, TN 38125
Tel: (800) 888-0211
PG-CA-1109
Fax: (800) 888-0690
2009 Thomas & Betts Corporation
All rights reserved. Printed in the USA. 5M