modular distribution blocks

40 to 250 A

Conform to EN 60947-1 n Modular distribution blocks


Insulating voltage according to EN 60947-1 / IEC 60664-1: 500 V
Impulse voltage (Uimp): 8 kV - Degree of pollution: 3 Single pole 125 - 160 - 250 A, Cat.Nos 0 048 71/83/73
Use in DC: without derating 60
Self-extinguishing 960 C on active parts supports 44 7 144

n Monobloc modular distribution blocks

104.5
101.5
45
Double pole 40 - 100 - 125 A, Cat.Nos 0 048 81/80/82 Width
Cat.Nos
(mm)
23

0 048 80 70
0 048 81 105
39

49

0 048 82 140 Connection


44 0 048 84 70 125 A 160 A 250 A
w 50
0 048 85 105 36
36 36
0 048 86 105
Four pole 40 - 100 - 125 A, Cat.Nos 0 048 85/84/86/88 Torque Torque Torque
0 048 88 140 3.5 Nm 24 Nm
3.5 Nm
23

0 048 76 179
0 048 77 160 10 Nm
0 048 79 179
88.5
86

Cat.No 048 71 Cat.No 048 83 Cat.No 048 73


44
w 50

Four pole 125 A Cat.No 0 048 76 n Distribution terminals, Cat.Nos 0 048 67/68
160 A 250 A
47 26.5 60 30
91.5

6.5 12.5 10.5 6.5 10 17 10


97

16

25
44
56

W 50

Four pole 160 A, Cat.No 0 048 79

80
23
91.5

96.8

44
w 50

Four pole 250 A, Cat.No 0 048 77


Self-extinguishing 960 C according to EN 60695-2-11
W
85

150
75
10
45

25

5.5 70.5
134.5 75

n Use of IP 2X terminal blocks (p. )


Modular IP 2X
Derating
distribution Terminal
blocks blocks Voltage Rating
0 048 80 0 048 32(1) 400 V 80 A
0 048 81 0 048 34(1) 400 V 40 A
0 048 82 0 048 35(1) 400 V 100 A
0 048 84 0 048 42(2) 400 V 80 A
0 048 85 0 048 44(2) 400 V 40 A
0 048 86 0 048 44(2) 400 V 100 A
0 048 88 0 048 45(2) 400 V 100 A
0 048 76 0 048 46(2) 400 V 100 A
0 048 79 0 048 45(2) 400 V 100 A

0 048 80 + 0 048 32
1: T
2: Neutral

191/a