3 phase 1 phase

58.8 kW 3.2 kW
415 V 230 V
0.9 PF 0.9 PF
65.3 kVA 3.6 kVA
90.9 A 15.5 A
106.9 Busbar 18.2 Busbar
106.9 MCCB/ MCB 18.2 MCCB/ MCB

25% more 113.61845 A 19.32367 A


Caf DB 133.66876 MCCB/ MCB 22.73373 MCCB/ MCB

Cable
125
171
MCCB/ MCB

MCCB/ MCB
Parameter description Value Unit
Mode of supply 3 Ph
Supply voltage 415 V
Supply frequency 50 Hz

100.9 kW
Input power
Efficiency 1
PF before compensation 0.85
Desired PF 0.95
Type of Capacitor connection Delta

Tan 1 0.62
Tan 2 0.33

Reactive power to be 29.4 kVAr


compensated

Capacitance for each delta 181 F


connected capacitor
Remarks
Input parameters
Calculated output parameters

Considered only for HVAC load @


0.85 diversity

Selection of 2 nos of 10kVAr and 2


nos of 5kVAr units for step control