FCU - FAT CONTROLLERS (Fan Coil Unit Fan Air Terminal)

Model CU780

Variable voltage fan speed control.


230 VAC 2 wire cooling actuator control.
230 V 2 Kw heater control.
3 Kw, 6 Kw single phase units available.
12 Kw, 20 Kw three phase units available.
BMS compatible.
Programmable settings.
2 Inputs for optional BMS monitoring.
All outputs are isolated.
Easy access for address setting.

Product features
Micropowers CU780 Controllers are designed for control of fan coil units or fan air terminals. The CU780 has a 2 Kw heater
output which can be configured to switched or modulated heating. A number of different sensor configurations can be
connected to the CU780 controller by means of a 2 wire sensor cable. The required actuator for chilled water (proportional)
control is a wax 230 V AC type (2 wire). When 230 V AC is applied to the actuator chilled water must flow through the heat-
exchanger. The fan motor speed is controlled by means of variable voltage control and only motors suitable for variable voltage
control may be used. Minimum fan speed can be adjusted by means of a potentiometer accessed through the top of the casing.
Three speed fan motor control by means of motor tappings is available with the use of an optional relay card.

General Specifications
Size Programmable BMS Settings
120 x 185, Depth 65mm (2Kw and 3 Kw models) Deadband,Travel Time, Heating Differential, Cooling
Supply Differential, Max Heating, MaxCooling, Setpoint Overide
230 VAC 10% 50Hz BMS Readings
Connections Room Temperature, Setpoint, % Heating, % Cooling,
1 x sensor socket (4pin) % Fan Speed
1 x slave socket (2 pin) BMS Protocols
1 x output socket (12 pin) Ansi/Ashrae standard 135-1995 BACnet
1 x BMS socket (4 pin) Johnson Metasys N2
1 x light socket 3 pin (optional) Other protocols drivers can be written if the protocol
Outputs specifications are provided
1 x 230 VAC fan Each unit represents a load to the RS485 network
1 x 230 VAC cooling actuator Fan Air Terminal mode
1 x 230 VAC 2 Kw heater output Fan speed increases with temperature increase above
1 x 24 V DC output (optional) to drive external light relay setpoint. Minimum and maximum speeds can be preset.
Digital Sensor This can be combined with fixed speed FCU control.
Wall sensor with 19- 24C setpoint adjuster and lights Fan Coil Unit mode
indicating heating, comfort and cool condition, fan speed, Fan has low, medium and high speeds. Minimum speed
buttons and A/C button can be preset. No FAT's connected in this mode.
Inputs
2 x input (potential free N/O contacts) optional BMS
function

FCU FAT Function Diagram

HIGH
MED SWITCHED
LOW FAN SPEED
MAX FAN SPEED

100% SWITCHED SETPOINT


SWITCHED 100%
HEATER
FAN
MODULATED
MODULATED
MIN FAN SPEED
COOLING

HEAT DIFFERENTIAL 0% 0% COOL DIFFERENTIAL