POWER GRID CORPORATION OF INDIA LIMITED 40G OFm| >806 Ohm (v) VERTICALITY CHECK: 1 No arrester unt wae checked for vrcalty es and found tobe vera (vi) TESTS ON SURGE MONITORS: Surge mentors were immersed water for 30rinThere was no water condersaton found on te meter lass ard paseo tne elowing lst: (a) COUNTER OPERATION TEST: The surge monfors vere subjected ocuentimpuse of 820 u Sec wave shape and found inet each surge countr incremented for every impulse, ()MeTER OPERATION TEST: {he surge nontors were tested for meter operation test and fund tobe operative iy Tests ON Zv0 ELEMENTS: Amexue Alached. (d)_ MEGGER TEST: This test was conducted on arrester with a megger of 5 kV. RefVoltage at | Partial Discharge Resid, Voltage Niegaer sr ‘SmApeak (ec) at T0kA, 8/20uS Test No ow) (evpeak) (Ohm) ‘Specified Specified ‘Spectied $0 Sonn Min 216kV Max. 10p¢ Max 550kVp ‘After Dip “Tested By Withessed by ‘AMOL SHINDE K.MAHAJAN, ‘SR.EXECUTIVE-QA ‘BY.MANAGER CGL-NASHIK POWERGRID-NASHIK AF 2 Crompton Greaves Limited A Strithgen Divison: Per Systeme 9 Ts 491 259.238 2271 F: 49) 253 238 1247 oT DATE: 04.06.2016 TO 07.06.2016 ANNEXURE TO FINAL ACCEPTANCE TEST CERTIFICATE, CIP | TESTS ON ZnO ELEMENT -JUNE- 2018 ZnO ELEMENT- CLASS -3 REFERENCE: SMQP SAC 111 SECTION - FINAL INSPECTION SHORT DURATION AGEING TEST TEST CONDITION: Temp. = 115+ 4 Deg C. Vig. Applied = TEST RESULTS: .B KV. Duration = 72Hours, Sample i 2 [3 28 |Watt loss in watts at 2 Hrs 198_| 158 |197| |, T=15 Hrs, 1a4 | 144 [1.86] | 18 T=30 Hrs. a7 [435 [168] |; T=45 His. 459 [121 [152] |" 45 T=60Hrs 4.48 | 1.08 [1.47 ‘Wat loss in waits at 7 I> 72Hrs 4.32_| 1.06 ]1.32 0 8 Mgt OR ‘Specification: Watt oss shall be less than the initial watt loss at star. THERMAL STABILITY & ENERGY CAPABILITY TEST TEST CONDITION: Rated Voltage = 3.25 kV for 10 Sec & reduced to MCOV 30 Min. Energy=8kJ/KV, ARV for TEST RESULTS: [Sample No a 3 IMCOV for 307min_| —2.8KV aK Zaky | Remark |Watioss 0 min Ost 0.53, 0.55. ‘OK iémin, 0.48, 0.48) 0.55 ‘OK. 30min 4g 0.45; 0.48. ‘OK. Specification: Wattloss trend shall be reducing. WATTLOSS TEST TEST CONDITION: This test was conducted on 3 samples. The walt-loss was measured at MCOV (2.8kV) TEST RESULTS: ‘Samgle No a 3 Watloss in watts TkV Rating] 0.16 | 0.16 Oar Specification: The wait-loss was found to be less than 0.26 walt / KV rating. Tested By Witnessed by ANIOL SHINDE SAURABH BANGADE SREXECUTIVE-QA ENGINEER-QA POWERGRID-NASHIK

You might also like