MITSUBISHI Numerical Protection Relay

MELPRO -D Series TM

MITSUBISHI Numerical Protection Relay


MELPRO -D Series TM

MELPRO -D TM

Mitsubishi ELectric corporation's PROtection relay for Distribution.

Relays suitable for advanced network


HEAD OFFICE : 7-3 MARUNOUCHI 2-CHOME, CHIYODA-KU systems and strongly support power
TOKYO, 100-8310, JAPAN
CAUTION distribution automation.
TO PREVENT IT FROM THE RISK OF DAMAGE AND MAL FUNCTION,
BE SURE TO READ OPERATING AND MAINTENANCE (SERVICING)
INSTRUCTIONS BEFORE USING.
We are waiting your technical contacts by FAX.
ATTN. Protective relay technical service
FAX NO. JAPAN +81-78-996-7074

SE-E840-C(11.03-1.0)ROS "MELPRO" is a trademark of the Mitsubishi Electric Corporation.


This printed matter has been published March 2011. Please note that specifications are subject to change without notice. Published Mar.2011
Safety section
This Safety section should be read before starting any work on the relay. Be sure to read the instruction
manuals and other related documents prior to commencing any work on the relay in order to maintain them
in a safe condition. Be sure to be familiar with the knowledge, safety information and all caution items of the
product prior to use.

CAUTION Caution means that failure to un-observe safety information, incorrect use, or improper use may endanger personnel and equipment and cause personnel injury or physical damage.
Items as classified to the caution may become to occur more sever results according to the circumstance. Therefore, all items described
in the safety section are important and to be respected without fail.

CAUTION
1. Items concerning transportation
(1) Be sure the equipment to be kept in normal direction
(2) Avoid the bumps, shock, and vibration, otherwise the product performance /life might be unfavorably affected.
2. Items concerning storage
(1) Environment shall be as below, otherwise the product performance/life might be unfavorably affected.
-Ambient temperature: -20+60(with no condensation nor freezing)
-Relative humidity: 3080% average of a day
-Altitude: Less than 2000m
-Avoid applying unusual shock, vibration or leaning or magnetic field
-Not expose to harmful smoke, gas, salty air, water, vapor, dust, powder, explosive material or wind, rain.
3. Items concerning mounting/wiring work
(1) Mounting and wiring work should be done correctly. Otherwise, damage, burning or erroneous operation might occur.
(2) Screw terminal should be tightened securely. Otherwise, damage and burning might occur.
(3) Grounding should be done correctly in case it is required. Otherwise, electric shock, damage, burning or erroneous operation might occur.
(4) Wiring should be done without mistake especially observing the correct polarity. Otherwise, damage, burning or erroneous operation might
occur.
(5) Wiring should be done without mistake especially observing the phase ordering. Otherwise, damage, or erroneous operation might occur.
(6) Auxiliary power source, measuring transformer and power source which have enough capacity for correct operation of product should be used.
Otherwise, an erroneous operation might occur.
(7) Be sure to restore the front cover, terminal cover, protection cover, etc to the original position, which have been removed during the mounting/
wiring work. Otherwise, electrical shock might occur at the time of checking.
(8) Connection should be done correctly using designated and right connectors. Otherwise, damage or burning might occur.
(9) Fully insert the sub unit into the case until you can hear a click while pressing the handles located on both sides of the sub unit front face.
Otherwise, incomplete inserting the sub unit might only establish a poor contact with the terminals located on the back side of unit, which might
cause erroneous operation or heating.
4. Concerning equipment operation and settings
(1) Operational condition should be as below. Otherwise, the product performance/life might be unfavorably affected.
-Deviation of auxiliary power: within +10%-15% of rated voltage
-Deviation of frequency: within 5%of rated frequency
-Ambient temperature: 0+40(-10+50 is permissible during couples of hour per day, with no condensation nor freezing)
-Relative humidity: 3080% average of a day
-Altitude: Less than 2000m
-Avoid to be exposed to unusual shock, vibration, leaning or magnetic field
-Not expose to harmful smoke, gas, salty air, water, vapor, dust, powder, explosive material, wind or rain.
(2) Qualified personnel may work on or operate this product, otherwise, the product performance/life might be unfavorably affected and/or
burning or erroneous operation might occur.
(3) Be sure to read and understand the instruction manuals and other related documents prior to commencing operation and maintenance work on
the product. Otherwise, electrical shock, injury, damage, or erroneous operation might occur.
(4) While energizing product, be sure not to remove any unit or parts without permissible one. Otherwise, damage, or erroneous operation might
occur.
(5) While energizing product, be sure to make short circuit of current transformer secondary circuits before setting change or drawing out the sub
unit. Otherwise, secondary circuit of live current transformer might be opened and damage or burning might occur due to the high level
voltage.
(6) While energizing product, be sure to open trip lock terminal before setting change or drawing out the internal unit of product. Otherwise,
erroneous operation might occur.
(7) Be sure to use the product within rated voltage and current. Otherwise, damage or erroneous operation might occur.
(8) While energizing product, be sure not to clean up the product. Only wiping a stain on the front cover of product with a damp waste might be
allowable. (Be sure to wring hardly the water out of the waste.)
5. Items concerning maintenance and checking
(1) Be sure that only qualified personnel might work on or operate this product. Otherwise, electrical shock, injury, damage, or erroneous operation
might occur.
(2) Be sure to read and understand the instruction manuals and other related documents prior to commencing operation and maintenance work on
the product. Otherwise, electrical shock, injury, damage, or erroneous operation might occur.
(3) In case of replacing the parts, be sure to use the ones of same type, rating and specifications, etc. If impossible to use above parts, be sure to
contact the sales office or distributor nearest you. Otherwise, damage or burning might occur.
(4) Testing shall be done with the following conditions.
-Ambient temperature: 2010
-Relative humidity: Less than 90%
-Magnetic field: Less than 80A/m
-Atmospheric pressure: 86106103 Pa
-Installation angle: Normal direction2
-Deviation of frequency: within 1%of nominal frequency
-Wave form (in case of AC): Distortion factor less than 2% (Distortion factor=100%effective value of harmonics/effective value of fundamental)
-Ripple (in case of DC): Ripple factor less than 3% (Ripple factor=100%(max-min)/average of DC)
-Deviation of auxiliary power: within 2% of nominal voltage
-Be sure not to inject the voltage or current beyond the overload immunity. Otherwise, damage or burning might occur.
-Be careful not to touch the energized parts. Otherwise, the electric shock might occur.
6. Items concerning modification and/or repair work
Be sure to ask any modification and/or repair work for product to the sales office or distributor nearest you.
Unless otherwise, any incidents occurred with modification or repair works (including software) done by any other entity than MITSUBIHI
ELECTRIC CORPORATION shall be out of scope on warranty covered by MITSUBISHI ELECTRIC CORPORATION.
7. Items concerning disposal
Particular regulations within the country of operation shall be applied to the disposal.

2 63
Request when placing order
Thank you very much for your usual selecting the MITSUBISHI ELECTRIC CORPORATION products.
When ordering our products described in this catalogue, please read and agree the followings before ordering as long as any special condition are not
nominated in the offer document, contract document, catalogue other than this.

1. Guarantee period
The guarantee period of this product should be one year after delivery, unless otherwise specified by both parties.
2. Scope of guarantee
When any fault or defect is detected during the period of guarantee and such fault or defect is proved to be caused apparently at the responsibility of
MITSUBISHI ELECTRIC CORPORATION, the defective unit concerned will be repaired or replaced by a substitute with free of charge. However, the fee
for our engineer dispatching to site has to be covered by the user. Also, site retesting or trial operation caused along with replacing the defect units should
be out of scope of our responsibilities. It is to be acknowledged that the following faults and defects should be out of this guarantee.
(1) When the faults or defects are resulted from the use of the equipment at the range exceeding the condition/environment requirements stated in the
catalogue and manual.
(2) When the faults or defects are resulted from the reason concerning without our products.
(3) When the faults or defects are resulted from the modification or repair carried out by any other entity than MITSUBISHI ELECTRIC CORPORATION.
(4) When the faults or defects are resulted from a phenomenon which can not be predicted with the science and technology put into practical use at the time
of purchase or contract.
(5) In case of integrating our products into your equipment, when damages can be hedged by the proper function or structure in the possession of your
equipment which should be completed according to the concept of the defact standard of industry.
(6) In case of that the faults or defects are resulted from un-proper application being out of instruction of MITSUBISHI ELECTRIC CORPORATION.
(7) In case that the faults or defects are resulted from force majeure such a fire or abnormal voltage and as an act of God such as natural calamity or disaster.
3. Exclusion of loss in opportunity and secondary loss from warranty liability
Regardless of the gratis warranty term, MITSUBISHI ELECTRIC CORPORATION shall not be liable for compensation of damages caused by any cause
found not be the responsibility of MITSUBISHI ELECTRIC CORPORATION, loss in opportunity, lost profits incurred to the user by failures of MITSUBISHI
ELECTRIC CORPORATION products, special damages and secondary damages whether foreseeable or not, compensation for accidents, and compensation
for damages to products other than MITSUBISHI ELECTRIC CORPORATION products and other tasks.
4. Applications of products
(1) The user is requested to confirm the standards, the regulations and the restrictions which should be applied, in case of utilizing products described in this
catalogue and another one in combination. Also, the user is requested to confirm the suitability of our products to your applied system or equipment or
apparatus by yourself. MITSUBISHI ELECTRIC CORPORATION shall not be liable for any suitability of our products to your utilization.
(2) This MITSUBISHI ELECTRIC CORPORATION products described in the catalogue have been designed and manufactured for application in general
industries, etc. Thus, application in which the life or an asset could be affected, such as medical system for life-sustaining, in nuclear power plants, power
plants, aerospace, and transportation devices (automobile, train, ship, etc) shall be excluded. In addition to above, application in which the life or an asset
could be affected by potentially chemical contamination or electrical interference and also in which the circumstances and condition are not mentioned in
this catalogue shall be excluded. Note even if the user wants to use for these applications with user's responsibility, the user to be requested to approve
the specification of MITSUBISHI ELECTRIC CORPORATION products and to contact to the technical section of MITSUBISHI ELECTRIC
CORPORATION prior to such applications. If the user applies MITSUBISHI ELECTRIC CORPORATION products to such applications without any
contact to our technical section, MITSUBISHI ELECTRIC CORPORATION shall not be liable for any items and not be insured, independently from
mentioned in this clause.
(3) In using MITSUBISHI ELECTRIC CORPORATION product, the working conditions shall be that the application will not lead to a major accident even if any
problem or fault occur, and that backup or duplicate system built in externally which should be decided depend on the importance of facility, are
recommended.
(4) The application examples given in this catalogue are reference only and you are requested to confirm function and precaution for equipment and apparatus
and then, use our products.
(5) The user is requested to understand and to respect completely all warning and caution items so that unexpected damages of the user or the third party
arising out of un-correct application of our products would not be resulted.
5. Onerous repair term after discontinuation of product
(1) MITSUBISHI ELECTRIC CORPORATION shall accept onerous product repairs for 7(seven) years after production is terminated. (However, please
consider the replacement for the products being in operation during 15 years from ex-work.)
(2) Product supply (including repair parts) is not available after production is discontinued.
6. Changes in product specification
The specification given in the catalogue, manuals or technical documents are subject to change without prior to notice.
7. Scope of service
The technical service fee such as engineer dispatching fee is excluded in the price of our products. Please contact to our agents if you have such a
requirement.

How to order
Please check the specifications and be ready with the following information when placing order.
Sample of ordering
Items to be informed In case of COC4-A01D1 Remarks
Fundamental specification

Type name COC4A01D1 Refer to the specifications for detail.


Frequency 50Hz Specify 50Hz or 60Hz.
Ratings Phase current 5A, Zero phase current 1A Refer to the specifications for detail.
Auxiliary power supply voltage AC/DC100220V Refer to the Common Technical data for detail.
Languages English language Specify English or Japanese.
Communication Communication card for CC-Link The communication feature may be installed later through subsequent purchase of
function the communication card. When communication feature is ordered at the same time
with relay itself, type CC-COM2 communication card will be supplied. However, in
case of subsequent purchase of the communication card, please include the
Optional specification

information in your ordering which are the type of relay and presence or absence of
connector for connecting PC located at the lower left corner of the relay front panel.
In case of presence of connector, type of communication card is CC-COM2. In case of
absence of connector, type of communication card is CC-COM.
Parts When ordering, please specify the type of case D1 or D2 and uses of case (for testing
Case purpose or not). Please note that CT circuits shorten mechanism is not equipped in
the dedicated case of testing purpose.

Cover Please specify the type of case D1 or D2.

Please specify the type of relay and terminal block arrangement(from the left side of
Terminal block (with cover)
the back A,B,C,E). Please note ordering only cover is not accepted.

Please note that other specification than described in this catalogue is not applicable for manufacturing.
3
Relays suitable for advanced communication network systems
contribute to build the automated power distribution.
Function
To improve the reliability of distribution system is quite
essential for the stable operation of all facilities installed in Multi function type
the factories and buildings. In order to realize high reliable
distribution system, more functional protection relay as the
core for the protection and control systems is essentially
required. Through passing the age of the electric mechanical Conformity with IEC/JEC
type relay and the transistor type relay, today, the main Protection for high voltage, extra high
voltage power receiving and distribution
stream of protection relay has been moved to the numerical Single function type
Interconnection protection
type. The numerical type protection relay MELPRO-D series Motor protection
Transformer protection
have been developed based on the combination of the plenty Generator protection
know how gained through numerical relay history in several
ten years and the latest electronics technology, and make Matching to JIS/conformity with JEC
Protection for high voltage power receiving and distribution
possible to respond to the recent age needs for more
functionality protection relay system. Hardware size

High accuracy & High speed processing

The high speed digital computation realizes the high accuracy operating characteristics never before possible. The operating
characteristics are configured by the software, so that little deterioration and the stabilized operation can be realized.
Digital computation

The digital computation is also


applied to filter and then little
Analog digital deterioration of filter characteristics
conversion makes improving of reliability.

High degree of reliability


Self-diagnosis function Dual output circuits
continuously monitored area

The self-diagnosis function which monitors continuously the input,


built-in power source and CPU is equipped. In the failures occurring X1
of the relay, they can be detected immediately by the self-diagnosis
function. Furthermore, dual output circuit makes possible to prevent
dual system

the occurrence of misoperation due to the hardware failures.


Dual system

Adopt the structure to be resistant to the disturbances such as the


electric surge and noise, the harmonics, the radio noise from the Always protect the electrical network and at the same time, Prevent the misoperation due
detect the defects of relay and indicated them on the LED. to the hardware failure.
cellular phone, the temperature and the humidity.

Suitable for advanced communication network system

PC

In consideration of future communication network


The communication network system enables the data
acquisition such as measurement value, operation system variations and compatibility, communication
status and setting value as well as the remote features are installed in the relay using a replaceable
operation such as the setting changes from the central P L C
card. Thereby, it is plenty flexible and extensible.
control system. Thereby, efficient operation and I/F CPU SI/O Master
maintenance can be realized.
Field bus
Communication card (option)

CC-Link
By connecting PC with relay via the RS232C port
located on the relay panel, local operation and RYMELPRO-D
monitoring are enabled as same as the remote RY Other than RY
operation and monitoring. Thereby, the maintenance
work at site is strongly supported.
Special HMI software (option) is needed for local Case
operation and monitoring.
Please refer to the specification table for each type of Sub unit
relay to confirm the capable of communication port
and cards. RS-232C Cover
4
Mitsubishi Numerical type protection relay MELPRO -D series TM

Programmable output contacts complying with requirements on the flexibility


The operating output contacts can be set by combing Output sequence
the outputs of the protection relay element using OR can be set freely I X0
logic, thereby simplifying sequence design. with usingORlogic
Contacts for signaling
Also, it is possible to reduce the cost of switchboard as I (4 circuits)
reducing wiring works.
X3

I X4
Contacts for tripping
X5 (2 circuits)
I
Schematic image of programmable output (Example: type COC4-A01)

Substantial measuring function

Possible to measure the steady state of the relay input values (Current,
Voltage, Power, Frequency, Power factor, Zero phase current and Zero
phase voltage), thereby possible to support the energy management.
Remark: Please note that measuring item is depended on the type of relay.
Refer to the specification table of each relay type for the detail on this regards.

In the event of system fault, input effective value and wave form data have been
measured and stored at the time when one of the protection elements operates to
issue an output signal. Data for up to five phenomena can be stored and displayed.
Therefore, analyze of phenomena becomes easy. Upper Fig. : Image of waveform down loaded by the Direct PC HMI software

Replacement of existing relay

The dimension of the panel cutting is the same as the prior MULTICAP series. Replacing from the existing one to this new type is possible easily without using adaptor.
Also, as this relay has a high degree of compatibility with the existing relay, the design change of the existing system is minimized.Except for some types of relay

Easy maintenance

The draw-out unit mechanisms with automatic CT shorting is adopted, so that relay unit can be draw out without removing any parts
or wirings. Thereby, it is possible to improve maintenance ease.

contents
Safety section 2 CDG Series EARTH FAULT DIRECTIONAL RELAY 24
Request when placing order 3 CAC Series BIASED DIFFERENTIAL 30
How to order 3 RELAY FOR TRANSFORMER PROTECTION
Features of MELPRO-D series 4 CMP Series MOTOR PROTECTION RELAY 35
Type of MELPRO-D series 6 CPP Series SYSTEM LINKAGE PROTECTION RELAY 42
(listing of implemented elements) CGP1 Series GENERATOR PROTECTION RELAY 47
Selection of type of relay (example) 7 CGP2 Series GENERATOR PROTECTION RELAY 53
Common Technical Data 8 MELPROD Series Dimensions 59
Suggestion from Mitsubishi Electric 60
COC Series OVER-CURRENT RELAY 9 (for improving reliability of system)
CBV, CUB Series VOLTAGE RELAY 20 CONTROL and OPERATION 61
CFP Series FEEDER PROTECTION RELAY 24 Display/Setting Operation 62

5
6
Type of MELPRO-D series (listing of implemented elements)
Type of MELPRO-D series and implemented elements for each type are shown as below Table.
Series Type 50/51 50G/51G 67G 27 59 64 87T 49 37 46 47 66 67S 67P 95L 95H 91L df/dt 84 87G 40 Remarks
COC1A01D1 CTphase current

COC1A02D1 CTphase current

COC2A01D1 CT2 phases current

COC3A01D1 Overcurrent relay CT3 phases current

COC3A03D1 P.9 CT3 phases current

COC4A01D1 CT3 phases current

COC4A02D1 CT3 phases current

COC4A03D1 CT3 phases currentWith 2nd harmonic current detection

CBV2A01D1 VT3 line voltage

CBV3A01D1 Voltage relay VT1 line voltage

CBV4A01D1 P.20 VT3 line voltage

CUB1A01D1 VT3 line voltage

CFP1A01D1 Feeder protection relay CT2 phases currentFor EVT




CFP1A02D1 P.24 CT2 phases currentFor EVT

CDG1A01D1 Earth fault directional relayP.24

CAC1A01D2 Biased differential relay for (2 windings) transformer protectionP.28

CMP1A01D1/2 CT2 phases currentFor EVT
Motor protection relay
CMP1A02D1 CT3 phases current
P.35
CMP2A02D2 CT3 phases current

CPP1A01D2 Interconnection protection relay for For extra high voltage interconnectionFor EVT
the dispersed generation system
CPP1A11D2 P.42 For extra high voltage interconnectionFor EVT

CGP1A01D2 Generator protection relay CT2 phases currentFor EVT

CGP1A03D2 P.47 CT3 phases current

CGP2A01D2
Biased differential relay for Generator protectionP.53
CGP2A02D2
Selection of type of relay (example)

TM
Network Device number MELPRO -D
1CBV3-A01D1
33W 66kV 33W 22kV/11kV 27
3CBV2-A01D1
Incoming of 50/51 3COC3-A01D1/COC3-A03D1
extra high voltage COC4-A01D1
VT 27 51G 1COC1-A02D1
VT 27 COC4-A02D1
U 50/51 3COC3-A01D1/COC3-A03D1
COC4-A03D1
U 51G 1COC1-A02D1
27 1CBV2-A01D1
CB CB 59 2CBV3-A01D1
50/51 51G 87T CAC1-A01D2
50/51 51G
CT I I 50/51 3COC3-A01D1/COC3-A03D1
CT I I COC4-A01D1
Extra high voltage 51G 1COC1-A02D1
(secondary of 50/51 3COC3-A01D1/COC3-A03D1
CT CT transformer) COC4-A01D1
51G 1COC1-A02D1
50/51 COC3-A01D1/COC3-A03D1
87T 27
TR
87T 59 CBV3-A01D1
TR Isolated neutral system Id/I
Id/I 64
50/51 51G
NGR 50/51 COC2-A01D1
50/51 51G CT I
I 67G CFP1-A01D1
Resistance grounded C T I I 27
neutral system CT
High voltage 59 CBV3-A01D1
27 59 (secondary of 64
CT U U transformer) 50 51 51G
CMP1-A02D1/CMP2-A02D2
37 46 49 66
27 59
50 51 67G
U U U 64 CMP1-A01D1/CMP1-A01D2
37 46 49 66
Remark 1: It is advisable to adopt the dual system or 2 out of 3 systems in order to improve the reliability of the important facilities.
CB CB EVT Remark 2: In case of not available an uninterruptible power source, please use AC/DC converter type B-T1 manufactured by
VT MITSUBISHI ELECTRIC CORPORATION or commercially available uninterruptible power source (UPS) instead of using AC
11kV/22kV 6.6kV/3.3kV auxiliary power source such as derived from VT secondary circuit because of no guarantee against power interruption during
67G 50 51 67G 37 46 49 66 system faults.
ZCT 3 I ZCT 3 III
CB 50/51 51G CB 50/51 51G CB 50 51 51G 37 46 49 66 INSC
III CB 50/51 CB Its
CT I I CT I I CT
INSC CT I CT
Its

SC M M

Abbreviation
CB : Circuit Breaker
CT : Current Transformer
EVT : Earthed type voltage Transformer
M : Motor
NGR : Neutral Grounded Resister
SC : Static Condenser
TR : Transformer
VT : Voltage Transformer

7
Common Technical Data

ITEM DESCRIPTION CONDITION STANDARD


Ambient operating
10 to 55 IEC60255-6
temperature
Ambient storage and
Environment 25 to 70 IEC60255-6
transport temperature

Damp heat 40, 95RH, 4days IEC60068-2-78

100, 110, 125, 220VDC


Auxiliary power supply 100,110,120,220VAC IEC60255-6
(Applicable to any voltage above)
DC: 15 to 10
Operative range of (Temporarily 20 to 30)
Ratings IEC60255-6
auxiliary power supply AC: 15 to 10
(Temporarily 15 to 15)
Frequency 50 or 60Hz IEC60255-6
VT
Specified per relay type
CT
Auxiliary power supply
Burden VT Specified per relay type
CT
Thermal VT 1.15VN, 3hours
withstand IEC60255-6
CT 40IN, 1second
110V DC: 15A, 0.5s
Make (L/R0) IEC60255-0-20
220V DC: 10A, 0.5s
For trip
110V DC: 0.3A
Break (L/R40ms) IEC60255-0-20
220V DC: 0.15A
Contact 500VA (cos 0.4)
capacity Break IEC60255-0-20
60W (L/R0.007s)

For signalling and alarm Max.


5A IEC60255-0-20
current
Max. 380VAC/125VDC IEC60255-0-20
voltage
1) Between each circuit and the
exposed conductive parts, the
Circuit of 60V or below 500VAC, 1min.
terminals of each independent
circuit being connected
together
Dielectric test IEC60255-5
2) Between independent circuits,
Circuit of more than 60V the terminals of each
2000VAC, 1min.
and 500V or below independent circuit being
connected together
Open contact 1000VAC, 1min. Between open contact poles
1) Between each circuit and the
exposed conductive parts, the
terminals of each independent
circuit being connected
Impulse voltage test 5kV, 1.2s/50s together IEC60255-5
2) Between independent circuits,
the terminals of each
independent circuit being
connected together
Between independent circuits, and
2.5kV peak, 1MHz with 200
High-frequency Common mode between independent circuit and
source impedance for 2second IEC60255-22-1
disturbance earth
class 3
test 1.0kV peak, 1MHz with 200 Across terminals of the same
Differential mode
source impedance for 2second circuit
8kV Contact discharge IEC60255-22-2
Electrostatic discharge test
15kV Air discharge class 4
Radiated electromagnetic field 38 to 87MHz 146 to 174MHz IEC60255-22-3
disturbance test 420 to 470MHz class 3
Fast transient disturbance test 2.0kV, 5ns/50ns, 1min. IEC60255-22-4
IEC60255-21-1
Vibration test Refer to class 1
class 1
IEC60255-21-2
Shock response Refer to class 2
class 2
IEC60255-21-2
Shock withstand Refer to class 1
class 1
IEC60255-21-2
Bump Refer to class 1
class 1
Enclosure protection IP51 IEC60529
VN: Rated voltageIN: Rated current
8
COC Series OVER-CURRENT RELAY
COC
Type, rating and specification
Type name COC1A02D1 COC1A01D1 COC2A01D1 COC3A01D1
Phase current 1A 5A 5A 5A
Rating Zero-phase current
Frequency 50Hz or 60Hz
Protective element 51/50 1 phase 51/50 2 phases 51/50 3 phases
Operation current LOCK0.10.8A0.05A step LOCK112A0.1A step
Operation time multiplier 0.250.550 0.5 step
Time-
Operation time Normal inverse time-delayed3 kinds, Very inverse time-delayed2 kinds,
delayed
characteristics Extremely inverse time-delayed3 kinds, Long inverse time-delayed3 kinds, Definite time-delayed1 kind
Reset time characteristics Normal inverse time-delayed 1 kind, Definite time-delayed 2 kinds
Setting Operation current LOCK18A0.1A step LOCK280A1A step
Instantaneous
Operation time INST0.10.5s 0.1s step
Output contact configuration Refer to the external connection diagram/Auto reset for all contacts Default setting at ex-works
Operation indicator LED hold All LED self-hold Default setting at ex-works
15101212.5152025304050607580100120125150200250300400500600750800100012001250
CT primary
150020002500300040005000600075008000[A] Positive phase rating : Applicable 1 A rating product only
Real time measurement Phase current 1 phase Phase current 2 phases Phase current 3 phases
Max.record Phase current 1 phase Phase current 2 phases Phase current 3 phases
Fault recordoperation value Phase current 1 phase Phase current 2 phases Phase current 3 phases
Fault recordoperation item Record and indicate the operated elements
Display
010 (The value 0 indicates the status of input current reaching the setting value or more and
Elapse of time-delayed timer
the value 110 indicate the elapse time up to operating of the time delayed element.
Normal result: On the RUN LEDgreenStatus indication item No.400=No display.
Self-diagnosis
Abnormal result: Off the RUN LEDStatus indication item No.400=Display defects code
Forced operation Each output contact
Direct communication port Standard equipmentPC software for Direct communication: option
Communication
Remote communication port Option For CC-LINK
Phase current circuit: Less than 0.5VA/phase
Burden (at rating) Auxiliary power supply circuit: at DC100V=Approx. 5W, at AC100V=Approx. 7VA, at DC220V=Approx. 6W,
at AC220V=Approx. 12VAIn case of installing communication card, add 2 VA.
Mass Net weight of relay unit: Approx. 2.3kg, Including case: Approx. 3.0kg
Sample of external connection diagram Fig.157 Fig.135 Fig.1-8 Fig.1-9
The rated current 0.2A product can be made based on the 1A rating product.Also, the rated current 1A
product can be made based on the 5A rating product.
Remarks
The setting value of time delayed element and instantaneous element of 0.2A product and 1A product are
calculated by performing a multiplication 1/5 of above mentioned value.

Please refer to the instruction manual regarding the details on this specification.

9
COC

Type name COC3A03D1 COC4A01D1 COC4A02D1 COC4A03D1


Phase current 5A 5A 5A 5A
Rating Zero-phase current 1A 5A 1A
Frequency 50Hz or 60Hz
Protective element 51/50 3 phases 51/50 3 phases, 51G/50GZero-phase
Operation current LOCK0.58A0.1A step LOCK112A0.1A step
Operation time multiplier 0.250.550 0.5 step
Phase fault
Operation time Normal inverse time-delayed 3 kinds, Very inverse time-delayed 2 kinds,
time-delayed
characteristics Extremely inverse time-delayed 3 kinds, Long inverse time-delayed 3 kinds, Definite time-delayed 1 kind
Reset time characteristics Normal inverse time-delayed1 kind, Definite time-delayed 2 kinds
Phase fault Operation current LOCK280A1A step
instantaneous Operation time INST0.10.5s 0.1s step
Operation current LOCK0.10.8A0.05A stepLOCK0.58A0.1A stepLOCK0.10.8A0.05A step
Earth fault Operation time multiplier 0.250.550 0.5 step
Setting time-delayed Operation time Normal inverse time-delayed (3 kinds) , Very inverse time-delayed (2 kinds),
characteristics Extremely inverse time-delayed (3 kinds) , Long inverse time-delayed (3 kinds),
Definite time-delayed (1 kind)
Reset time characteristics Normal inverse time-delayed 1 kind, Definite time-delayed 2 kinds
Earth fault Operation current LOCK18A0.1A step LOCK280A1A step LOCK18A0.1A step
instantaneous Operation time INST0.10.5s 0.1s step
2nd harmonic blocking 1025%5% step
Operation indicator LED hold Refer to the external connection diagram/Auto reset for all contacts Default setting at ex-works
Output contact configuration All LED self-hold Default setting at ex-works
CT primaryPhase current 15101212.5152025304050607580100120125150200250300400500600750800100012001250
CT primaryZero-phase current 150020002500300040005000600075008000[A] Positive phase rating : Applicable 1 A rating product only
Phase current 3 phases,
Real time measurement Phase current 3 phases Phase current 3 phases, Zero-phase current Zero-phase current Percentage of
2nd harmonic current content
Max.record Phase current 3 phases Phase current 3 phases, Zero-phase current
Fault recordoperation value Phase current 3 phases Phase current 3 phases, Zero-phase current
Display
Fault recordoperation item Record and indicate the operated elements
010 (The value 0 indicates the status of input current reaching the setting value or more and
Elapse of time-delayed timer
the value 110 indicate the elapse time up to operating of the time delayed element.
Normal result: On the RUN LEDgreenStatus indication item No.400=No display.
Self-diagnosis
Abnormal result: Off the RUN LEDStatus indication item No.400=Display defects code
Forced operation Each output contact
Direct communication port Not applicable Standard equipmentPC software for Direct communication: option
Communication
Remote communication port Not applicable Option For CC-LINK
Phase current circuit: Less than 0.5VA/phase, Zero phase circuit: Less than 0.5VA
Burden (at rating) Auxiliary power supply circuit: at DC100V=Approx. 5W, at AC100V=Approx. 7VA, at DC220V=Approx. 6W,
at AC220V=Approx. 12VAIn case of installing communication card, add 2 VA.
Mass Net weight of relay unit: Approx. 2.3kg, Including case: Approx. 3.0kg
Sample of external connection diagram Fig.19 Fig.11013 Fig.11012, 14 Fig.11013
The rated current 1A product can be made based on the 5A rating product.
The setting value of time delayed element and instantaneous element of 1A product is calculated by
Remarks performing a multiplication 1/5 of above mentioned value.
The operation current setting range "LOCK-2130A (1A step)" for phase fault instantaneous element of
type COC4-A02D1 is also available.

Please refer to the instruction manual regarding the details on this specification.

10
COC
Characteristics
Items Condition Guaranteed performance
Setting 1.02.0A for 5A rating product
Setting 0.20.4A for 1A rating product
Phase fault time- Setting value 10%
delayed element For setting of other range
Setting value 5%
Phase fault instantaneous element Common condition1 Setting value 10%
Setting 0.10.2A for 5A rating product
Setting 0.020.04A for 1A rating product
Earth fault time-
Setting value 10%
delayed element For setting of other range
Setting value 5%
Operation
Earth fault instantaneous element Setting value 10%
current
In case of half-wave rectified current
superposing
IDCSetting tap value80 IAC254330
2 Setting value10%
I
2f/1f blocking
If2 3 DC
100
If1
COC4A03D1 2 IAC IDC
2
10 Setting value
In case of harmonic current Setting value 15
superposing method 1525 Setting value
Setting value 10
Setting 1.02.0A for 5A rating product
Setting 0.20.4A for 1A rating product
Phase fault time- Operation value90% or more
delayed element For setting of other range
Operation value95% or more
Operation value95% or more
Phase fault instantaneous element
Reset value Common condition1 Setting 0.10.2A for 5A rating product
Setting 0.020.04A for 1A rating product
Earth fault time- Operation value90% or more
delayed element For setting of other range
Operation value95% or more
Earth fault instantaneous element Operation value95% or more
2f/1f blockingCOC4A03D1 Operation value85% or more
Operation setting value:Minimum, Refer to fig.1-1.2
Phase fault time-
Operation time multiplier:10 Timing accuracy for I3Current setting value,
delayed element
Input :0Operation setting value300% or more 3.5% of reference at actual pick up
Phase fault Setting value 25ms
Operation setting value:Minimum
instantaneous In case of INST setting 40ms or less (except COC4-A03D1)
Input :0200% of setting value
element 50ms or lessCOC4-A03D1
Operation time
Operation setting value:Minimum, Refer to fig.1-1.2
Earth fault time
Operation time multiplier:10 Timing accuracy for I3Current setting valve,
delayed element
Input :0Operation setting value300% or more 3.5% of reference at actual pick up
Earth fault Setting value 25ms
Operation setting value:Minimum
instantaneous In case of INST setting 40ms or less (except COC4-A03D1)
Input :0200% of setting value
element 50ms or lessCOC4-A03D1
Reset time All elements 300% of setting value0A Refer to table 1-1
Time-delayed operation value: Minimum
Phase fault time Operation time multiplier:10
Overshoot No-operation limit time/Operation time=90% or more
delayed element Operation characteristic:All characteristics
characteristic
Input current :0ASetting value1000%
Earth fault time-delayed element Same as the above Same as the above

1Common condition
1Rating Frequency2Ambient temperature203Auxiliary power supply: Rating voltage

11
COC
Precaution for application
1. Guarantee against interruption of AC power supply of the relay and the self-diagnosis output contact feed from a same
When an uninterruptible AC power source is not available in your power source, the break contact will be closed temporarily after
system for the auxiliary power supply, use the type B-T1 AC/DC auxiliary power supply is turned on. In this case where the
converter or commercially available uninterruptible power supply phenomenon stated in the above would conflict with your system
(UPS). In addition, possible duration of the power supply type B-T1 requirement, it is recommended that the self-diagnosis output contact
AC/DC converter is confirmed as about 2 seconds in combination should be connected via the time-delay timer.
with one MELPRO-D series relay. Therefore, in the case that the 5. Grounding circuit
required duration of power supply after power source loss exceeds 2 Be sure to make a wiring to the earth terminal located on the back of
seconds, please use a suitable commercial uninterruptible power the relay according to the Class D earth wiring method (Grounding
supply. When power supply back up for the circuit breaker is resistance should be less than 100 ohm).
required, it is necessary to prepare the power supply independent 6. CC-Link communication circuit
from the type B-T1 AC/DC converter. Please include the communication card into your purchasing order in
2. Inrush current of power supply case of the application of the communication facility as the card
Since inrush current (about 2ms duration) as below may flow into the necessary for communication (CC-Link ) is option. In case of retrofit
relay when the power supply is turned on, please make a existing relay with communication card, please inform the followings
consideration on this regard for selection of power circuit breaker. of existing relay. a:Type, b:Style number, c:Manufacturing year,
d:Serial number, e:Date of stamp on the checking seal (The above
Input voltage Inrush current Ip
mentioned items a.d. are indicated on the bottom right of front face
DC110V Approx. 20A
of the relay and item e. is indicated on the upper of back side of the
DC220V Approx. 55A
relay.) The version number of CC-Link is 1.00.
AC100V Approx. 25A
7. Improvement of reliability of protection system
AC220V Approx. 65A
For the important facilities, multiplex system such as dual should be
3. Trip circuit provided to improve reliability.
Only the dedicated contacts can be used for the circuit breaker trip 8. Effects of external surge
circuit. Please keep in mind that the contacts for signaling can not be Some type of surge with a certain condition may inversely affect the
used for the trip circuit. (If used, the contact may burn). Also, connect relay. If so, take it into account to install surge absorbers.
the pallet contact (52a) of the circuit breaker to the trip coil circuit in 9. The residual connection of 3 phases CT is needed for the earth fault
series. current elements of COC4-A01, A02, A03D1 types.
4. Self-diagnosis output circuit 10. It is possible to use the COC3 and COC4 as the phase over current
The self-diagnosis output contact is so configured that the auxiliary protection provided with two phases. However, residual connection of
relay is energized ( break contactopened) when normal result of 2 phases can not be applied to the earth fault over current element of
self-diagnosis is received. This type of contact will allow the relay to COC3 and COC4 types. The residual connection of 3 phases only can
output abnormal result even after the built-in power failures. be applied to the earth fault over current element. In case of only two
Therefore, the break contact is still closed in the aftermath of the phase CTs being available for phase over current protection, ZCT or
power applying and will be opened after 50ms. If the auxiliary power one more CT is needed for earth fault over current element.

Precaution for using


1. When the product is shipped from the factory, each setting value is 3. The setting of measuring transformer ratio is applied only for the
LOCK (for element with LOCK position) or minimum setting measuring indication converted to the primary side, and is not
value(for element without LOCK position) applied for protection element.
2. To set as [LOCK] position means to set the element out of use.

Precaution for safety


Please refer to page2 and 3 regarding the safty information and request
when placing order.

12
COC
Operation time and Reset time characteristics
The time-delayed element have 12 kinds of operation characteristics as shown on Fig.1-1 and Fig.1-2, and 3 kinds of reset time
characteristics as shown on table 1-1.

500 NI01Normal inverse time-delayed characteristic NI11Normal inverse time-delayed characteristic


500
0.14 M 0.0515 M
t 0.02
I 1

10 (s)
t 0.02
I 1
0.114
10 (s)

VI01Very inverse time-delayed characteristic EI11Extremely inverse time-delayed characteristic


13.5 M 19.61 M
100 t
I1

10 (s) 100
t 2
I 1
0.491
10 (s)

EI01Extremely inverse time-delayed characteristic EI12Extremely inverse time-delayed characteristic


80 M 28.2 M
t 2
I 1

10 (s)
t 2
I 1
0.1217
10 (s)
Operation time t (s)

Operation time t (s)


LI01Long inverse time-delayed characteristic NI21Normal inverse time-delayed characteristic
54 M 2.4 M
10
t
I1

10 (s)
10
t 0.4
I 1
1.2
10 (s)
LI02
LI02Long inverse time-delayed characteristic VI21Very inverse time-delayed characteristic
LI01 80 M LI21
16 M
NI01 t
I

10 (s)
NI21
t
I1
0.4
10 (s)

DT01Definite time-delayed characteristic VI21 LI21Long inverse time-delayed characteristic


DT01
M NI11 60 M
VI01 t 2 t
1 10 (s) I1 10 (s)
1
Operation time EI11 Operation time
Current Current
EI01 (Multiple of input current (Multiple of input current
EI12
against setting value) against setting value)
Operation time multiplier Operation time multiplier

These curves show the operation


0.1 0.1 time characteristic for each type in
1 2 5 10 20 1 2 5 10 20 case of the time multiplier M=10.
Current (Multiple of input current against setting value) I Current (Multiple of input current against setting value) I

Fig.1-1Operation time characteristics1 Fig.1-2Operation time characteristics2

Table 1-1Reset time characteristic


InputSetting value3000
Output contact Reset of operation timer inside relay
Definite time delayed.200ms immediately
Inverse time delayed. Approx.M10
Definite time delayed.50ms or less immediately

Inverse time-delayed characteristic for reset


Following the principle of resetting an electromagnetic mechanical type induction disc, the
inverse time-delayed characteristic given by the equation below is used for computing the
reset time of the internal operation timer, although the output contact will be reset after a
definite period of time (0.2 s). The inverse time-delayed characteristic may be useful for
detecting an intermittent overload, which typically occurs in starting a motor.

8 M
tr (s)
1I2 10

13
COC
Sample of external connection diagram

+ A01 B05
A B C Auxiliary Y Self diagnosis output
power supply B06
circuit A03
B07
X0
B08 Instantaneous
B09 I
X1
A07 B10 For
B11 signaling
IA X2
A08
B12 Time-delayed
B13 I
X3
B14
CT
B17
X4
B18
IOR I For trip
B19
X5
B20
Programmable output
ED Communication card Default setting at ex-works
B01 DA
B02 DB
(option)

Serial communication bus


B03 DG
E A02
B04 SLD
ED

Fig.13COC1A01D1Phase fault protection

+ A01 B05
A B C Auxiliary Y Self diagnosis output
power supply B06
circuit A03
B07
X0
B08 Instantaneous
B09 I
X1
B10 For
B11 signaling
X2
B12 Time-delayed
A07 B13 I
X3
IO B14
A08
B17
X4
B18
IOR I For trip
B19
CT X5
B20
Programmable output
Communication card

ED
B01 DA Default setting at ex-works
B02 DB
(option)

Serial communication bus


B03 DG
E A02
B04 SLD
ED

Fig.14COC1A01D1Solidly grounded neutral system, Earth fault protection


The connection diagram shows concepts of the wiring only. Therefore, please note that there will have some difference
between the connection diagram and actual installation status of CT,VT and safety devices such as fuse, etc.
14
COC

+ A01 B05
A B C Auxiliary Y Self diagnosis output
power supply B06
circuit A03
B07
X0
B08 Instantaneous
B09 I
X1
A05 B10 For
B11 signaling
I0 X2
A06
B12 Time-delayed
B13 I
X3
COC3A01D1 B14
CT
B17
X4
B18
IOR I For trip
B19
X5
B20
Programmable output
Communication card
ED Default setting at ex-works
B01 DA
(option) B02 DB
Serial communication bus
B03 DG
E A02
B04 SLD
ED

The terminal number A-05 is changed to A-07 and A-06 is changed to A-08 in case of COC1-A01D1 type

Fig.15COC1A01D1COC1A02D1Earth fault protection

Example: 100A grounding system


+ A01 B05
A B C Auxiliary Y Self diagnosis output
power supply B06
circuit A03
B07
COC3A01D1 X0
B08 Earth fault
Instantaneous
B09 I
X1
B10 For
B11 signaling
X2
Earth fault
Example: B12 Time-delayed
400/5 or more B13 I
X3
CT B14
ED B17
A05 X4
Example: B18 For trip
I0 IOR I
100/5 A06 B19
X5
ED B20
Programmable output
Communication card

B01 DA Default setting at ex-works


B02 DB
(option)

Serial communication bus


B03 DG
E A02
B04 SLD
ED

Fig.16COC1A02D1Earth fault protection


The connection diagram shows concepts of the wiring only. Therefore, please note that there will have some difference
between the connection diagram and actual installation status of CT,VT and safety devices such as fuse, etc.
15
COC

Example: 100A grounding system


+ A01 B05
A B C Auxiliary Y Self diagnosis output
power supply B06
circuit A03
B07
X0
B08 Earth fault
Instantaneous
B09
X1 I
B10 For
B11 signaling
X2 Earth fault
B12 Time-delayed
A05 B13 I
X3
ZCT B14
IO
Example: 100/5 A06
B17
X4
ED B18 IOR I For trip
B19
X5
B20
Programmable output
Communication card Default setting at ex-works
B01 DA
B02 DB
(option)

Serial communication bus


B03 DG
E A02
B04 SLD
ED

Fig.17COC1A02D1Earth fault protection

+ A01 B05
A B C Auxiliary Y Self diagnosis output
power supply B06
circuit A03
B07
X0
B08 Instantaneous
B09 I
X1
A07 B10 For
B11 signaling
IA A08 X2
B12 Time-delayed
B13 I
X3
A11
B14
IC B17
A12 X4
CT B18
IOR I For trip
B19
X5
B20
Programmable output
Communication card

ED
B01 DA Default setting at ex-works
(option)

B02 DB
Serial communication bus
B03 DG
E A02
B04 SLD
ED

Fig.18COC2A01D1Phase fault protection


The connection diagram shows concepts of the wiring only. Therefore, please note that there will have some difference
between the connection diagram and actual installation status of CT,VT and safety devices such as fuse, etc.
16
COC

+ A01 B05
A B C Auxiliary Y Self diagnosis output
power supply B06
circuit A03
B07
X0
B08 Instantaneous
B09 I
X1
A07 B10 For
B11 signaling
IA X2
A08
B12 Time-delayed
A09 B13 I
X3
IB B14
A10
B17
X4
A11 B18
IOR I For trip
B19
IC X5
A12
B20
CT Programmable output
Communication card B01 DA Default setting at ex-works
(option) B02 DB
Serial communication bus
B03 DG
ED E A02
B04 SLD
ED

The serial communication facility is not available for type COC3-A03D1.

Fig.19COC3A01D1COC3A03D1Phase fault protection

+ A01 B05
A B C Auxiliary Y Self diagnosis output
power supply B06
circuit A03
B07 Earth faultInstantaneous
X0 I
A07 B08
IA B09 Earth faultTime-delayed
A08 X1 I
B10 For
A09 signaling
B11 Phase faultInstantaneous
IB X2 I
A10 B12
B13 Phase faultTime-delayed
A11 X3 I
IC B14
CT A12 B17
X4
A05 IOR I
B18
For trip
I0 B19 OR IOR I
A06 X5
B20
ED Programmable output
Communication card

B01 DA Default setting at ex-works


Tr
(option)

B02 DB
Serial communication bus
B03 DG
E A02
B04 SLD
ED

Fig.110COC4A01D1COC4A02D1COC4A03D1
The connection diagram shows concepts of the wiring only. Therefore, please note that there will have some difference
between the connection diagram and actual installation status of CT,VT and safety devices such as fuse, etc.
17
COC

+ A01 B05
A B C Auxiliary Y Self diagnosis output
power supply B06
circuit A03
B07 Earth faultInstantaneous
X0 I
A07 B08
IA B09 Earth faultTime-delayed
A08 X1 I
B10 For
A09 signaling
B11 Phase faultInstantaneous
IB X2 I
A10 B12
B13 Phase faultTime-delayed
A11 X3 I
IC B14
CT
A12 B17
X4
IOR I
ED B18
For trip
B19 OR IOR I
A05 X5
B20
ZCT I0 Programmable output
Example: 100/5 A06 Communication card Default setting at ex-works
B01 DA
ED B02 DB
(option)

Serial communication bus


B03 DG
E A02
B04 SLD
ED

Fig.111COC4A01D1COC4A02D1COC4A03D1

+ A01 B05
A B C Auxiliary Y Self diagnosis output
power supply B06
circuit A03
B07 Earth faultInstantaneous
X0 I
A07 B08
IA B09 Earth faultTime-delayed
A08 X1 I
B10 For
A09 signaling
B11 Phase faultInstantaneous
IB X2 I
A10 B12
B13 Phase faultTime-delayed
A11 X3 I
Example: IC B14
400/5 or more A12 B17
X4
IOR I
B18
CT ED For trip
B19 OR IOR I
A05 X5
B20
Example: I0 Programmable output
Communication card

100/5 A06 Default setting at ex-works


B01 DA
B02 DB
(option)

ED
Serial communication bus
B03 DG
E A02
B04 SLD
ED

Fig.112COC4A01D1COC4A02D1COC4A03D1
The connection diagram shows concepts of the wiring only. Therefore, please note that there will have some difference
between the connection diagram and actual installation status of CT,VT and safety devices such as fuse, etc.
18
COC

Example: 100A grounding system


+ A01 B05
A B C Auxiliary Y Self diagnosis output
power supply B06
circuit A03
B07 Earth faultInstantaneous
X0 I
A07 B08
IA B09 Earth faultTime-delayed
A08 X1 I
B10 For
A09 signaling
B11 Phase faultInstantaneous
IB X2 I
A10 B12
B13 Phase faultTime-delayed
A11 X3 I
IC B14
CT
A12 B17
X4
IOR I
ED B18
For trip
B19 OR IOR I
A05 X5
B20
I0 Programmable output
Communication card
Tr
A06 B01 DA Default setting at ex-works
ZCT (option) B02 DB
Example: 100/5 Serial communication bus
B03 DG
E A02
ED B04 SLD
ED

Fig.113COC4A01D1COC4A03D1

Example: Solidly grounded neutral system


+ A01 B05
A B C Auxiliary Y Self diagnosis output
power supply B06
circuit A03
B07 Earth faultInstantaneous
X0 I
A07 B08
IA B09 Earth faultTime-delayed
A08 X1 I
B10 For
A09 signaling
B11 Phase faultInstantaneous
IB X2 I
A10 B12
B13 Phase faultTime-delayed
A11 X3 I
IC B14
CT
A12 B17
X4
IOR I
ED B18
For trip
B19 OR IOR I
A05 X5
B20
Tr I0 Programmable output
Communication card

A06 B01 DA Default setting at ex-works


B02 DB
(option)

CT Serial communication bus


B03 DG
E A02
ED B04 SLD

ED

Fig.114COC4A02D1
The connection diagram shows concepts of the wiring only. Therefore, please note that there will have some difference
between the connection diagram and actual installation status of CT,VT and safety devices such as fuse, etc.
19
CBV, CUB Series VOLTAGE RELAY
Type, rating and specification
Type name CBV2A01D1 CBV3A01D1 CBV4A01D1 CUB1A01D1
CBV Voltage 57120V 57120V 57120V 57120V
CUB Rating Zero-phase voltage 110V/190V 110V/190V
Frequency 50Hz or 60Hz
27 3 phases, 27 1 phase, 59 1 phase, 27 3 phases, 27 3 phases,
Protective element
59 3 phases 64 Zero-phase 64 Zero-phase 2 59 3 phases, 47
Under Operation voltage LOCK10110V1V step
voltage Operation time INST0.110s 0.1s step
Over Operation voltage LOCK60155V1V step LOCK60155V1V step
voltage Operation time INST0.110s 0.1s step INST0.110s 0.1s step
Earth fault Operation voltage LOCK560V1V step
over voltage Operation time INST0.110s 0.1s step
Reverse Changeover Lock/Use LOCKUSE
phase Operation time 0.110s 0.1s step
Setting Open Operation voltage LOCK1050V1V step
phase Operation time 0.110s 0.1s step
Output contact configuration Refer to the external connection diagram/Auto reset for all contacts Default setting at ex-works
Operation indicator LED hold All LED self-hold Default setting at ex-works
VT primary 100999V1V step10009990V10V step10.0k99.9kV0.1kV step100k300kV1kV step
VT secondary 100/3110/3115/3120/3100110115120V
100999V1V step,10009990V10V step,
EVT primary
10.0k99.9kV0.1kV step,100k300kV1kV step
EVT tertiary 1001101151201003110311531203V
Line voltage, Line voltage3,
Real time measurement Line voltage3 Line voltage3
Zero-phase voltage Zero-phase voltage
Line voltage, Line voltage3,
Max.record Line voltage3 Line voltage3
Zero-phase voltage Zero-phase voltage
Display Line voltage, Line voltage3, Line voltage3,
Fault record (operation value) Line voltage3
Zero-phase voltage Zero-phase voltage Negative sequence voltage
Fault record (operation item) Record and indicate the operated elements.
Normal result:On the RUN LED (green) Status indication item No.400=No display.
Self-diagnosis
Abnormal result:Off the RUN LEDStatus indication item No.400=Display defects code
Forced operation Each output contact
Direct communication port Standard equipmentPC software for Direct communication: Option Not applicable
Communication
Remote communication port Option For CC-LINK Not applicable
Voltage circuit:Less than 1 VA, Zero-phase voltage circuit:Less than 0.15 VA
Burden (at rating) Auxiliary power supply circuit:at DC100V=Approx. 5W, at AC100V=Approx. 7VA,
at DC220V=Approx. 6W, at AC220V=Approx. 12VAIn case of installing communication card, add 2 VA.
Mass Net weight of relay unit:Approx. 2.3kg, Including case:Approx. 3.0kg
Sample of external connection diagram Fig.21 Fig.22 Fig.23 Fig.24

Please refer to the instruction manual regarding the details on this specification.

20
Characteristics
Items Condition Guaranteed performance
Under voltage element
Over voltage element Common condition1 Setting value5%
Earth fault over voltage element CBV
Operation value Reverse phase element Impress 3 phases negative sequence voltage Operates from about 1V or more CUB
Impress 3 phases negative sequence voltage
Setting value5%
Open phase element However, in case of applying single phase power source,
However, minimum permissible error is 1V
impress the voltage of setting value3
Under voltage element Operation value105% or less
Over voltage element
Operation value95% or more
Reset value Earth fault over voltage element Common condition1
Reverse phase element Reset from about 1V or more
Open phase element Operation value95% or more
Under voltage element Rated voltagesetting value70% Setting INST 40ms or less
50ms only for Over voltage element
Over voltage element 0Vsetting value120%
Setting 0.4s or lesssetting value25ms
Earth fault over voltage element 0Vsetting value150% Setting 0.5s or moresetting value5%
Operation time
Setting 0.4s or lesssetting value25ms
Reverse phase element 0V3 phases negative sequence voltage
Setting 0.5s or moresetting value5%
Do it by single phase power source Setting 0.4s or lesssetting value25ms
Open phase element
0V setting value3120% Setting 0.5s or moresetting value5%
Under voltage element Setting value70%Rated voltage
60ms or less CBV2, 3, 4A01D1
Over voltage element Setting value120%0V
200ms25ms CUB1A01D1
Earth fault over voltage element Setting value150%0V
Reset time
Reverse phase element 3 phases negative sequence voltage 0V
Do it by single phase power source. 200ms25ms
Open phase element
Setting value3120% 0V
1Common condition 1Rating Frequency2Ambient temperature203Auxiliary power supply: Rating voltage
2Please refer to the instruction manual regarding the details on this specification.

Precaution for application


1. Guarantee against interruption of AC power supply output abnormal result even after the built-in power failures.
When an uninterruptible AC power source is not available in your Therefore, the break contact is still closed in the aftermath of the
system for the auxiliary power supply, use the type B-T1 AC/DC power applying and will be opened after 50ms. If the auxiliary power
converter or commercially available uninterruptible power supply of the relay and the self-diagnosis output contact feed from a same
(UPS). In addition, possible duration of the power supply type B-T1 power source, the break contact will be closed temporarily after
AC/DC converter is confirmed as about 2 seconds in combination auxiliary power supply is turned on. In this case where the
with one MELPRO-D series relay. Therefore, in the case that the phenomenon stated in the above would conflict with your system
required duration of power supply after power source loss exceeds 2 requirement, it is recommended that the self-diagnosis output contact
seconds, please use a suitable commercial uninterruptible power should be connected via the time-delay timer.
supply. When power supply back up for the circuit breaker is 5. Grounding circuit
required, it is necessary to prepare the power supply independent Be sure to make a wiring to the earth terminal located on the back of
from the type B-T1 AC/DC converter. the relay according to the Class D earth wiring method (Grounding
2. Inrush current of power supply resistance should be less than 100 ohm).
Since inrush current (about 2ms duration) as below may flow into the 6. CC-Link communication circuit
relay when the power supply is turned on, please make a Please include the communication card into your purchasing order in
consideration on this regard for selection of power circuit breaker. case of the application of the communication facility as the card
Input voltage Inrush current Ip necessary for communication (CC-Link ) is option. In case of retrofit
existing relay with communication card, please inform the followings
DC110V Approx. 20A of existing relay. a:Type, b:Style number, c:Manufacturing year,
DC220V Approx. 55A d:Serial number, e:Date of stamp on the checking seal (The above
AC100V Approx. 25A mentioned items a.d. are indicated on the bottom right of front face
AC220V Approx. 65A of the relay and item e. is indicated on the upper of back side of the
relay.) The version number of CC-Link is 1.00.
3. Trip circuit 7. Improvement of reliability of protection system
Only the dedicated contacts can be used for the circuit breaker trip For the important facilities, multiplex system such as dual should be
circuit. Please keep in mind that the contacts for signaling can not be provided to improve reliability.
used for the trip circuit. (If used, the contact may burn). Also, connect 8. Effects of external surge
the pallet contact (52a) of the circuit breaker to the trip coil circuit in Some type of surge with a certain condition may inversely affect the
series. relay. If so, take it into account to install surge absorbers.
4. Self-diagnosis output circuit 9. Make a wiring between EVT a terminal and A-06 terminal of
The self-diagnosis output contact is so configured that the auxiliary relay and EVT f terminal and A-05 terminal of relay. Also, the
relay is energized ( break contactopened ) when normal result of grounding of EVT tertiary circuit has to be configured by the
self-diagnosis is received. This type of contact will allow the relay to connection betweenfterminal of EVT and earth terminal.

Precaution for using


1. When the product is shipped from the factory, each setting value is 4. The EVT tertiary voltage ratio should be set as output nominal
LOCK (for element with LOCK position) or minimum setting voltage between terminalaandfof EVT.
value(for element without LOCK position) Example: 190/3190V, 110/3110V
2. To set as [LOCK] position means to set the element out of use. 5. The UV test function will be used for single phase test for under
3. The setting of measuring transformer ratio is applied only for the voltage element. (UV test LED (yellow color) will turn on during
measuring indication converted to the primary side, and is not selecting UV TEST). UV TEST should be set as OFF in the
applied for protection element. operational condition.

Precaution for safety


Please refer to page2 and 3 regarding the safty information and request
when placing order.
21
Sample of external connection diagram

CBV
CUB + A01 B05
A B C Auxiliary Y Self diagnosis output
power supply B06
circuit A03
B07
X0
B08 Under voltage
B09 U
VT X1
A07 B10 For
B11 signaling
A08 X2
VAB B12 Over voltage
A09 B13 U
X3
B14
ED A10
B17
VBC X4
A11 B18
UOR U For trip
B19
VCA A12 X5
B20
Programmable output
Communication card
B01 DA Default setting at ex-works
(option) B02 DB
Serial communication bus
B03 DG
E A02
B04 SLD
ED

Fig.21CBV2A01D1Input line voltage

A + A01 B05
Auxiliary Y Self diagnosis output
B power supply B06
circuit A03
B07
C X0
B08 Earth fault over voltage
B09 U
EA X1
EVT B10
For
B11 Under voltage signaling
X2
U
B12
ED B13 Over voltage
A07 X3
U
B14
VAB
A08 B17
X4
B18 UOR
For trip
B19 UOR U
X5
a f B20
A05 Programmable output
Communication card

R B01 DA Default setting at ex-works


ED V0 A06 B02 DB
(option)

Serial communication bus


B03 DG
E A02
B04 SLD
ED

A resistance is necessary for the isolated neutral system.

Fig.22CBV3A01D1
The connection diagram shows concepts of the wiring only. Therefore, please note that there will have some difference
between the connection diagram and actual installation status of CT,VT and safety devices such as fuse, etc.
22
CBV
A + A01 B05 CUB
Auxiliary Y Self diagnosis output
B power supply B06
circuit A03
B07 Earth fault over voltage 1
C X0 U
B08
B09 Earth fault over voltage 2
EA X1 For
A07 U
EVT B10 signaling
B11
VAB A08 X2
B12 Under voltage
ED B13 U
A09
X3
VBC B14
A10
B17
X4
A11 B18 UOR
For trip
B19 UOR U
VCA A12 X5
B20
Programmable output
a f Default setting at ex-works
A05

Communication card
R B01 DA
ED V0 A06 B02 DB

(option)
Serial communication bus
B03 DG
E A02
B04 SLD
ED
A resistance is necessary for the isolated neutral system.

Fig.23CBV4A01D1

+ A01 B05
A B C Auxiliary Y Self diagnosis output
power supply B06
circuit A03
B07 Under voltage
X0 U
B08
B09 Over voltage
VT X1
A07 U
B10 For
B11 signaling
Reverse phase
A08 X2 RV
VAB B12
A09 B13 Open phase
X3 UNSV
B14
A10
B17
VBC X4
A11 B18 UOR UOR
For trip
B19 RVOR UNSV
VCA A12 X5
B20
Programmable output
Default setting at ex-works

E A02

ED

Fig.24CUB1A01D1
The connection diagram shows concepts of the wiring only. Therefore, please note that there will have some difference
between the connection diagram and actual installation status of CT,VT and safety devices such as fuse, etc.
23
CFP Series FEEDER PROTECTION RELAY
CDG Series EARTH FAULT DIRECTIONAL RELAY
Type, rating and specification
Type name CFP1A01D1 CFP1A02D1 CDG1A01D1
Phase current 5A 5A -
Zero-phase current 2A 2A 1A
Rating
Zero-phase voltage 110/190V 110/190V 100208V
Frequency 50Hz or 60Hz
Protective element 51/50 2 phases, 67G 51/50 2 phases, 67G 67G
CFP
Combined Zero-phase current Commercially available ZCTConformity with JEC-1201200/1.5mA -
CDG instrument
transformer Zero-phase voltage Commercially available EVTConformity with JEC-1201 Commercially available EVT(Conformity with JEC1201)
Operation current LOCK112A0.1A step -
Operation time multiplier 0.250.550 0.5 step -
Time-
delayed Operation time Normal inverse time-delayed3 kinds, Very inverse time-delayed2 kinds,
Extremely inverse time-delayed3 kinds, -
characteristics
Long inverse time-delayed3 kinds, Definite time-delayed1 kind
Reset time characteristics Normal inverse time-delayed 1 kind, Definite time-delayed 2 kind -
Operation current LOCK280A1A step -
Instantaneous
Operation time INST0.10.5s 0.1s step -
I0 operation current 10mAZCT secondary current 0.5mA step 0100mAZCT secondary current
5mA step 0.051.0A0.05A step
V0 operation voltage LOCK560VEVT tertiary 1V step LOCK560V1S step
Operation time INST0.110s0.1s step 0.110s0.1s step
Lead 090 5 step Lead 030 5 step
V0
V0
I0 Lead Lag I0
Maximum
Earth fault Maximum
sensitive angle
directional sensitive angle
Maximum
sensitive angle
Operation area Operation area
Setting 15
Non-operation area
15

Output contact configuration Refer to the external connection diagram/Auto reset for all contacts Default setting at ex-works
Operation indicator LED hold All LED self-hold Default setting at ex-works
15101212.515202530405060758010012012515020025030040050060075080010001200
CT primaryPhase current)
1250150020002500300040005000600075008000[A]Applicable 1 A rating product only.
100999V1V step,
100999V1V step,10009990V10V step, 10009990V10V step,
EVT primary
10.0k99.9kV0.1kV step, 100k300kV1kV step 10.0k99.9kV0.1kV step,
100k300kV1kV step
1001101151201003
EVT tertiary 1001101151201003110311531203V
100311531203V
ZCT error correction on/off OFFON -
When the actual measured transforming ratio is within range of 200/
ZCT error adjustment -
1.54.1mA, the deviation from the ZCT nominal transforming ratio 200/1.5mA can be corrected.
Real time measurement Phase current2, Zero-phase current, Zero-phase voltage, Characteristic angle Zero phase current, Zero phase voltage, Phase
Max.record Phase current2, Zero-phase current, Zero-phase voltage Zero phase current, Zero phase voltage
Fault record (operation value) Phase current2, Zero-phase current, Zero-phase voltage, Characteristic angle Zero phase current, Zero phase voltage, Phase
Fault record (operation item) Record and indicate the operated elements
Display
010(The value 0 indicates the status of input current reaching the setting value or more and
Elapse of time-delayed timer -
the value 110 indicate the elapse time up to operating of the time delayed element.)
Normal result:On the RUN LED (green) Status indication item No.400=No display.
Self-diagnosis
Abnormal result:Off the RUN LEDStatus indication item No.400=Display defects code
Forced operation Each output contact
Direct communication port Standard equipmentPC software for Direct communication:Option Not applicable
Communication
Remote communication port Option For CC-LINK Not applicable
Phase current circuitLess than 0.5VA, Zero-phase current circuitLess than 10,
Zero-phase voltage circuitLess than 0.15VA,
Burden (at rating)
Auxiliary power supply circuitat DC100V=Approx. 5W, at AC100V=Approx. 7VA, at DC220V=Approx. 6W,
at AC220V=Approx. 12VAIn case of installing communication card, add 2 VA.
Mass Net weight of relay unit:Approx. 2.3kg, Including case:Approx. 3.0kg
Sample of external connection diagram Fig.31 Fig.3-2,3-3
The rated current 1 A product can be made based on the 5A rating product.
Remarks The setting value of time delayed element and instantaneous element of -
1A product is calculated by performing a multiplication 1/5 of above mentioned value.

Please refer to the instruction manual regarding the details on this specification.

24
Characteristics
Items Condition Guaranteed performance
Setting 1.02.0A for 5A rating productSetting value 10%
Phase fault time-
Setting 0.20.4A for 1A rating productSetting value 10%
delayed element Common condition
For setting of other rangeSetting value 5%
Phase fault instantaneous element Setting value 10%
Zero-phase Setting: Zero phase voltage=minimum
Setting 1.0 or 1.5mA: Setting value10 CFP
current Input: Zero phase voltage=Rating voltage30%, CDG
(CFP1-A01/A02D1) For setting of other rangeSetting value 5%
Phase=Maximum sensitive angle
directional element

Operation Zero-phase Input: Zero phase voltage=rating voltage Setting 0.05A: Setting value 10%
value current
Phase: Maximum sensitive angle For setting other range: Setting value 5%
(CDG1-A01D1)
Earth fault

Zero-phase Setting: Zero phase current=minimum


voltage Input: Zero phase voltage=Setting valve1000%, Setting value 5%
(CFP1-A01/A02D1) Phase=Maximum sensitive angle
Zero-phase Input: Setting value200%
voltage Setting value 5%
Phase: Maximum sensitive angle
(CDG1-A01D1)
Setting 1.02.0A for 5A rating product
Operation value90% or more
Phase fault time- Setting 0.20.4A for 1A rating product
delayed element Common condition Operation value90% or more
For setting of other range
Operation value95% or more
Phase fault instantaneous element Operation value95% or more
Zero-phase Setting: Zero phase voltage=minimum
current Input: Zero phase voltage=Rating voltage30%, Operation value90% or more
Reset (CFP1-A01/A02D1)
value Phase=Maximum sensitive angle
directional element

Zero-phase Input: Zero phase voltage=rating voltage Setting 0.05A: Operation value90% or more
current
Phase: Maximum sensitive angle For setting other range: Operation value95% or more
(CDG1-A01D1)
Earth fault

Zero-phase Setting: Zero phase current=minimum


voltage Input: Zero phase voltage=Setting valve1000%, Operation value90% or more
(CFP1-A01/A02D1) Phase=Maximum sensitive angle
Zero-phase
Input: Setting value200%
voltage Operation value95% or more
(CDG1-A01D1) Phase: Maximum sensitive angle

Operation setting value: Minimum Refer to fig.1-1.2


Phase fault time-
Operation time multiplier: 10 Timing accuracy for I3Current setting value,
delayed element
Input:0Operation setting value300,500,1000% 3.5% of reference at actual pick up
Phase fault Operation setting value:Minimum value Setting value25ms
instantaneous element Input:0200% of setting value In case of INST setting 40ms or less
Setting: Zero phase current, voltage=minimum
Earth fault INST Setting 80ms or less
Operation Input: Zero phase current=0Setting value1000%,
directional element 0.10.4s Setting: Setting value25ms
time Zero phase voltage=0Rating voltage30%
(CFP1-A01/A02D1) 0.51.0s Setting: Setting value5%
Phase=Maximum sensitive angle
Input: Zero phase current and voltage to be changed
Earth fault quickly at the same time.
0.10.4s setting: Setting value25ms
Directional element Zero phase current: 0ASetting value300%
0.5s or more setting: Setting value5%
(CDG1-A01D1) Zero phase voltage: 0VRating voltage
Phase: Maximum sensitive angle
Phase fault time-delayed element
300% of setting value0A Refer to COC series table 1-1
Phase fault instantaneous element
Setting: Zero phase current, voltage=minimum
Earth fault
Input: Zero phase current=Setting value1000%0,
directional element 200ms25ms
Reset (CFP1-A01/A02D1) Zero phase voltage=Rating voltage30%0
time Phase=Maximum sensitive angle
Input: Zero phase current and voltage to be changed
Earth fault quickly at the same time.
Directional element Zero phase current: Setting value300%0A 200ms25ms
(CDG1-A01D1) Zero phase voltage: Rating voltage0V
Phase: Maximum sensitive angle
17. Type CDG1 is applicable for earth fault directional relay in the resistance grounded neutral system.
Refer to the Fig 3-2 and Fig. 3-3 on the combination with the Overcurrent relay.
Common condition 1Rating Frequency2Ambient temperature203Auxiliary power supplyRating voltage

25
Characteristics
Items Condition Guaranteed performance
Time-delayed operation value: Minimum
Overshoot Phase fault time- Operation time multiplier: 10
No-operation limit time/Operation time=90% or more
characteristic delayed element Operation characteristic: All characteristics
Input current:0ASetting value1000%
Earth fault Setting: Zero phase current, voltage=minimum
CFP
CDG directional element Input: Zero phase current=Setting value1000%, Maximum sensitive angle5
Phase (CFP1-A01/A02D1) Zero phase voltage=Rating voltage30%
characteristic Operation time: Minimum
Earth fault
Directional element Input: Zero phase current=Setting value1000% Setting value5
(CDG1-A01D1) Zero phase voltage=30V
17. Type CDG1 is applicable for earth fault directional relay in the resistance grounded neutral system.
Refer to the Fig 3-2 and Fig. 3-3 on the combination with the Overcurrent relay.
Common condition 1Rating Frequency2Ambient temperature203Auxiliary power supplyRating voltage

26
Precaution for application
1. Guarantee against interruption of AC power supply necessary for communication (CC-Link) is option. In case of retrofit
When an uninterruptible AC power source is not available in your existing relay with communication card, please inform the followings
system for the auxiliary power supply, use the type B-T1 AC/DC of existing relay. a:Type, b:Style number, c:Manufacturing year, d:
converter or commercially available uninterruptible power supply Serial number, e:Date of stamp on the checking seal (The above
(UPS). In addition, possible duration of the power supply type B-T1 mentioned items a.d. are indicated on the bottom right of front face
AC/DC converter is confirmed as about 2 seconds in combination of the relay and item e. is indicated on the upper of back side of the
with one MELPRO-D series relay. Therefore, in the case that the relay.) The version number of CC-Link is 1.00. CFP
required duration of power supply after power source loss exceeds 2 7. Improvement of reliability of protection system CDG
seconds, please use a suitable commercial uninterruptible power For the important facilities, multiplex system such as dual should be
supply. When power supply back up for the circuit breaker is provided to improve reliability.
required, it is necessary to prepare the power supply independent 8. Effects of external surge
from the type B-T1 AC/DC converter. Some type of surge with a certain condition may inversely affect the
2. Inrush current of power supply relay. If so, take it into account to install surge absorbers.
Since inrush current (about 2ms duration) as below may flow into the 9. Make a wiring between EVT a terminal and A-06 terminal of
relay when the power supply is turned on, please make a relay and EVT f terminal and A-05 terminal of relay. Also, the
consideration on this regard for selection of power circuit breaker. grounding of EVT tertiary circuit has to be configured by the
Input voltage Inrush current Ip connection betweenfterminal of EVT and earth terminal.
DC110V Approx. 20A 10. The test terminal ktand ltof ZCT should be no wiring in the
DC220V Approx. 55A operational condition of relay as the test terminal may be allowed to
AC100V Approx. 25A use only for the artificial fault current injection test. (Relay will not
AC220V Approx. 65A operate with these terminals short-circuited.)
11. To prevent the influence from noise or surge, a shielded 2 cores (size
3. Trip circuit is 0.751mm2) cable should be used for the connection between ZCT
Only the dedicated contacts can be used for the circuit breaker trip or EVT and relay, and shield wire should be connected to the earth
circuit. Please keep in mind that the contacts for signaling can not be terminal of the relay or the earth terminal located inside of the
used for the trip circuit. (If used, the contact may burn). Also, connect switchboard. (Grounding resistance should be less than 100 ohm).
the pallet contact (52a) of the circuit breaker to the trip coil circuit in Further more, the go and return burden of the cable should be less
series. than 5 ohms which is almost equal to 100m distance in case of core
4. Self-diagnosis output circuit size 0.75mm2.
The self-diagnosis output contact is so configured that the auxiliary 12. The power cable should be applied for the primary conductor of
relay is energized ( break contactopened ) when normal result of ZCT. The earth of shield wire of cables should be done according to
self-diagnosis is received. This type of contact will allow the relay to the regulation.
output abnormal result even after the built-in power failures. 13. The wiring between ZCT, EVT and relay should be according to the
Therefore, the break contact is still closed in the aftermath of the connection diagram of each relay with a precaution on the polarity.
power applying and will be opened after 50ms. If the auxiliary power 14. A commercially available ZCT conformity with JEC1201 (type BZ in
of the relay and the self-diagnosis output contact feed from a same case of MITSUBISHI ELECTRIC CORPORATION) may be applicable
power source, the break contact will be closed temporarily after for the type CFP1-A01D1 and CFP1-A02D1.
auxiliary power supply is turned on. In this case where the 15. No wiring to the terminal concerning to the elements without use
phenomenon stated in the above would conflict with your system for protection is acceptable. Also, regarding the setting of protection
requirement, it is recommended that the self-diagnosis output contact elements without use, to set the LOCK position is recommended.
should be connected via the time-delay timer. Please note that the setting LOCK of 67G element means the loss of
5. Grounding circuit all function of 67G which includes the 51G element, 64 element and
Be sure to make a wiring to the earth terminal located on the back of fault direction element.
the relay according to the Class D earth wiring method (Grounding 16. Only one number of ZCT can be connected to one number of the
resistance should be less than 100 ohm). type CFP1. Correct operation of the relay can not be guaranteed
6. CC-Link communication circuit against two or more numbers of ZCT to connect to one number of
Please include the communication card into your purchasing order in the type CFP1.
case of the application of the communication facility as the card

Precaution for using


1. When the product is shipped from the factory, each setting value is 5. The UV test function will be used for single phase test for under
LOCK (for element with LOCK position) or minimum setting voltage element. (UV test LED (yellow color) will turn on during
value(for element without LOCK position) selecting UV TEST). UV TEST should be set as OFF in the
2. To set as [LOCK] position means to set the element out of use. operational condition.
3. The setting of measuring transformer ratio is applied only for the 6. The function of the ZCT error correction installed in the relay is
measuring indication converted to the primary side, and is not applied for the purpose of correcting ZCT transformation error, so
applied for protection element. that improving the composite characteristics is achieved. The ZCT
4. The EVT tertiary voltage ratio should be set as output nominal error correction range is 200mA/1.5mA4.1mA(0+2.6mA) for the
voltage between terminal a and f of EVT. Example: 190/3 nominal transformation ratio 200mA/1.5mA specified with JEC-1201.
190V, 110/3110V

Precaution for safety


Please refer to page2 and 3 regarding the safty information and request
when placing order.

27
Sample of external connection diagram

A + A01 B05
B Auxiliary Y Self diagnosis output
power supply B06
C circuit A03
B07
CFP X0
CDG EA A09 B08 Earth fault directional
CB
EVT B09 I
IA A10 X1
B10
For
A11 B11 Phase faultInstantaneous signaling
X2 I
CT IC A12 B12
B13 Phase faultTime-delayed
X3 I
k ED+ A07 B14
a f K
I0 B17
R ZCT X4
A08 IOR
(200/1.5mA) L B18
r IOR I For trip
B19
ED + A05 X5
B20
ED V0 A06
Programmable output
Default setting at ex-works

Communication card
B01 DA

(option)
B02 DB
Serial communication bus
B03 DG
E A02
B04 SLD
ED

A resistance is necessary for the isolated neutral system.

Fig.31CFP1A01D1CFP1A02D1

A + A01 B05
B Auxiliary Y Self diagnosis output
power supply B06
C circuit A03
B07
X0
EA A07 B08
CB
EVT B09
I0 A08 X1
B10 Earth fault directional For
B11 I signaling
X2
B12
B13
COC3-A01D1 X3
CT
B14
B17
X4
B18 I For trip
B19
ED + A05 X5
B20
ED V0 A06
Programmable output
Default setting at ex-works

E A02

ED

Fig.32CDG1A01D1
The connection diagram shows concepts of the wiring only. Therefore, please note that there will have some difference
between the connection diagram and actual installation status of CT,VT and safety devices such as fuse, etc.
28
A + A01 B05
B Auxiliary Y Self diagnosis output
power supply B06
C circuit A03
B07
X0 CFP
EA CB B08 CDG
EVT B09
X1
B10 Earth fault directional For
B11 I signaling
X2
CT B12
COC3-A01D1
B13
X3
ED A07 B14
I0 B17
A08 X4
B18 I For trip
B19
ED + A05 X5
B20
ED V0 A06
Programmable output
Default setting at ex-works

E A02

ED

Fig.33CDG1A01D1

The connection diagram shows concepts of the wiring only. Therefore, please note that there will have some difference
between the connection diagram and actual installation status of CT,VT and safety devices such as fuse, etc.
29
CAC Series BIASED DIFFERENTIAL RELAY FOR TRANSFORMER PROTECTION
Type, rating and specification
Type name CAC1A01D2
Phase current 5AAllowable continuous current: 8.7A
Rating
Frequency 50Hz or 60Hz
Protective element 87Tfor 2 windings transformer
Tr primary side CT matching tap IT1 2.212.5A0.1A step
Tr secondary side CT matching tap IT2 2.212.5A0.1A step
Operation Current ITLOCK203040%
Bias 203040%
Setting
2nd harmonic blocking 1025%5% step
Differential overcurrent multiplier IT512 times 1time step
CAC Output contact configuration Refer to the external connection diagram/Auto reset for all contacts Default setting at ex-works
Operation indicator LED hold All LED self-hold Default setting at ex-works
Real time measurement Restraining current, Differential current, Percentage of 2nd harmonic current content
Max.record Restraining current, Differential current
Fault record (operation value) Restraining current, Differential current, Percentage of 2nd harmonic current content
Display
Fault record (operation item) Record and indicate the operated elements.
Normal result:On the RUN LEDgreenStatus indication item No.400=No display.
Self-diagnosis
Abnormal result:Off the RUN LEDStatus indication item No.400=Display defects code
Forced operation Each output contact
Direct communication port Standard equipmentPC software for Direct communication:Option
Communication
Remote communication port Option For CC-LINK
Phase current circuit:Less than 0.5VA/phase
Burden (at rating) Auxiliary power supply circuit:at DC100V=Approx. 7W, at AC100V=Approx. 25VA, at DC220V=Approx. 9W,
at AC220V=Approx. 30VAIn case of installing communication card, add 2 VA.
Mass Net weight of relay unit:Approx. 3.8kg, Including case:Approx. 5.0kg
Sample of external connection diagram Fig.415
Remarks Possible to make 1A rating

Characteristics
Items Condition Guaranteed performance
Operation Biased differential element Iop=ITOperation current%
Within Iop5%
current Differential overcurrent element Iop=ITDifferential overcurrent
Reset Biased differential element Iop=ITOperation current%
95% or more of operations current
value Differential overcurrent element Iop=ITDifferential overcurrent
Operation Biased differential element 0[A]Iop300% 50ms or less
time Differential overcurrent element 0[A]Iop300% 40ms or less
Reset Biased differential element Iop300%0[A]
within 20025ms
time Differential overcurrent element Iop300%0[A]
Matching tapIT1 = IT2 = IT
At minimum matching tap setting I1 I2 =20 setting: 1525%
Biased differential characteristic I2 = IT200% =30 setting: 2535%
I1I2 CT CT =40 setting: 3545%
Bias Tr
Whichever is greater
Internal fault side
I1
Both lead and lag operation phase angle between I1 and I2 are shown below table.
Matching tapIT1 = IT2 = IT
Operating zone
Nominal bias ratio
Phase characteristic At minimum matching tap setting 20[%] 168.55
I1=I2= IT200% 30[%] 162.75
I2
Through fault side 40[%] 156.95
Matching tapIT1 = IT2 = IT
At minimum matching tap setting IAC=254330[%]setting:10%
IDC=80% of setting value 2 IAC=137188[%]setting:15%
IDC
If2 3
2nd harmonic blocking IDC=Half wave rectifier current =100 IAC=81119[%]setting:20%
If1
characteristic IAC=Sine wave current 2 IACIDC IAC=4777[%]setting:25%
2
Percentage of 2nd harmonic current content
In case of the method of harmonic superposing,
2nd harmonic blocking ratio: Setting value 10
If1 is equal to 300% of the matching tap value.

Please refer to the instruction manual regarding the details on this specification.

30
Precaution for application
1. Guarantee against interruption of AC power supply necessary for communication (CC-Link ) is option. In case of retrofit
When an uninterruptible AC power source is not available in your existing relay with communication card, please inform the followings
system for the auxiliary power supply, use the type B-T1 AC/DC of existing relay. a:Type, b:Style number, c:Manufacturing year,
converter or commercially available uninterruptible power supply d:Serial number, e:Date of stamp on the checking seal (The above
(UPS). In addition, possible duration of the power supply type B-T1 mentioned items a.d. are indicated on the bottom right of front face
AC/DC converter is confirmed as about 2 seconds in combination of the relay and item e. is indicated on the upper of back side of the
with one MELPRO-D series relay. Therefore, in the case that the relay.) The version number of CC-Link is 1.00.
required duration of power supply after power source loss exceeds 2 7. Improvement of reliability of protection system
seconds, please use a suitable commercial uninterruptible power For the important facilities, multiplex system such as dual should be
supply. When power supply back up for the circuit breaker is provided to improve reliability.
required, it is necessary to prepare the power supply independent 8. Effects of external surge
from the type B-T1 AC/DC converter. Some type of surge with a certain condition may inversely affect the CAC
2. Inrush current of power supply relay. If so, take it into account to install surge absorbers.
Since inrush current (about 2ms duration) as below may flow into the 9. The external wiring should be done according to Connection diagram.
relay when the power supply is turned on, please make a There is some possibility to detect differential current in case of
consideration on this regard for selection of power circuit breaker. wrong wiring.
Input voltage Inrush current Ip 10. The wiring of CT circuit is depended on the connection of the
DC110V Approx. 20A transformer winding (yd1, yd11, dy1, dy11, etc). Therefore, special
DC220V Approx. 55A attention on this regard is requested.
AC100V Approx. 25A 11. Regarding the CT sircuits on the transformer primary side, the
AC220V Approx. 65A incoming wiring should be connected to lower number of terminals
and the outgoing wiring of them should be connected to higher
3. Trip circuit number of terminals. Also, regarding the CT circuits on the
Only the dedicated contacts can be used for the circuit breaker trip transformer secondary side, the incoming wiring should be connected
circuit. Please keep in mind that the contacts for signaling can not be to higher number of terminals and outgoing wiring of them should be
used for the trip circuit. (If used, the contact may burn). Also, connect connected to lower number of terminals.
the pallet contact (52a) of the circuit breaker to the trip coil circuit in 12. When the differential current check (defect code 0017) is detected,
series. careful checking of wiring connection and setting value are requested
4. Self-diagnosis output circuit as there are some possibilities to have some mistake of the wiring or
The self-diagnosis output contact is so configured that the auxiliary improper setting of matching tap.
relay is energized ( break contact opened) when normal result of 13. At the time of site testing or commissioning, please confirm if
self-diagnosis is received. This type of contact will allow the relay to external wiring of CT circuits is correct or not by using the CT
output abnormal result even after the built-in power failures. polarity check function(item number 905) of relay.
Therefore, the break contact is still closed in the aftermath of the 14. If the 2nd harmonic blocking elements (the digit number 7 to 9) are
power applying and will be opened after 50ms. If the auxiliary power set to ON for a contact arrangement, the contact will make when
of the relay and the self-diagnosis output contact feed from a same the 2nd harmonic blocking element operate. Therefore, set them to
power source, the break contact will be closed temporarily after OFF for the trip contact arrangement to prevent from incorrect
auxiliary power supply is turned on. In this case where the operation. (Example of ON setting: The CB of primary side of
phenomenon stated in the above would conflict with your system transformer is closed and then, trip contact will make by the
requirement, it is recommended that the self-diagnosis output contact operation of the 2nd harmonic blocking element. Finally, CB will be
should be connected via the time-delay timer. tripped.) Please note that in the default setting at the time of ex-work,
5. Grounding circuit the 2nd harmonic blocking elements are not set to ONfor contact
Be sure to make a wiring to the earth terminal located on the back of arrangement on the trip circuit.
the relay according to the Class D earth wiring method (Grounding 15. Another relays and load such as OCR or Aux-CT should not be
resistance should be less than 100 ohm). connected in the same CT secondary circuits of differential relay for
6. CC-Link communication circuit the primary and secondary of transformer because differential
Please include the communication card into your purchasing order in current will be caused due to the unbalance of the burden between
case of the application of the communication facility as the card both circuits.

Precaution for using


1. When the product is shipped from the factory, each setting value is out characteristic test. Because this relay has continuously monitoring
LOCK (for element with LOCK position) or minimum setting function of differential current, so that the monitoring abnormality
value(for element without LOCK position) (0017) will occur when current applied on. The DIF test LED (yellow)
2. To set as [LOCK] position means to set the element out of use. will become on when setting. And do not forget to set the DIF test
3. The setting item ofDIF test (515)should be setONwhen carry (515)OFFafter finishing the characteristic test.

Precaution for safety


Please refer to page2 and 3 regarding the safty information and request
when placing order.

31
Sample of external connection diagram

A B C + A01 B05
IA IB IC Auxiliary Y Self diagnosis output
power supply B06
circuit A03
B07 Biased differential
k IA A17 X0
B08 Differential overcurrent A phase
IB
A18 B09 Biased differential
IC X1
K A19 Differential overcurrent B phase
B10 For
CT1 B11
CAC A20 Biased differential signaling
X2
L r A21 B12 Differential overcurrent C phase
B13 2f blocking
Transformer A22 X3
B14 A,B,C phase
Dd0 ED
B17
L r X4 Biased differential
CT2 B18 Differential overcurrent
IA A11 A phase OR B phase OR For trip
K B19
X5 C phase
A12
B20
IB A13
Programmable output
A14 Default setting at ex-works

Communication card
B01 DA
IC A15
B02 DB
k
A16 (option) Serial communication bus
B03 DG
E A02
B04 SLD

ED ED

Fig.41CAC1A01D2TransformerDd0

A B C + A01 B05
IA IB IC Auxiliary Y Self diagnosis output
power supply B06
circuit A03
B07 Biased differential
k IAIC A17 X0
B08 Differential overcurrent A phase
IBIA
A18 B09 Biased differential
ICIB X1
r A19 Differential overcurrent B phase
K B10 For
A20 B11 signaling
CT1 Biased differential
X2
L A21 B12 Differential overcurrent C phase
B13 2f blocking
Transformer A22 X3
Y B14 A,B,C phase
Yd1 ED
B17
r X4 Biased differential
L
CT2 B18 Differential overcurrent For trip
IAIC A11 A phase OR B phase OR
K B19
X5 C phase
A12
B20
IBIA A13
Programmable output
A14 Default setting at ex-works
Communication card

B01 DA
ICIB A15
B02 DB
(option)

k
A16 Serial communication bus
B03 DG
E A02
B04 SLD

ED ED

Fig.42CAC1A01D2Transformer YYd1
The connection diagram shows concepts of the wiring only. Therefore, please note that there will have some difference
between the connection diagram and actual installation status of CT,VT and safety devices such as fuse, etc.
32
A B C + A01 B05
IA IB IC Auxiliary Y Self diagnosis output
power supply B06
circuit A03
B07 Biased differential
k IAIB A17 X0
B08 Differential overcurrent A phase
IBIC
A18 B09 Biased differential
ICIA X1
A19 Differential overcurrent B phase
K r B10
For
A20 B11 Biased differential signaling CAC
CT1 X2
L A21 Differential overcurrent C phase
B12
B13 2f blocking
Transformer A22 X3
Y B14 A,B,C phase
Yd11 ED
B17
r X4 Biased differential
L
CT2 B18 Differential overcurrent
IAIB A11 For trip
K B19 A phase OR B phase OR
X5 C phase
A12
B20
IBIC A13
Programmable output
A14 Default setting at ex-works

Communication card
B01 DA
ICIA A15
B02 DB

(option)
k
A16 Serial communication bus
B03 DG
E A02
B04 SLD

ED ED

Fig.43CAC1A01D2Transformer YYd11

A B C + A01 B05
Auxiliary Y Self diagnosis output
power supply B06
circuit A03
B07 Biased differential
k IAIB A17 X0
B08 Differential overcurrent A phase
IBIC
K A18 B09 Biased differential
ICIA X1
A19 Differential overcurrent B phase
B10 For
CT1 signaling
L A20 B11 Biased differential
X2
r A21 B12 Differential overcurrent C phase
B13 2f blocking
Transformer A22 X3
Y B14 A,B,C phase
Dy1 ED
B17
X4 Biased differential
L B18 Differential overcurrent For trip
r A11 A phase OR B phase OR
CT2 B19
X5 C phase
K A12
B20
A13
IAIB Programmable output
A14 Default setting at ex-works
Communication card

IBIC
B01 DA
A15
B02 DB
(option)

ICIA A16 Serial communication bus


IA IB IC B03 DG
k
E A02
B04 SLD

ED ED

Fig.44CAC1A01D2TransformerYDy1
The connection diagram shows concepts of the wiring only. Therefore, please note that there will have some difference
between the connection diagram and actual installation status of CT,VT and safety devices such as fuse, etc.
33
A B C + A01 B05
Auxiliary Y Self diagnosis output
power supply B06
circuit A03
B07 Biased differential
k IAIC A17 X0
B08 Differential overcurrent A phase
IBIA
K A18 B09 Biased differential
ICIB X1
A19 Differential overcurrent B phase
B10 For
CT1
CAC L A20 B11 Biased differential signaling
X2
r A21 B12 Differential overcurrent C phase
B13 2f blocking
Transformer A22 X3
Y B14 A,B,C phase
Dy11 ED
B17
L X4 Biased differential
CT2
K B18 Differential overcurrent
r IAIC A11 For trip
B19 A phase OR B phase OR
X5 C phase
IBIA A12
B20
ICIB A13
Programmable output
k Default setting at ex-works
A14

Communication card
B01 DA
A15
B02 DB
A16 (option) Serial communication bus
IA IB IC B03 DG
E A02
B04 SLD

ED ED

Fig.45CAC1A01D2TransformerYDy11

The connection diagram shows concepts of the wiring only. Therefore, please note that there will have some difference
between the connection diagram and actual installation status of CT,VT and safety devices such as fuse, etc.
34
CMP Series MOTOR PROTECTION RELAY
Type, rating and specification
Type name CMP1A01D1 CMP1A01D2
Phase current 5A
Zero-phase current 2A
Zero-phase voltage 100208V
DC110V (Permissible variable range 77143V) or
Rating

DC24V(Permissible variable range DC19.2V31.2V)


Photo coupler input voltage Input voltage 24V is applicable only for the case that auxiliary

D2 type only power supply voltage is 24V.
In any other cases, only DC110V is applicable as for photo
coupler input voltage.
Frequency 50Hz or 60Hz
Protective element 50/51 2 phases , 49, 46, 37, 66, 67G
Combined Zero-phase current Commercially available ZCT Conformity with JEC-1201200/1.5mA
instrument
transformer Zero-phase voltage Commercially available EVT Conformity with JEC-1201
Motor rated currentIM 25A 0.1A step
Overcurrent Operation current LOCK10100A 1A step
instantaneous Operation time INST0.11.0s 0.1s step
CMP
Operation current LOCKIM130300% 10% step
Operation timeKoct 45681012162024324048648096112128160200240
Overcurrent Koct KoctOperation time setting
time-delayed Operation time Toct3s
I IPhase current
unit: multiple to IM
characteristics
equation
The selected Koct valve is equal to the operating time of time-delayed element in case of I3.
Negative Operation current LOCKIM0.58 times 0.5 times step
sequence
overcurrent Operation time 0.110s
0.1s step
Operation current LOCKIM105125% 5% step
Operation timeKTH 812162024324048648096112128160200240
Operation time characteristics for HOT KTHOperation time settingKNegative-sequence heat multiplying factor
I12KI22 IP12KIP22
I1Positive sequence current of present inputunit: multiple to IM
TTH8.49KTHloges
I12KI22 1
Operation time I2Negative sequence current of present inputunit: multiple to IM
characteristics IP1Positive sequence current before overloadunit: multiple to IM
Overload equation IP2Negative sequence current before overloadunit: multiple to IM
Operation time for COLD characteristics, in the above equation, becomes equal to case conditioned as follows :IP12KIP22 0
Selected value of KTH, when input is provided so as to meet the conditions of I12KI2232 and IP12KIP220,
becomes equal to the time (sec) that will be taken until operation.
Setting

Negative-sequence heat
110
1 step
multiplying factorK
Changeover characteristic 0
COLD 1 HOT
Operation current LOCK1.04.0A 0.1A step
Undercurrent
Operation time 1600s 1s step
Limit the Number of start-up LOCK15 1 step
number of Start-up time 2120s 1s step
start-up times Countdown rate 2250s/h0.5s/h step
Io Operation current 110mA ZCT secondary current 0.5mA step
Earth fault Vo Operation voltage LOCK560V 1V step
directional Operation time INST0.110s 0.1s step
Maximum sensitive angle Lead 0905 step
Output contact configuration Refer to the external connection diagram/Auto reset for all contacts
Default setting at ex-works
Operation indicator LED hold All LED self-hold
Default setting at ex-works
15101212.5152025304050607580100120125150200250300400500600750800100012001250
CT primaryPhase current
150020002500300040005000600075008000[A]Applicable only 1 A
100999V 1V step ,10009990V 10V step ,
EVT primary
10.0k99.9kV 0.1kV step ,100k300kV 1kV step
EVT tertiary 1001101151201003110311531203V
ZCT error correction on/off OFFON
When the actual measured transforming ratio is within range of 200/1.54.1mA,
ZCT error adjustment
the deviation from the ZCT nominal transforming ratio 200/1.5mA can be corrected.
Real time measurement Phase current, Zero-phase current, Zero-phase voltage, Characteristic angle, Negative sequence current
Max.record Phase current, Zero-phase current, Zero-phase voltage
Display

Fault recordoperation value Phase current, Zero-phase current, Zero-phase voltage, Characteristic angle, Negative sequence current
Fault recordoperation item Record and indicate the operated elements.
Normal result:On the RUN LED green Status indication item No.400=No display.
Self-diagnosis
Abnormal result:Off the RUN LEDStatus indication item No.400=Display defects code
Forced operation Each output contact
Direct communication port Standard equipment PC software for Direct communication:Option
Communication
Remote communication port OptionFor CC-LINK
Phase current circuitLess than 0.5VA, Zero-phase current circuitLess than 10, Zero-phase voltage circuitLess than 0.15VA
Burden (at rating) Auxiliary power supply circuitat DC100V=Approx. 4W, at AC100V=Approx. 8VA, at DC220V=Approx. 5W,
at AC220V=Approx. 15VA In case of installing communication card, add 2 VA.
Net weight of relay unit:Approx. 2.1kg D1 type , Including case:Approx. 2.8kg D1 type ,
Mass
Net weight of relay unitApprox. 3.1kg D2 type , Including case:Approx. 4.3kg D2 type
Sample of external connection diagram Fig.51,2
The rated current 1A product can be made based on the 5A rating product. The setting value of current elements
Remarks on 1A product is calculated by performing a multiplication 1/5 of above mentioned value. The DI input facility is
available for CMP1-A01D2, CMP1-A02D2 and not available for type CMP1-A01D1 and CMP2-A01D1.

Please refer to the instruction manual regarding the details on this specification.
35
Type name CMP1A02D1 CMP2A02D2
Phase current 5A
Zero-phase current 5A
DC110V (Permissible variable range 77143V) or
DC24V(Permissible variable range DC19.2V31.2V)
Rating

Photo coupler input voltage Input voltage 24V is applicable only for the case that auxiliary

D2 type only power supply voltage is 24V.
In any other cases, only DC110V is applicable as for photo
coupler input voltage.
Frequency 50Hz or 60Hz
Protective element 50/51 3 phases , 49, 46, 37, 66, 51G
Motor rated currentIM 25A 0.1A step
Overcurrent Operation current LOCK10100A 1A step
instantaneous Operation time INST0.11.0s 0.1s step
Operation current LOCKIM130300% 10% step
Operation timeKoct 45681012162024324048648096112128160200240
CMP
Overcurrent Koct KoctOperation time setting
time-delayed Operation time Toct3s
I IPhase current
unit: multiple to IM
(1) characteristics
equation
The selected Koct valve is equal to the operating time of time-delayed element in case of I3.
Overcurrent Operation current LOCKIM115450% 5% step
time-delayed
(2) Operation time 0.55.0s
0.5s step
Negative Operation current LOCKIM0.58 times 0.5 times step
sequence
overcurrent Operation time 0.110s
0.1s step
Operation current LOCKIM105125% 5% step
Operation timeKTH 812162024324048648096112128160200240
Operation time characteristics for HOT KTHOperation time settingKNegative-sequence heat multiplying factor
I12KI22 IP12KIP22
I1Positive sequence current of present inputunit: multiple to IM
TTH8.49KTHloges
Setting

I12KI22 1
Operation time I2Negative sequence current of present inputunit: multiple to IM
characteristics IP1Positive sequence current before overloadunit: multiple to IM
Overload equation IP2Negative sequence current before overloadunit: multiple to IM
Operation time for COLD characteristics, in the above equation, becomes equal to case conditioned asIP12KIP220
Selected value of KTH, when input is provided so as to meet the conditions of I12KI2232 and IP12KIP220,
becomes equal to the time (sec) that will be taken until operation.
Negative-sequence heat
multiplying factorK 110
1 step

Changeover characteristic 0
COLD 1 HOT
Operation current LOCK1.04.0A 0.1A step
Undercurrent
Operation time 1600s 1s step
Limit the Number of start-up LOCK15 1 step
number of Start-up time 2120s 1s step
start-up times Countdown rate 2250s/h 0.5s/h step
Earth fault Operation current LOCK0.052.50A 0.05A step
overcurrent Operation time INST0.110s0.1s step
Output contact configuration Refer to the external connection diagram/Auto reset for all contacts Default setting at ex-works
Operation indicator LED hold All LED self-hold
Default setting at ex-works
1#5101212.5152025304050607580100120125150200250300400500600750800100012001250
CT primaryPhase current
150020002500300040005000600075008000[A]#Applicable only 1 A product
CT primaryZero-phase current Same as phase current
Real time measurement Phase current3, Zero-phase current, Negative sequence current
Max.record Phase current3, Zero-phase current
Display

Fault recordoperation value Phase current3, Zero-phase current, Negative sequence current
Fault recordoperation item Record and indicate the operated elements.
Normal result:On the RUN LED green Status indication item No.400=No display.
Self-diagnosis
Abnormal result:Off the RUN LEDStatus indication item No.400=Display defects code
Forced operation Each output contact
Direct communication port Standard equipment PC software for Direct communication:Option
Communication
Remote communication port OptionFor CC-LINK
Phase current circuitLess than 0.5VA, Zero-phase current circuitLess than 10, Zero-phase voltage circuitLess than 0.15VA
Burden (at rating) Auxiliary power supply circuitat DC100V=Approx. 4W, at AC100V=Approx. 8VA, at DC220V=Approx. 5W,
at AC220V=Approx. 15VAIn case of installing communication card, add 2 VA.
Net weight of relay unit:Approx. 2.1kg D1 type , Including case:Approx. 2.8kg D1 type ,
Mass
Net weight of relay unitApprox. 3.1kg D2 type , Including case:Approx. 4.3kg D2 type
Sample of external connection diagram Fig.53 Fig.54
The rated current 1A product can be made based on the 5A rating product. The setting value of current elements
Remarks on 1A product is calculated by performing a multiplication 1/5 of above mentioned value. The DI input facility is
available for CMP1-A01D2, CMP2-A02D2 and not available for type CMP1-A01D1 and CMP1-A02D1.

Please refer to the instruction manual regarding the details on this specification.

36
Characteristics
Items Condition Guaranteed performance
Overload element Positive sequence current
Overcurrent time-delayed element (1)
Overcurrent time-delayed element (2)
Common condition1
Overcurrent instantaneous element
Under current element
Negative sequence overcurrent element Negative sequence current
Operation Setting: Zero phase voltage=minimum
directional element

Zero-phase Setting value 5%


value Input: Zero phase voltage=Rating voltage30%,
CMP1-A01

current
Phase=Maximum sensitive angle
Earth fault

Setting: Zero phase current=minimum


Zero-phase
Input: Zero phase current=Setting value1000%,
voltage
Phase=Maximum sensitive angle
Earth fault overcurrent element
Common condition1
CMP1A02 CMP
Overload element
Overcurrent time-delayed element (1)
Overcurrent time-delayed element (2) Common condition1 Operation value95% or more
Overcurrent instantaneous element
Negative sequence overcurrent element
Setting: Zero phase voltage=minimum
directional element

Zero-phase
Input: Zero phase voltage=Rating voltage30%,
CMP1-A01

Reset current
value Phase=Maximum sensitive angle
Earth fault

Operation value90% or more


Setting: Zero phase current=minimum
Zero-phase
Input: Zero phase current=Setting value1000%,
voltage
Phase=Maximum sensitive angle
Earth fault overcurrent element
Operation value95% or more
CMP1A02 Common condition1
Under current element Operation value105% or less
Earth fault Setting: Zero phase current=minimum
Phase directional element Input: Zero phase current=Setting value1000%, Setting value 5
CMP1-A01 Zero phase voltage=Rating voltage30%
SettingOperation time setting KTH=8
Input 150%Error against normal 17 or less
Overload element Input: Positive sequence current=0A
Input 300%Error against normal 12 or less
150% and 300% of motor rated current
SettingOperation time setting Koct=4 Input 300%Error against normal 12 or less
Overcurrent time-
Input: Phase current=0A Input 500%Error against normal 7 or less
delayed element (1)
300%,500% and 1000% of motor rated current (IM) Input 1000%Error against normal 7 or less
Overcurrent time- Setting: minimum
Setting value 5
delayed element (2) Input: Phase current=0A300%
In case of INST setting40ms or less
Overcurrent Setting: minimum
0.10.4s settingSetting value 25ms
instantaneous element Input:0setting value200%
Operation 0.51.0s settingSetting value 5%
time Setting: maximum
Under current element Setting value 5%
Input:Setting value300%IM12%
Negative sequence Setting: minimum 0.10.4s settingSetting value 25ms
overcurrent element Input:Negative sequence current=0Setting value200% 0.51.0s settingSetting value 5%
Setting: Zero phase current=minimum
Earth fault In case of INST setting80ms or less
Input: Zero phase current=0Setting value1000%
directional element 0.10.4s settingSetting value 25ms
CMP1-A01 Zero phase voltage=0Rating voltage30%
0.510s settingSetting value 5%
Phase=Maximum sensitive angle
Earth fault In case of INST setting40ms or less
Setting: minimum
overcurrent element 0.10.4s settingSetting value 25ms
CMP1A02 Input: Zero phase current=0Setting value200%
0.510s settingSetting value 5%
1Common condition
1Rating Frequency2Ambient temperature203Auxiliary power supply: Rating voltage

37
Items Condition Guaranteed performance
HOT characteristic300% input is applied for 5
SettingOperation time settingKTH=8 minutes or more and then input is turned to zero.
Overload element
Input: Positive sequence current=Setting value300%0A 149.2s15%
COLD characteristic: 20025ms
Overcurrent time-delayed element (1)
Setting: minimum
Overcurrent time-delayed element (2)
Input: Setting value300%0A
Overcurrent instantaneous element
Setting: maximum
Reset Under current element
time Input: IM12%Setting value200%
Negative sequence Setting: minimum
overcurrent element Input: Negative sequence current=Setting value300%0A 20025ms
Setting: Zero-phase current, voltage=minimum
Earth fault
Input: Zero-phase current=Setting value1000%0A
directional element
CMP CMP1-A01 Zero-phase voltage=Rating voltage30%0V
Phase=Maximum sensitive angle
Earth fault overcurrent element Setting: minimum
CMP1A02 Input: Zero-phase current Setting value300 %0A
Setting: Number of start-up times=1,
Restriction Limit of the number of Start-up time=2s
1s5%
start time start-up times element Countdown rate of start-up time counter=2s/h
Input: A-phase current=0AIM300%
Setting: Number of start-up times=1,
Restriction Limit of the number of Start-up time=2s 10%
14.4s 0%
end time start-up times element Countdown rate of start-up time counter=250s/h
Input: A-phase current=0AIM300%for 2s0A

38
Precaution for application
1. Guarantee against interruption of AC power supply Please include the communication card into your purchasing order in
When an uninterruptible AC power source is not available in your case of the application of the communication facility as the card
system for the auxiliary power supply, use the type B-T1 AC/DC necessary for communication (CC-Link ) is option. In case of retrofit
converter or commercially available uninterruptible power supply existing relay with communication card, please inform the followings
(UPS). In addition, possible duration of the power supply type B-T1 of existing relay. a:Type, b:Style number, c:Manufacturing year, d:
AC/DC converter is confirmed as about 2 seconds in combination Serial number, e:Date of stamp on the checking seal (The above
with one MELPRO-D series relay. Therefore, in the case that the mentioned items a.d. are indicated on the bottom right of front face
required duration of power supply after power source loss exceeds 2 of the relay and item e. is indicated on the upper of back side of the
seconds, please use a suitable commercial uninterruptible power relay.) The version number of CC-Link is 1.00.
supply. When power supply back up for the circuit breaker is 7. Improvement of reliability of protection system
required, it is necessary to prepare the power supply independent For the important facilities, multiplex system such as dual should be
from the type B-T1 AC/DC converter. provided to improve reliability.
2. Inrush current of power supply 8. Effects of external surge
Since inrush current (about 2ms duration) as below may flow into the Some type of surge with a certain condition may inversely affect the
relay when the power supply is turned on, please make a relay. If so, take it into account to install surge absorbers.
consideration on this regard for selection of power circuit breaker. 9. It is possible to input the equipment fault signal and the operation
signal (under voltage, etc.) of external protection relay etc to the DI(1) CMP
Input voltage Inrush current Ip
DC110V Approx. 20A and DI(2). These input signals can initiate the related operation
DC220V Approx. 55A output signals.
AC100V Approx. 25A 10. Make a wiring between EVT a terminal and A-06 ( A-16 for
AC220V Approx. 65A CMP1-A01D2) terminal of relay and EVT f terminal and A-05

( A-15 for CMP1-A01D2) terminal of relay. Also, the grounding of
3. Trip circuit EVT tertiary circuit has to be configured by the wiring between f
Only the dedicated contacts can be used for the circuit breaker trip terminal of EVT and earth terminal. Any other wiring than above
circuit. Please keep in mind that the contacts for signaling can not be will not realize the correct detection on the earth fault directional.
used for the trip circuit. (If used, the contact may burn). Also, connect 11. A commercially available ZCT conformity with JEC1201 (type BZ in
the pallet contact (52a) of the circuit breaker to the trip coil circuit in case of MITSUBISHI ELECTRIC CORPORATION) may be applicable
series. for the type CMP1-A01D1/2.
4. Self-diagnosis output circuit 12. Only one number of ZCT can be connected to one number of the
The self-diagnosis output contact is so configured that the auxiliary type CMP1-A01D1/D2. Correct operation of the relay can not be
relay is energized ( break contact opened) when normal result of guaranteed against two or more numbers of ZCT to connect to one
self-diagnosis is received. This type of contact will allow the relay to number of the type CMP1-A01D1/2.
output abnormal result even after the built-in power failures. 13. It is possible to use the CMP1-A02 type as the phase over current
Therefore, the break contact is still closed in the aftermath of the protection provided with two phases. However, residual connection of
power applying and will be opened after 50ms. If the auxiliary power 2 phases can not be applied to the earth fault over current element.
of the relay and the self-diagnosis output contact feed from a same The residual connection of 3 phases only can be applied to the earth
power source, the break contact will be closed temporarily after fault over current element. In case of only two phase CTs being
auxiliary power supply is turned on. In this case where the available for phase over current protection, ZCT or one more CT is
phenomenon stated in the above would conflict with your system needed for earth fault over current element. Also. the negative
requirement, it is recommended that the self-diagnosis output contact sequence over current element is not operated properly by the CT
should be connected via the time-delay timer. circuits provided with two phases. Therefore, in this case, please
5. Grounding circuit make a setting of negative sequence of over current element to
Be sure to make a wiring to the earth terminal located on the back of LOCK position.
the relay according to the Class D earth wiring method (Grounding 14. The DI input of CMP1-A01D2 and CMP2-A02D2 has a polarity.
resistance should be less than 100 ohm). Therefore, please pay attention to polarity as DI input can not be
6. CC-Link communication circuit detected properly due to the wrong connection of DI circuit.

Precaution for using


1. When the product is shipped from the factory, each setting value is voltage between terminal a and f of EVT. Example: 190/3
LOCK (for element with LOCK position) or minimum setting 190V, 110/3110V
value(for element without LOCK position) 5. The function of the ZCT error correction installed in the relay(CMP1-
2. To set as [LOCK] position means to set the element out of use. A01D1/D2 type only, item No. 904,905) is applied for the purpose of
3. The setting of measuring transformer ratio is applied only for the correcting ZCT transformation error, so that improving the composite
measuring indication converted to the primary side, and is not characteristics is achieved. The ZCT error correction range is
applied for protection element. 200mA/1.5mA4.1mA(0+2.6mA) for the nominal transformation
4. The EVT tertiary voltage ratio should be set as output nominal ratio 200mA/1.5mA specified with JEC-1201.

Precaution for safety


Please refer to page2 and 3 regarding the safty information and request
when placing order.

39
Sample of external connection diagram

B05
A + A01 Y Self diagnosis output
B Auxiliary B06
power supply
C circuit A03 B07 Overcurrent
X0 under current element
B08 III
EA A09
CB B09
EVT X1 Overload element
IA A10
B10
B11 Negative sequence
overcurrent element For
A11 X2 signaling
B12 INSC
CT IC A12 B13 Earth fault directional element
X3 I
B14
CMP a f k ED + A07 B15 Limit of the number
K I0 of start-up times element
X4
R 1 ZCT
ts
200/1.5mA A08 B16
L B17 IOR IOR
r
ED X5
+ A05 IOR OR For trip
B18
ED V0 A06 B19 INSCOR I
X6
B20 Programmable output

Communication card
B01 DA Default setting at ex-works
B02 DB

(option)
M Serial communication bus
B03 DG
E A02
B04 SLD
ED

1 A resistance is necessary for the isolated neutral system.

Fig.51CMP1A01D1

B05
A + A01 Y Self diagnosis output
B Auxiliary B06
power supply
C circuit A03 B07 Overcurrent
X0 under current element
B08 III
EA A19
CB B09
EVT X1 Overload element
IA A20
B10
B11 Negative sequence
For
A21 X2 overcurrent element signaling
B12 INSC
CT IC A22 B13 Earth fault directional element
X3 I
B14
k ED + A17 Limit of the number
a f K B15 of start-up times element
I0 X4 ts
R 1 ZCT
200/1.5mA A18 B16 IOR IOR
L B17
r IOR OR For trip
ED X5
+ A15
B18 INSCOR I
ED V0 A16 B19
OR DI1OR DI2
X6
+ E01 B20 Programmable output
Default setting at ex-works
Communication card

2
DC110V DI input1E03 B01 DA
+ E02
(option)

M B02 DB
2 Serial
DC110V DI input2E04 B03 DG communication bus

E A02
1 A resistance is necessary for the isolated neutral system. B04 SLD
2 In case of auxiliary power supply voltage 24V, ED
input voltage E-01, 03 and E-02, 04 should be DC 24V.

Fig.52CMP1A01D2
The connection diagram shows concepts of the wiring only. Therefore, please note that there will have some difference
between the connection diagram and actual installation status of CT,VT and safety devices such as fuse, etc.
40
B05
A + A01 Y Self diagnosis output
B Auxiliary B06
power supply
C circuit A03 B07
X0 Overcurrent
B08 under current element
A07 III
CB B09
IA A08 X1 Overload element
B10
B11 Negative sequence For
A09 X2 overcurrent element signaling
B12 INSC
IB A10 B13
X3 Earth fault overcurrent element
B14 I
A11 CMP
CT B15 Limit of the number
X4 of start-up times element
IC A12 B16 ts
B17 IOR IOR
+ A05 X5
B18 IOR OR For trip
I0
B19 INSCOR I
A06 X6
B20 Programmable output

Communication card
ED Default setting at ex-works
B01 DA
(option) B02 DB
M Serial communication bus
B03 DG
E A02
B04 SLD
ED

Fig.53CMP1A02D1

B05
A + A01 Y Self diagnosis output
B Auxiliary B06
power supply
C circuit A03 B07 Overcurrent
X0
P under current element
B08
A17 III
CB B09
IA A18 X1 Overload element
B10
B11 Negative sequence overcurrent element For
A19 X2 signaling
INSC
B12
IB A20 B13 Earth fault overcurrent element
X3 I
B14 Limit of the number
A21 of start-up times element
CT B15
X4 ts
IC A22 B16 IOR IOR
B17
X5 IOR OR
+ A15 For trip
B18 INSCOR I
I0
B19 OR DI1OR DI2
A16 X6
M + E01 B20 Programmable output
ED
Communication card

1 Default setting at ex-works


DI input1E03 B01 DA
DC110V
B02 DB
(option)

+ E02
B03 DG Serial communication bus
DI input2E04
N
E A02
B04 SLD
1 In case of auxiliary power supply voltage 24V, ED
input voltage E-01, 03 and E-02, 04 should be DC 24V.

Fig.54CMP2A02D2
The connection diagram shows concepts of the wiring only. Therefore, please note that there will have some difference
between the connection diagram and actual installation status of CT,VT and safety devices such as fuse, etc.
41
CPP Series SYSTEM LINKAGE PROTECTION RELAY
Type, rating and specification
Type name CPP1A01D2 CPP1A11D2
Phase current 5A
Voltage 57120V
Zero-phase voltage 100208V
Rating DC110VPermissible variable range 77143Vor DC24VPermissible variable range DC19.2V31.2V
Photo coupler input
Input voltage 24V is applicable only for the case that auxiliary power supply voltage is 24V.
voltageD2 type only
In any other cases, only DC110V is applicable as for photo coupler input voltage.
Frequency 50Hz or 60Hz
Protective element 64,59,27,67S,95L,95H,67P,91L,df/dt Applicable only for A11
Combined instrument transformer Zero-phase voltage Commercially available EVTConformity with JEC-1201

Earth fault Operation voltage LOCK560V1V step


over voltage
Operation time 0.050.115s 0.1s step
Over Operation voltage LOCK110150V1V step
voltage Operation time 0.050.115s 0.1s step
Under Operation voltage LOCK20110V1V step
voltage Operation time 0.050.115s 0.1s step
L element operation value LOCKRated current5A 120%1% step
CPP L element operation time 0.050.115s 0.1s step
Phase fault
directional H element operation value LOCKRated current5A 20100%1% step
H element operation time 0.050.115s 0.1s step
UV element for DS operation value NO USE20100V1V step
Under Operation value Rated frequency:50HzLOCK49.545Hz0.1Hz step,Rated frequency:60HzLOCK59.555Hz0.1Hz step
frequency Operation time 0.050.115s 0.1s step
Reverse Operation value LOCKRated current5A 0.230%0.21%:0.1% step,130%:1% step
power Operation time 0.050.115s 0.1s step
Over Operation value Rated frequency:50HzLOCK50.555Hz0.1Hz step,Rated frequency:60HzLOCK60.565Hz0.1Hz step
Setting frequency Operation time 0.050.115s 0.1s step
Operation value LOCKRated current5A 130%1% step
Under
power Operation time 0.050.115s 0.1s step
Open circuit detecting function lock OFFONSet ON in case of open circuit detecting function lock
Lock at uninterconnected condition 010s 0.1s step
Islanding Operation value LOCK0.0252Hz/s

detection 0.025Hz/s step
df/dt Operation time 0.21s 0.1s step
Output contact configuration Refer to the external connection diagram/Auto reset for all contacts Default setting at ex-works
Operation indicator LED hold All LED self-hold Default setting at ex-works
5101212.51520253040506075801001201251502002503004005006007508001000120012501500
CT primary
20002500300040005000600075008000[A]
VT primary 100999V1V step10009990V10V step10.0k99.9kV0.1kV step100k300kV1kV step
VT secondary 100/3110/3115/3120/3100110115120V
100999V1V step,10009990V10V step,
EVT primary
10.0k99.9kV0.1kV step,100k300kV1kV step
EVT tertiary 1001101151201003110311531203V
Real time measurement Phase current3, voltage, Zero-phase voltage, Active power, Reverse power, Power factor, Frequency
Max.record Phase current3, voltage, Zero-phase voltage, Active power, Reverse power
Fault recordoperation value Phase current3, voltage, Zero-phase voltage, Active power, Reverse power, Power factor, Frequency
Display
Fault recordoperation item Record and indicate the operated elements.
Normal result:On the RUN LEDgreenStatus indication item No.400=No display.
Self-diagnosis
Abnormal result:Off the RUN LEDStatus indication item No.400=Display defects code
Forced operation Each output contact
Direct communication port Standard equipmentPC software for Direct communication:Option
Communication
Remote communication port Option For CC-LINK
Phase current circuit:Less than 0.5VA, voltage circuit:Less than 1.0VA,
Zero-phase voltage circuit:Less than 1.5VA
Burden (at rating)
Auxiliary power supply circuit:at DC100V=Approx. 6W, at AC100V=Approx. 12VA, at DC220V=Approx. 6W,
at AC220V=Approx. 14VAIn case of installing communication card, add 2 VA.
Mass Net weight of relay unit:Approx.3.5kg, Including case:Approx.4.5kg
Sample of external connection diagram Fig.61
Remarks The island detection facility is available for CPP1-A11D2 and not available for type CPP1-A01D2

Please refer to the instruction manual regarding the details on this specification.

42
Characteristics
Items Condition Guaranteed performance
Earth fault over
voltage element
Common condition1
Over voltage element
Under voltage element
Input voltage: Rated voltage Setting value 5%
Phase fault directional element
Phase of current: Maximum sensitive angle
L,H element
Set UV element for the NO USE position
Phase fault directional element
Common condition1
U,V element
Operation
value Under frequency element Input voltage: Rated voltage Setting value 0.05Hz
For 0.20.5% setting: Setting value1.5mA
Reverse power Input voltage: Rated voltage
element For 0.60.9% setting: Setting value7%
Phase of current: Maximum sensitive angle
For another setting: Setting value5%
Over frequency element Input voltage: Rated voltage Setting value 0.05Hz
Under power Input voltage: Rated voltage
Setting value 5%
element Phase of current: Maximum sensitive angle
Islanding detection Input voltage: Rated voltage
[Value for full operation]
element Change frequency quickly from rated frequency CPP
CPP1-A11D2 Setting value: 0.0125Hz/s
In case of operation time setting is 1s, frequency should be swept.
Earth fault over
operation value95% or more
voltage element
Common condition1
Over voltage element operation value95% or more
Under voltage element operation value105% or less
Phase fault directional element Input voltage: Rated voltage
operation value95% or more
L,H element Phase of current: Maximum sensitive angleSet UV element for the NO USE position
Phase fault directional element
Common condition1 operation value105% or less
U,V element
Reset value Under frequency Difference between operation value and reset value is
Input voltage: Rated voltage
element 0.05Hz or less
For 0.20.5% setting: Operation value80% or more
Reverse power Input voltage: Rated voltage
For 0.60.9% setting: Operation value93% or more
element Phase of current: Maximum sensitive angle
For another setting: Operation value95% or more
Over frequency Difference between operation value and reset value is
element Input voltage: Rated voltage
0.05Hz or less
Under power Input voltage: Rated voltage
operation value105% or less
element Phase of current: Maximum sensitive angle
Earth fault over Operation setting value: Minimum
voltage element Input: Operation setting value150%
Operation setting value: Minimum
Over voltage element
Input: Operation setting value120%
Operation setting value: 100V
Under voltage element
Input: rated voltageoperation setting value70%
Operation setting value: minimum, UV setting for DS: NO USE
Phase fault
Input voltage: Rated voltage
directional element
L,H element Input current: 0setting value200%
Phase of current: Maximum sensitive angle
Operation setting value: Minimum
Operation Under frequency Input voltage: Rated voltage
time element Frequency: Rated frequency Setting value 20ms or 5% whichever is greater
setting value1Hz with moving down rate df/dt=5Hz/s
Operation setting value: Minimum
Reverse power Input voltage: Rated voltage
element Input current: 0setting value200%
Phase of current: Maximum sensitive angle
Operation setting value: Minimum
Over frequency Input voltage: Rated voltage
element Frequency: Rated frequency
setting value+1Hz with moving up rate df/dt=5Hz/s
Operation setting value: Maximum
Under power Input voltage: Rated voltage
element Input current: setting value200%0
Phase of current: Maximum sensitive angle
1Common condition
1Rating Frequency2Ambient temperature203Auxiliary power supply: Rating voltage

43
Items Condition Guaranteed performance
Operation setting value: Minimum
Islanding detection Input voltage: Rated voltage
Operation element Frequency:Rated frequency Setting value: 40ms
time CPP1-A11D2 Rated frequency+setting value 500%
Change abruptly at the same phase.
Lock reset time of lock function at DI input voltage: Rated voltage0
Setting value 50ms or 5% whichever is greater
un-interconnected condition Measuring the time between contact open statusclose status.
Earth fault over Operation setting value: Minimum
voltage element Input: Operation setting value150%0
Over voltage Operation setting value: Minimum
element Input: Operation setting value120%0
Under voltage Operation setting value: 100V
element Input: operation setting value70%rated voltage
Operation setting value: minimum, UV setting for DS: NO USE
Phase fault
Input voltage: Rated voltage
directional element
L,H element Input current: setting value200%0
Phase of current: Maximum sensitive angle
CPP Operation setting value: Minimum
Under frequency Input voltage: Rated voltage
Reset time element Frequency: setting value+1Hz 200ms20ms
Rated frequency with moving up rate df/dt=5Hz/s
Operation setting value: Minimum
Reverse power Input voltage: Rated voltage
element Input current: setting value200%0
Phase of current: Maximum sensitive angle
Operation setting value: Minimum
Over frequency Input voltage: Rated voltage
element Frequency: setting value1Hz
Rated frequency with moving down rate df/dt=5Hz/s
Operation setting value: Maximum
Under-power Input voltage: Rated voltage
element Input current: 0setting value300%
Phase of current: Maximum sensitive angle
Islanding detection
Output contact
element Common condition1
latching time
CPP1-A11D2

55
5
Phase fault Input voltage: Rated voltage 305
5 Operation side
directional element Input current: setting value200%
L,H element USE UV setting for DS: NO USE
35

Phase Reverse power Input voltage: Rated voltage


characteristic element Input current: setting value200%
Operation side

Maximum sensitive angle=05


Under power Input voltage: Rated voltage


element Input current: setting value200% Operation side


Maximum sensitive angle=1805

1Common condition
1Rating Frequency2Ambient temperature203Auxiliary power supply: Rating voltage

44
Precaution for application
1. Guarantee against interruption of AC power supply phenomenon stated in the above would conflict with your system
When an uninterruptible AC power source is not available in your requirement, it is recommended that the self-diagnosis output contact
system for the auxiliary power supply, use the type B-T1 AC/DC should be connected via the time-delay timer.
converter or commercially available uninterruptible power supply 5. Grounding circuit
(UPS). In addition, possible duration of the power supply type B-T1 Be sure to make a wiring to the earth terminal located on the back of
AC/DC converter is confirmed as about 2 seconds in combination the relay according to the Class D earth wiring method (Grounding
with one MELPRO-D series relay. Therefore, in the case that the resistance should be less than 100 ohm).
required duration of power supply after power source loss exceeds 2 6. CC-Link communication circuit
seconds, please use a suitable commercial uninterruptible power Please include the communication card into your purchasing order in
supply. When power supply back up for the circuit breaker is case of the application of the communication facility as the card
required, it is necessary to prepare the power supply independent necessary for communication (CC-Link ) is option. In case of retrofit
from the type B-T1 AC/DC converter. existing relay with communication card, please inform the followings
2. Inrush current of power supply of existing relay. a:Type, b:Style number, c:Manufacturing year,
Since inrush current (about 2ms duration) as below may flow into the d:Serial number, e:Date of stamp on the checking seal (The above
relay when the power supply is turned on, please make a mentioned items a.d. are indicated on the bottom right of front face
consideration on this regard for selection of power circuit breaker. of the relay and item e. is indicated on the upper of back side of the
Input voltage Inrush current Ip relay.) The version number of CC-Link is 1.00.
DC110V Approx. 20A 7. Improvement of reliability of protection system
DC220V Approx. 55A For the important facilities, multiplex system such as dual should be
AC100V Approx. 25A provided to improve reliability.
AC220V Approx. 65A 8. Effects of external surge CPP
Some type of surge with a certain condition may inversely affect the
3. Trip circuit relay. If so, take it into account to install surge absorbers.
Only the dedicated contacts can be used for the circuit breaker trip 9. Lock at un-interconnected condition (Terminal number E-01,E-
circuit. Please keep in mind that the contacts for signaling can not be 03) Operation of each element (DS, RP, UF, OF, UP and df/dt) are
used for the trip circuit. (If used, the contact may burn). Also, connect locked for the determined time after interconnection (set by the timer
the pallet contact (52a) of the circuit breaker to the trip coil circuit in element of un-interconnected condition) in order to prevent
series. unnecessary operations due to the power fluctuation. The lock
4. Self-diagnosis output circuit condition will be released in the determined time.
The self-diagnosis output contact is so configured that the auxiliary 10. The DI input of un-interconnected condition (Terminal number E-
relay is energized ( break contactopened ) when normal result of 01,E-03) has a polarity. Therefore, please pay attention to polarity
self-diagnosis is received. This type of contact will allow the relay to as the DI input can not be detected properly due to the wrong
output abnormal result even after the built-in power failures. connection of DI circuit.
Therefore, the break contact is still closed in the aftermath of the 11. Make a wiring between EVT a terminal and A-12 terminal of
power applying and will be opened after 50ms. If the auxiliary power relay and EVT f terminal and A-11 terminal of relay. Also, the
of the relay and the self-diagnosis output contact feed from a same grounding of EVT tertiary circuit has to be configured by the wiring
power source, the break contact will be closed temporarily after betweenfterminal of EVT and earth terminal.
auxiliary power supply is turned on. In this case where the

Precaution for using


1. When the product is shipped from the factory, each setting value is for under voltage element. (UV test LED will turn on during selecting
LOCK (for element with LOCK position) or minimum setting UV TEST). UV TEST should be set as OFF in the operational
value(for element without LOCK position) condition.
2. To set as [LOCK] position means to set the element out of use. 6. The DS test function (item No. 546) will be used for single phase test
3. The setting of measuring transformer ratio is applied only for the for the phase fault directional element. (DS test LED will turn on
measuring indication converted to the primary side, and is not during selecting DS TEST). DS TEST should be set as OFF in the
applied for protection element. operational condition.
4. The EVT tertiary voltage ratio should be set as output nominal 7. The 67P and 91L elements detect 3 phases active power(3EIcos).
voltage between terminal a and f of EVT. Example: 190/3 100% of 3 phases power equal to that when nominal voltage (110V)
190V, 110/3110V and nominal current (5A) are impressed.
5. The UV test function (item No. 533) will be used for single phase test

Precaution for safety


Please refer to page2 and 3 regarding the safty information and request
when placing order.

45
Sample of external connection diagram

Main power network


+ A01
Auxiliary B05
power supply Y Self diagnosis output
circuit A03 B06

A18 B07 Earth fault over voltage element


52R X0 U
IA A17 B08

B09 Over voltage element


A20 X1 U
B10
IB A19
B11 Under voltage element
X2 U
A22
CT B12
IC A21 B13 Phase fault directional element
X3 I
ED B14
CPP C07 Under frequency element For
X4 f signaling
EA C08

EVT C09 Reverse power element


A13 X5 P
C10
VAB
A14
C11 Over frequency element
VBC X6 f
A15
C12
Tr
ED C13 Under-power element
X7 P
C14
1
a f C15 Islanding detection element
X8 df/dt
R 3 + A11
C16
ED V0 A12 2
B17 Under voltage element
X9
U
X8
B18
2
+ B19 Under-power element
Xa
Un-interconnected P
X9
condition B20
+ E01 1 For trip
2
4 C17 UOR UOR I
52Rb52Gb etc Xb
DC110V E03 Xa OR fOR POR f
C18
OR df/dt
2
C19
Xc
Xb
52G C20

Programmable output
Default setting at ex-works
G
Communication card

B01 DA
Consumer-owned
B02 DB
(option)

dispersed generator
Serial communication bus
B03 DG
A02
E B04 SLD
ED
1 The island detection facility is not available for CPP1-A01D2.
2 The output contact device number for CPP1-A01D2 is the number inside the parentheses.
3 A resistance is necessary for the isolated neutral system.
4 The application voltage for terminal E-01, E-03 is 24V in case that the supplied auxiliary power voltage is 24V.

Fig.61CPP1A01D2, CPP1A11D2
The connection diagram shows concepts of the wiring only. Therefore, please note that there will have some difference
between the connection diagram and actual installation status of CT,VT and safety devices such as fuse, etc.
46
CGP1 Series GENERATOR PROTECTION RELAY
Type, rating and specification
Type name CGP1A01D2 CGP1A03D2
Phase current 5A
Line voltage 57120V
Zero-phase voltage 100208V
Rating DC110V
Permissible variable range 77143Vor DC24V Permissible variable range DC19.2V31.2V
Photo coupler input voltage Input voltage 24V is applicable only for the case that auxiliary power supply voltage is 24V.
In any other cases, only DC110V is applicable as for photo coupler input voltage.
Frequency 50Hz or 60Hz
Protective element 51,50,462,84,59,27,95L,95H,67P,67G,64 51,50,462,84,59,27,95L,95H,67P,51G
Combined instrument Zero phase current Commercially available ZCTConformity with JEC-1201 200/1.5mA

transformer Zero-phase voltage Commercially available EVT Conformity with JEC-1201
IG Generator rating current 2.55A 0.1A step
Operation current LOCKIG100120%1% step
Operation time multiplier 0.250.5100.5 step
NI 0.14 M
t s tOperation time
Overcurrent Normal inverse time-delayed I0.021 10 s
time-delayed EI 150 M IMultiple of input current against setting
Operation time t s
characteristics Extremely inverse time-delayed I21 10 value
IG100%120%
DT M MOperation time multiplier times
t2 s
Definite time-delayed 10

Overcurrent Operation current LOCKIG100%1200%50% step


instantaneous Operation time INST0.10.5s0.1s step
Operation current LOCKIG5%30% 1% step
Operation time multiplier 10501 step
Unbalance
current 1 tOperation time s
Operation time M
t s I2Multiple of input negative sequence current against IG
characteristics I22
MOperation time multiplier times
Unbalance Operation current LOCKIG5%30% 1% step CGP1
current 2 Operation time 110s
0.1s step
Voltage Operation LOCK80110V 1V step
detecting Operation time 0.510s 0.1s step
Over Operation LOCK110155V 1V step
voltage Operation time 0.110s 0.1s step
Under Operation LOCK20110V 1V step
voltage Operation time 0.110s 0.1s step
Under Operation Rating50HzLOCK49.5Hz45Hz 0.1Hz step ,Rating60HzLOCK59.555Hz 0.1Hz
frequency Operation time 0.110s 0.1s step
Over Operation Rating50HzLOCK50.5Hz55Hz 0.1Hz step ,Rating60HzLOCK60.565Hz 0.1Hz
Setting frequency Operation time 0.110s 0.1s step
Reverse Operation LOCKIG0.5130% 1% step
power Operation time 0.120s 0.1s step
Operation currentI0 10mAZCT secondary 0.5mA step
Earth fault OperationV0 LOCK560V 1V step
directional Operation time INST0.110s0.1s step
Maximum sensitive angle Lead 0
905 step
Earth fault Operation LOCK560V 1V step
over voltage Operation time 0.120s0.1s step
Earth fault Operation LOCK0.12.0A0.1A step
overcurrent Operation time INST0.10.5s0.1s step
Output contact configuration Refer to the external connection diagram/Auto reset for all contacts
Default setting at ex-works
Operation indicator LED hold All LED self-hold
Default setting at ex-works
5101212.5152025304050607580100120125150200250300400500600750800100012001250
CT primary
150020002500300040005000600075008000[A]
VT primary 100999V 1V step 10009990V 10V step 10.0k99.9kV0.1kV step 100k300kV 1kV step
VT secondary 100/3110/3115/3120/3100110115120V
100999V 1V step ,10009990V 10V step ,
EVT primary
10.0k99.9kV 1kV step ,100k300kV 1kV step
10011011512010031103
EVT tertiary
11531203V
ZCT error correction on/off OFFON
When the actual measured transforming ratio is within
ZCT error adjustment range of 200/1.54.1mA, the deviation from the ZCT
nominal transforming ratio 200/1.5mA can be corrected.
Real time measurement Phase current3, voltage, Zero-phase voltage#, Active power, Reverse power, Power factor, Frequency
Max.record Phase current3, voltage, Zero-phase voltage#, Active power, Reverse power
Fault record (operation value) Phase current3, voltage, Zero-phase voltage#, Active power, Reverse power, Power factor, Frequency
Display
Fault record (operation item) Record and indicate the operated elements.
Normal result:On the RUN LED green Status indication item No.400=No display.
Self-diagnosis
Abnormal result:Off the RUN LEDStatus indication item No.400=Display defects code
Forced operation Each output contact
Direct communication port Standard equipment PC software for Direct communication:Option
Communication
Remote communication port OptionFor CC-LINK
Phase current circuit:Less than 0.5VA, Voltage circuit:Less than 1.0VA,
Zero-phase voltage circuit:Less than 0.15VAA01 type
Burden (at rating) Zero-phase current circuit: Less than 10A01 type
Auxiliary power supply circuit:at DC100V=Approx. 6W, at AC100V=Approx. 12VA, at DC220V=Approx. 6W,
at AC220V=Approx. 14VA In case of installing communication card, add 2 VA.
Mass Net weight of relay unit:Approx. 3.5kg, Including case:Approx. 4.5kg
Sample of external connection diagram Fig.71 Fig.72
Please refer to the instruction manual regarding the details on this specification.
# Not applicable for CGP1-A03D2 47
Characteristics
Items Condition Guaranteed performance
Overcurrent time-delayed element Setting value 5%
Common condition 1
Overcurrent instantaneous element Setting value 10%
Unbalance current element 1
Negative sequence current
Unbalance current element 2
Voltage detecting element Setting value 5%
Over voltage element Common condition 1
Under voltage element
Under frequency element Input voltage: Rated voltage
Setting value 0.05Hz
Over frequency element Input voltage: Rated voltage
Operation Reverse power Input voltage: Rated voltage 0.5, 13% setting: Setting value5mA
value element Phase of current: Maximum sensitive angle For another setting: setting value 5%
Setting: Zero phase voltage: minimum
Zero phase 1.0 and 1.5mA setting: setting value10%
Input: Zero phase voltage=rated voltage30%
Earth fault current For another setting: setting value 5%
Phase: maximum sensitive angle
directional element
Setting: Zero phase current: minimum
CGP1A01D2 Zero phase
Input: Zero phase current=setting value1000% Setting value 5%
voltage
Phase: maximum sensitive angle
Earth fault overcurrent
Common condition 1 Setting value 5%
CGP1A03D2
Earth fault over voltage element
Common condition 1 Setting value 5%
CGP1A01D2
Overcurrent time-delayed element
Common condition 1
Overcurrent instantaneous element
Unbalance current element 1
Negative sequence current Setting value95% or more
Unbalance current element 2
CGP1 Voltage detecting element
Over voltage element Common condition 1
Under voltage element Setting value105% or less
Under frequency element Input voltage: Rated voltage Difference between operation value and reset value is
Over frequency element Input voltage: Rated voltage 0.05Hz or less
Reverse power Input voltage: Rated voltage 0.5, 13% setting: operation value80% or more
Reset value element Phase of current: Maximum sensitive angle For another setting: setting value95% or more
Setting: Zero phase voltage: minimum
Zero phase
Input: Zero phase voltage=rated voltage30%
Earth fault current
Phase: maximum sensitive angle
directional element Operation value90% or more
Setting: Zero phase current: minimum
CGP1A01D2 Zero phase
voltage Input: Zero phase current=setting value1000%
Phase: maximum sensitive angle
Earth fault overcurrent
Common condition 1 Setting value95% or more
CGP1A03D2
Earth fault over voltage element
Common condition 1 Setting value95% or more
CGP1A01D2
Operation setting value: minimum NI,EI Input: 300%: nominal value12% or less
Operation time multiplier: 10 Input: 500%: nominal value12% or less
Input: 0setting value300.500.1000% Input: 1000%: nominal value7% or less
NINormal inverse time delayed 0.14 M DT Nominal value5% or less
Overcurrent t s
characteristics I0.021 10
time-delayed EIExtremely inverse 150 M
element t s
time-delayed characteristic I21 10
DTDefinite time-delayed M
t2 s
characteristic 10
t: operation time(s)
I: Multiple of input current against operation value
(Ig100120%)
M: Operation time multiplier times
Overcurrent Operation setting value: minimum Setting value25ms or less and at the time of INST
Operation
instantaneous element Input: 0200% of setting value setting: 40ms or less
time
Operation setting value: minimum Input: 300%: nominal value20% or less
Operation time multiplier: 10 Input: 500%: nominal value15% or less
Input: 030,50,100% of Generator rated current Ig Input: 1000%: nominal value10% or less
Unbalance current
element 1 t: operation time(s)
M I2: Multiple of input negative sequence
t s
I22 current against Ig
M: Operation time multiplier
times
Unbalance current Setting: minimum
element 2 Input: negative sequence current=0setting value200% Setting value 5% or less
Voltage detecting element Operation setting value: minimum
Over voltage element Input: 0operation setting value120%
0.10.5s setting: setting value25ms or less
Under voltage Operation setting value: 100V
element For 0.610s setting: Within setting value5%
Input: rated voltageoperation setting value70%

1Common condition
1Rating Frequency2Ambient temperature203Auxiliary power supply: Rating voltage

48
Items Condition Guaranteed performance
Operation setting value: minimum
Under frequency Input voltage: Rated voltage
element Frequency: Rated frequencysetting value1Hz with
moving down rate df/dt=5Hz/s
Operation setting value: maximum
Over frequency Input voltage: Rated voltage 0.10.5s setting: setting value25ms or less
element Frequency: Rated frequencysetting value+1Hz with For 0.610s setting: Within setting value5%
moving up rate df/dt=5Hz/s
Operation setting value: minimum
Operation Reverse power Input voltage: Rated voltage
time element Input current: 0setting value200%
Phase of current: Maximum sensitive angle
Setting: Zero phase current, voltage=minimum
Earth fault In case of INST setting: 80ms or less
Input: Zero phase current=0setting value1000%
directional element 0.10.5s setting: within25ms of setting value
Zero phase voltage=0rated voltage30%
CGP1A01D2 0.61.0s setting: within5% of setting value
Phase: maximum sensitive angle
Earth fault overcurrent element Operation setting value: minimum
Within setting value 25ms
CGP1A03D2 Input: Zero phase current=0setting value1000%
Earth fault over voltage element Operation setting value: minimum 0.10.5s setting: setting value25ms or less
CGP1A01D2 Input: Operation setting value150% For 0.610s setting: Within setting value5%
Overcurrent time-delayed element Operation setting value: minimum
Overcurrent instantaneous element Input: Operation setting value300%0
Unbalance current element 1 Setting: minimum
Unbalance current element 2 Input: negative sequence current=setting value300%0A CGP1
Voltage detecting element Operation setting value: minimum
Over voltage element Input: Operation setting value120%0
Under voltage Operation setting value: 100V
element Input: Operation setting value70%rated voltage
Operation setting value: minimum
Under frequency Input voltage: Rated voltage
element Frequency: Setting value1Hzrated frequency with
moving up rate ,df/dt=5Hz/s
Operation setting value: maximum
Reset time Over frequency Input voltage: Rated voltage
200ms25ms
element Frequency: Setting value+1Hzrated frequency with
moving down rate ,df/dt=5Hz/s
Operation setting value: minimum
Reverse power Input voltage: Rated voltage
element Input current: setting value200%0
Phase of current: Maximum sensitive angle
Setting: Zero phase current, voltage=minimum
Earth fault
Input: Zero phase current=setting value1000%0
directional element
Zero phase voltage=rated voltage30%0
CGP1A01D2
Phase: maximum sensitive angle
Earth fault overcurrent element Operation setting value: minimum
CGP1A03D2 Input: Zero phase current=setting value1000%0
Earth fault over voltage element Operation setting value: minimum
CGP1A01D2 Input: operation setting value150%0
Reverse power Input voltage: Rated voltage
Maximum sensitive angle=0
5
element Current input: setting value200%
Phase
Setting: Zero phase current, voltage=minimum
characteristic Earth fault
directional element Input: Zero phase current=setting value1000% Maximum sensitive angle5
CGP1A01D2 Zero phase voltage=rated voltage30%
Settings: Time-delayed operation value=minimum,
Overcurrent operation time multiplier=10,
time-delayed element operation characteristic=all characteristics
Overshoot
characteristic Current input: 0A setting value1000% No-operation limit time/operation time=90% or more
Settings: Time-delayed operation value=minimum,
Unbalance current
element 1 operation time multiplier=10
Current input: 0A setting value1000%

49
Precaution for application
1. Guarantee against interruption of AC power supply 7. Improvement of reliability of protection system
When an uninterruptible AC power source is not available in your For the important facilities, multiplex system such as dual should be
system for the auxiliary power supply, use the type B-T1 AC/DC provided to improve reliability.
converter or commercially available uninterruptible power supply 8. Effects of external surge
(UPS). In addition, possible duration of the power supply type B-T1 Some type of surge with a certain condition may inversely affect the
AC/DC converter is confirmed as about 2 seconds in combination relay. If so, take it into account to install surge absorbers.
with one MELPRO-D series relay. Therefore, in the case that the 9. Make a wiring between EVT a terminal and A-10 terminal of
required duration of power supply after power source loss exceeds 2 relay and EVT f terminal and A-09 terminal of relay. Also, the
seconds, please use a suitable commercial uninterruptible power grounding of EVT tertiary circuit has to be configured by the wiring
supply. When power supply back up for the circuit breaker is between f terminal of EVT and earth terminal. Any other wiring
required, it is necessary to prepare the power supply independent than above will not realize the correct detection on the earth fault
from the type B-T1 AC/DC converter. directional.
2. Inrush current of power supply 10. Lock function by external control input
Since inrush current (about 2ms duration) as below may flow into the Two DI circuits are installed for the interlock by external control signals,
relay when the power supply is turned on, please make a and a relay element can be locked by DI input. Moreover, the relay element
consideration on this regard for selection of power circuit breaker. locked at the time of DI input arising can be set up to each DI circuit.
Input voltage Inrush current Ip 11. A commercially available ZCT conformity with JEC1201 (type BZ in
case of MITSUBISHI ELECTRIC CORPORATION) may be applicable
DC110V Approx. 20A
for the type CGP1-A01D2.
DC220V Approx. 55A
12. Only one number of ZCT can be connected to one number of the
AC100V Approx. 25A type CGP1-A01D2. Correct operation of the relay can not be
AC220V Approx. 65A guaranteed against two or more numbers of ZCT to connect to one
3. Trip circuit number of the type CGP1-A01D2.
Only the dedicated contacts can be used for the circuit breaker trip 13. It is possible to use the type CGP1-A03 as the phase over current
circuit. Please keep in mind that the contacts for signaling can not be protection provided with two phases. However, residual connection of
used for the trip circuit. (If used, the contact may burn). Also, connect 2 phases can not be applied to the earth fault over current element.
the pallet contact (52a) of the circuit breaker to the trip coil circuit in The residual connection of 3 phases only can be applied to the earth
series. fault over current element. In case of only two phase CTs being
CGP1
4. Self-diagnosis output circuit available for phase over current protection, ZCT or one more CT is
The self-diagnosis output contact is so configured that the auxiliary needed for earth fault over current element. Also. The unbalance
relay is energized ( break contact opened) when normal result of current elements are not operated properly by the CT circuits
self-diagnosis is received. This type of contact will allow the relay to provide with two phases. Therefore, please make a setting of
output abnormal result even after the built-in power failures. unbalance current elements as LOCK position.
Therefore, the break contact is still closed in the aftermath of the 14. The DI input for interlock (Terminal number E-01,E-03 and
power applying and will be opened after 50ms. If the auxiliary power E-02,E-04) has a polarity. Therefore, please pay attention to
of the relay and the self-diagnosis output contact feed from a same polarity as the input signals can not be detected properly due to the
power source, the break contact will be closed temporarily after wrong connection of DI circuit.
auxiliary power supply is turned on. In this case where the 15. According to the connection diagram, ZCT terminalKis assigned
phenomenon stated in the above would conflict with your system as utility side and terminalLis assigned as load (generator) side.
requirement, it is recommended that the self-diagnosis output contact However, it is possible to assign the ZCT terminal K as load
should be connected via the time-delay timer. (generator) side and the ZCT terminalLas utility side. In this case,
5. Grounding circuit make a wiring between ZCT secondary terminal k and relay
Be sure to make a wiring to the earth terminal located on the back of terminal A-16 and between ZCT terminal l and relay terminal
the relay according to the Class D earth wiring method (Grounding A-15. Regarding a CT connection, make wiring as R phase current
resistance should be less than 100 ohm). flows into the terminal A-18 of relay and T phase current flows
6. CC-Link communication circuit into the terminal A-22 of relay in case of normal operation. Please
Please include the communication card into your purchasing order in note allow marks indicated in the connection diagram shows the
case of the application of the communication facility as the card direction of current in case of faults occurrence in the generator.
necessary for communication (CC-Link ) is option. In case of retrofit 16. To prevent the influence from noise or surge, a shielded 2 cores (size
existing relay with communication card, please inform the followings is 0.751mm2) cable should be used for the connection between ZCT
of existing relay. a:Type, b:Style number, c:Manufacturing year, or ZVT and relay and shield wire should be connected to the earth
d:Serial number, e:Date of stamp on the checking seal (The above terminal of the relay or the earth terminal located inside of the
mentioned items a.d. are indicated on the bottom right of front face switchboard. Further more, the go and return burden of the cable
of the relay and item e. is indicated on the upper of back side of the should be less than 5 ohms which is almost equal to 100m distance in
relay.) The version number of CC-Link is 1.00. case of 0.75mm2 .

Precaution for using


1. When the product is shipped from the factory, each setting value is correcting ZCT transformation error, so that improving the composite
LOCK (for element with LOCK position) or minimum setting characteristics is achieved. The ZCT error correction range is
value(for element without LOCK position) 200mA/1.5mA4.1mA(0+2.6mA) for the nominal transformation
2. To set as [LOCK] position means to set the element out of use. ratio 200mA/1.5mA specified with JEC-1201.
3. The setting of measuring transformer ratio is applied only for the 6. The UV test function (item No. 533) will be used for single phase test
measuring indication converted to the primary side, and is not for under voltage element. (UV test LED will turn on during selecting
applied for protection element. UV TEST). UV TEST should be set as OFF in the operational
4. The EVT tertiary voltage ratio should be set as output nominal condition.
voltage between terminal a and f of EVT. Example: 190/3 7. The 67P element detect 3 phases active power(3EIcos). 100% of 3
190V, 110/3110V phases power equal to that when nominal voltage (110V) and nominal
5. The function of the ZCT error correction installed in the relay (CGP1- current (5A) are impressed.
A01D2 type only, item No. 906,907) is applied for the purpose of

Precaution for safety


Please refer to page2 and 3 regarding the safty information and request
when placing order.

50
Sample of external connection diagram
A
+ A01
B Auxiliary B05
C power supply Y Self diagnosis output
circuit A03 B06
EA B07 Over current element
EVT X0 IORI
B08

B09 Earth fault over voltage element


X1 U
CB B10

B11 Earth fault directional element


a f X2 I
B12
R 1 + A09
B13 Unbalance current element 1
ED V0 A10 X3 INSC
B14
67G B15
trip Unbalance current element 2
k + A15 X4 INSC
direction K
I0 B16
ZCT A16
(200/1.5mA) L C07 Voltage detecting element For
r X5 signaling CGP1
ED U
ZCT
A17 C08

L r C09 Over voltage element


ED IA 3 A18 X6 U
CT
C10
K k A21
C11 Under voltage element
IC 3 A22 X7 U
C12
67P
protection C13 Under frequency element
direction VT A11
X8 f
VAB C14
A12
C15 Over frequency element
VBC X9 f
ED A13
C16

C17 Reverse power element


Xa P
C18

B17 IOR IOR UOR


Xb IOR INSCOR INSC
B18 For trip
+ E01 OR UOR UOR
+ B19 fOR fOR P
DC110V DI1 Xc
2 E03
B20 Programmable output
Default setting at ex-works
Lock function by external control input + E02
+
DC110V DI2
G 2 E04
Communication card

B01 DA
Generator
B02 DB
(option)

Serial communication bus


B03 DG
A02
E B04 SLD
ED
1 A resistance is necessary for the isolated neutral system.
2 The application voltage for terminal E-01, E-03 and terminal E-02, E-04 is 24V in case that the supplied auxiliary power voltage is 24V.
3 Indicates the direction of current flowing into the generator side during generator failure occurrence.
Indicates the direction of current being output from the generator side when the system is healthy.

Fig.71CGP1A01D2
The connection diagram shows concepts of the wiring only. Therefore, please note that there will have some difference
between the connection diagram and actual installation status of CT,VT and safety devices such as fuse, etc.
51
+ A01
Auxiliary B05
power supply Y Self diagnosis output
circuit A03 B06

B07 Overcurrent time-delayed element


X0 I
B08

B09 Overcurrent instantaneous element


X1 I
CB A17 B10

B11 Earth fault overcurrent element


IA 2 A18 X2 I
B12
ED A19
B13 Unbalance current element 1
IB 2 X3 INSC
67P A20
trip B14
direction A21 B15 Unbalance current element 2
X4 INSC
CT IC 2 A22 B16

C07 Voltage detecting element For


CGP1 + A15 X5 signaling
U
I0 C08
A16
C09 Over voltage element
X6 U
C10

C11 Under voltage element


X7 U
VT A11 C12

VAB C13 Under frequency element


A12
X8 f
VBC C14
ED A13
C15 Over frequency element
X9 f
C16

C17 Reverse power element


Xa P
+ E01 C18
+
DC110V DI1 B17 IOR IOR I
1 E03
Xb I OR INSC
OR NSC

Lock function by external control input B18 For trip


+ E02 OR UOR UOR
+ B19 fOR fOR P
DC110V DI2 Xc
1 E04
B20 Programmable output
Default setting at ex-works

G Generator
Communication card

B01 DA

B02 DB
(option)

Serial communication bus


B03 DG
A02
E B04 SLD
ED

1 The application voltage for terminal E-01, E-03 and terminal E-02, E-04 is 24V in case that the supplied auxiliary power voltage is 24V.
2 Indicates the direction of current flowing into the generator side during generator failure occurrence.
Indicates the direction of current being output from the generator side when the system is healthy.

Fig.72CGP1A03D2
The connection diagram shows concepts of the wiring only. Therefore, please note that there will have some difference
between the connection diagram and actual installation status of CT,VT and safety devices such as fuse, etc.
52
CGP2 Series GENERATOR PROTECTION RELAY
Type, rating and specification
Type name CGP2A01D2 CGP2A02D2
Phase current 5A
Line voltage 100120V
DC110VPermissible variable range 77143Vor DC24VPermissible variable range DC19.2V31.2V
Rating
Photo coupler input voltage Input voltage 24V is applicable only for the case that auxiliary power supply voltage is 24V.
In any other cases, only DC110V is applicable as for photo coupler input voltage.
Frequency 50Hz or 60Hz
Protective element 87G,40 87G
Minimum operation current LOCK0.41.0A0.2A step
Biased
Bias 1020%5% step
differential
Operation time INST60ms or less 0.10.5s 0.1s step
Impedance ZF LOCK5.050.0 0.5 step
Loss of
excitation Impedance ZB 0.44.0 0.04 step
Operation time 0.210s 0.1s step
DI lock time 0.15.0s 0.1s step
Setting
Output contact configuration Refer to the external connection diagram/Auto reset for all contacts Default setting at ex-works
Operation indicator LED hold All LED self-hold Default setting at ex-works
5101212.5152025304050607580100120125150200250300400500600750800100012001250
CT primary
150020002500300040005000600075008000[A]
100999V1V step10009990V10V step10.0k
VT primary
99.9kV0.1kV step100k300kV1kV step
VT secondary 100/3110/3115/3120/3100110115120V
Real time measurement Phase current3, Differential current, Line voltage, Phase, Frequency
Max.record Phase current3, Differential current, Line voltage
Fault record (operation value) Phase current3, Differential current, Line voltage, Phase
Display
Fault record (operation item) Record and indicate the operated elements.
Normal result:On the RUN LED (green) Status indication item No.400=No display.
Self-diagnosis CGP2
Abnormal result:Off the RUN LEDStatus indication item No.400=Display defects code
Forced operation Each output contact
Direct communication port Standard equipmentPC software for Direct communication:Option
Communication
Remote communication port Option For CC-LINK
Phase current circuit:Less than 0.5VA, Phase current circuit:Less than 0.5VA,
Voltage circuit:Less than 1.0VA, Auxiliary power supply circuit:
Auxiliary power supply circuit: at DC100V=Approx. 6W,
at DC100V=Approx. 6W, at AC100V=Approx. 12VA,
Burden (at rating)
at AC100V=Approx. 12VA, at DC220V=Approx. 6W,
at DC220V=Approx. 6W, at AC220V=Approx. 14VA
at AC220V=Approx. 14VA In case of installing communication card, add 2 VA.
In case of installing communication card, add 2 VA.
Mass Net weight of relay unit:Approx. 3.5kg, Including case:Approx. 4.5kg
Sample of external connection diagram Fig.8-1 Fig.8-2, 3

Please refer to the instruction manual regarding the details on this specification.

53
Characteristics
Items Condition Guaranteed performance
Biased differential Setting: Minimum operation value,
characteristic Bias and operation time for all elements = minimum
Setting value 5%
Minimum operation Input: One terminal feeding for neutral side or load side
Operation current ( called "one terminal feeding" in afterward)
value Loss of excitation element
Setting: All settings operation time = minimum Setting value 5%
ZF operation value
Input: Current=rated current12 constantly 10A
Loss of excitation element Ia=5A, Ib5A, Ia-Ib=10A Setting value 5%
ZB operation value Current phase: lag 270 against voltage
Loss of excitation element When measuring operation values, if voltage reaches 110V
or more with the 2rated current being constant, 105% or less of operation value
ZF reset value
measurement is realized by reducing the current with
Loss of excitation element
voltage being constant at 110V. 95% or more of operation value
Reset value ZB reset value
Biased differential Setting: Minimum operation value,
characteristic Bias and operation time for all elements = minimum 95% or more of operation value
Reset value Input: One terminal feeding
Setting: Minimum operation current=minimum,
Biased differential At INST setting: 60ms or less
Bias=minimum, all operation time settings
characteristic At 0.10.5s setting: setting value 20ms
Input: One terminal feeding condition 0(A) minimum operation current300%.
Operation
Setting: ZF,ZB=minimum, all operation time settings
time
Loss of excitation Input: Current=0 Arated current12 constantly 10A, In case of setting value 0.2s0.4s, setting value20ms
element Voltage=110V40 V In case of setting value 0.5s or more, setting value5%
Current phase: lag 270against voltage
Setting: Minimum operation current=minimum,
Biased differential Bias=minimum, all operation time settings
200ms20ms
characteristic Input: One terminal feeding condition,
minimum operation current300%0 A.
CGP2 Reset time
Setting: ZF,ZB=minimum, all operation time settings
Loss of excitation Input: Current=rated current12 constantly 10A0 A,
200ms20ms
element Voltage=40V110 V
Current phase: lag 270against voltage

Setting: Minimum operation value, Bias and operation time for Bias setting I1 Bias
10% 11A
Biased differential characteristic all elements 15% 11.5A I2=10A
5%
Bias characteristic Input: Fixed I1 according to right side table and vary I2 20% 12A

Input: Fixed I1 to 30A and vary I2 I2:15A10%


Setting: Minimum operation current = minimum,
Biased differential Bias10%:174.35
Bias and operation time for all elements = minimum
characteristic Bias15%:171.45
Input: Fixed I1 and I2 to 10A and vary the phase between
Bias20%:168.55
I1 and I2, measure operating angle.
Phase
characteristic Setting: ZF, ZB=minimum, operation time=minimum
In the inputting theoretic operation value,
Input current=rated current2 constantly10AIA=5A,IB=5A, IAIB=10A
theoretic phase angle value5% and theoretic
Loss of excitation element The characteristics control points: 2 pointslag 240
and 300
against voltage.
operation value5% at the characteristic
For the method of seeking the operation theoretic value,
control point.
refer to the instruction manual.
Loss of excitation element ZF V-I characteristic Setting: Minimum operation time for all elements Setting value 5%
Loss of excitation element ZB Input current=0.8A40ANo operation below 0.8A
Setting value 5%
V-I characteristic Current=lag 270 against voltage
Loss of excitation element, 51 stopper operation value Common condition 0.8A5%

Please refer to the instruction manual regarding the details on this specification.

54
Precaution for application
1. Guarantee against interruption of AC power supply necessary for communication (CC-Link) is option. In case of retrofit
When an uninterruptible AC power source is not available in your existing relay with communication card, please inform the followings
system for the auxiliary power supply, use the type B-T1 AC/DC of existing relay. a:Type, b:Style number, c:Manufacturing year,
converter or commercially available uninterruptible power supply d:Serial number, e:Date of stamp on the checking seal (The above
(UPS). In addition, possible duration of the power supply type B-T1 mentioned items a.d. are indicated on the bottom right of front face
AC/DC converter is confirmed as about 2 seconds in combination of the relay and item e. is indicated on the upper of back side of the
with one MELPRO-D series relay. Therefore, in the case that the relay.) The version number of CC-Link is 1.00.
required duration of power supply after power source loss exceeds 2 7. Improvement of reliability of protection system
seconds, please use a suitable commercial uninterruptible power For the important facilities, multiplex system such as dual should be
supply. When power supply back up for the circuit breaker is provided to improve reliability.
required, it is necessary to prepare the power supply independent 8. Effects of external surge
from the type B-T1 AC/DC converter. Some type of surge with a certain condition may inversely affect the
2. Inrush current of power supply relay. If so, take it into account to install surge absorbers.
Since inrush current (about 2ms duration) as below may flow into the 9. The external wiring should be done according to the connection
relay when the power supply is turned on, please make a diagram of each relay. If a wrong wiring would be made, there are
consideration on this regard for selection of power circuit breaker. some possibilities that causing of the differential current and
Input voltage Inrush current Ip improper operation of loss of excitation element.
DC110V Approx. 20A 10. Lock function by external control input
DC220V Approx. 55A Two DI circuits are installed for the interlock by external control
AC100V Approx. 25A signals, and a relay element can be locked by DI input. Moreover, the
AC220V Approx. 65A relay element locked at the time of DI input arising can be set up to
each DI circuit.
3. Trip circuit 11. In case of application of the loss of excitation element only, wiring
Only the dedicated contacts can be used for the circuit breaker trip should be made for the VT circuit Vab, CT circuits Ia (terminal
circuit. Please keep in mind that the contacts for signaling can not be numberA17-A18), Ib ( terminal numberA19 - A20) and not
used for the trip circuit. (If used, the contact may burn). Also, connect necessary to make a wiring for other terminals.
the pallet contact (52a) of the circuit breaker to the trip coil circuit in 12. The DI input for interlock (Terminal number E-01,E-03 and
series. E-02,E-04) has a polarity. Therefore, please pay attention to
4. Self-diagnosis output circuit polarity as the input signals can not be detected properly due to the
The self-diagnosis output contact is so configured that the auxiliary wrong connection of DI circuit. CGP2
relay is energized ( break contact opened ) when normal result of 13. The differential current, caused by the flow-through current ( due to
self-diagnosis is received. This type of contact will allow the relay to inrush current of transformer or faults current) of CT which has
output abnormal result even after the built-in power failures. different saturated characteristics for each other and are located in
Therefore, the break contact is still closed in the aftermath of the the neural point and load side of generator, will become cause of miss-
power applying and will be opened after 50ms. If the auxiliary power operation of the relay. To prevent from such an incorrect operation, it
of the relay and the self-diagnosis output contact feed from a same is recommended to apply the CT in which accuracy limit factor is
power source, the break contact will be closed temporarily after more than 20 and accuracy is 1P class or 1PS class.
auxiliary power supply is turned on. In this case where the 14. Despite of no faults in the excitation circuit, the calculated
phenomenon stated in the above would conflict with your system impedance in the relay will be closed to the operation area and the
requirement, it is recommended that the self-diagnosis output contact loss of excitation element will operate due to unbalance of 3 phases
should be connected via the time-delay timer. PT circuit voltage (caused by a broken wire for example) or
5. Grounding circuit unbalance of burden for each phase. To prevent from such incorrect
Be sure to make a wiring to the earth terminal located on the back of operation, it is recommended to apply the voltage balance relay.
the relay according to the Class D earth wiring method (Grounding 15. When the differential current check is detected (contact X4 is in
resistance should be less than 100 ohm). operation and differential check LED is in lit condition), careful
6. CC-Link communication circuit checking of external wiring is requested as there are a possibility to
Please include the communication card into your purchasing order in have some mistake of the wiring.
case of the application of the communication facility as the card

Precaution for using


1. When the product is shipped from the factory, each setting value is 3. When current input for the loss of excitation element is derived from
LOCK (for element with LOCK position) or minimum setting the generator neutral point side, the phase current measuring does
value(for element without LOCK position) not indicate outgoing current but incoming current.
2. To set as [LOCK] position means to set the element out of use.

Precaution for safety


Please refer to page2 and 3 regarding the safty information and request
when placing order.

55
Sample of external connection diagram

A B C + A01
Auxiliary B05
power supply Y Self diagnosis output
circuit A03 B06

VT A09 B15
X4 Differential current check
VAB B16
A10
B07
ED X0 Biased differential A phase
A17 B08

B09
A18 X1 Biased differential B phase
B10
IA A19 For
B11 signaling
X2 Biased differential C phase
A20
B12
IB A21 B13
X3 Loss of excitation
A22 B14

CT IC B17
Biased differential or
X5
Loss of excitation
B18
For trip
ED B19
Biased differential or
CGP2 X6
Loss of excitation
B20
Generator G Programmable output
Default setting at ex-works

ED
CT A15

A16

IC A13

A14

IB A11

A12

IA

+ E01
+
DC110V DI1
1 E03

DI operation lock function + E02


+
Communication card

N.G.R B01 DA
DC110V DI2
1 E04
B02 DB
(option)

Serial communication bus


B03 DG
A02
E B04 SLD
ED

1 The application voltage for terminal E-01, E-03 and terminal E-02, E-04 is 24V in case that the supplied auxiliary power voltage is 24V.

Fig.81CGP2A01D2
The connection diagram shows concepts of the wiring only. Therefore, please note that there will have some difference
between the connection diagram and actual installation status of CT,VT and safety devices such as fuse, etc.
56
A B C + A01
Auxiliary B05
power supply Y Self diagnosis output
circuit A03 B06

VT A09 B15
X4 Differential current check
VAB B16
A10
B07
ED X0 Biased differential A phase
A17 B08

B09
A18 X1 Biased differential B phase
B10
IA A19 For
B11 signaling
X2 Biased differential C phase
A20
B12
IB A21 B13
X3 Loss of excitation
A22 B14

CT B17
Biased differential or
X5
Loss of excitation
B18
For trip
ED B19
Biased differential or
X6 CGP2
Loss of excitation
B20
Generator G Programmable output
Default setting at ex-works

A15

A16

A13

A14

A11

A12

+ E01
+
DC110V DI1
1 E03

DI operation lock function + E02


+
Communication card

N.G.R B01 DA
DC110V DI2
1 E04
B02 DB
(option)

Serial communication bus


B03 DG
A02
E B04 SLD
ED

1 The application voltage for terminal E-01, E-03 and terminal E-02, E-04 is 24V in case that the supplied auxiliary power voltage is 24V.

Fig.82CGP2A01D2Apply only 40 element


The connection diagram shows concepts of the wiring only. Therefore, please note that there will have some difference
between the connection diagram and actual installation status of CT,VT and safety devices such as fuse, etc.
57
A B C + A01
Auxiliary B05
power supply Y Self diagnosis output
circuit A03 B06

B15
X4 Differential current check
B16

B07
X0 Biased differential A phase
A17 B08

B09
A18 X1 Biased differential B phase
B10 For
IA A19 signaling
B11
X2 Biased differential C phase
A20
B12
IB A21 B13
X3 Biased differential for all phases OR
A22 B14

CT B17
IC
X5 Biased differential for all phases OR
B18
For trip
ED B19
CGP2 X6 Biased differential for all phases OR
B20
Generator G Programmable output
Default setting at ex-works

ED
CT A15

A16

IC A13

A14

IB A11

A12

IA

+ E01
+
DC110V DI1
1 E03

DI operation lock function + E02


+
Communication card

N.G.R B01 DA
DC110V DI2
1 E04
B02 DB
(option)

Serial communication bus


B03 DG
A02
E B04 SLD
ED

1 The application voltage for terminal E-01, E-03 and terminal E-02, E-04 is 24V in case that the supplied auxiliary power voltage is 24V.

Fig.83CGP2A02D2
The connection diagram shows concepts of the wiring only. Therefore, please note that there will have some difference
between the connection diagram and actual installation status of CT,VT and safety devices such as fuse, etc.
58
MELPROD Series Dimensions
A 35 203 C

46 holes B Case type A B C


(185) (18)
D 1 151 114 130

D 2 251 214 230


2 out of 3
relay case 351 314 330
205

184

150

194
M3.5 screws
4M5 screws
Dimension in mm

CPS1

59
Suggestion From Mitsubishi Electric
(for improving reliability of system)
As a way to improve the realiability of Protection system,
MITSUBISHI ELECTRIC also provides customers the following products.
Reduntant fault detection system
2 out of 3 methodThe method that the power system faults are detected by at least 2 relays among 3-
relay set.
In this way, the power system faults can be detected when 2 relays operate, even if
the other relay is in failure. (refer to the following concept diagram)

COFIGURATION CONCEPT

Ry 1
Ry 1 Ry 2 Ry 3
Ry 2 Trip
Ry 2 Ry 3 Ry 1
Ry 3

Trip

We provide a compact unit integrating 3 relays in one case.

60
Control and Operation

Item Data LED


Item No. indicator LED
RUN LED
Communication LED

Unit LED
Phase LED
Setting/Cancel switch
Select/Set switch
Setting/Cancel indicator LED
UP switch
Setting End/Trip switch
DOWN switch
Setting End/Trip LED Indication/
Indication End switch
Operation Indicator
Reset switch

Operation Indicator LEDs

Direct communication port

Explanation of Front panel


No. Designation Symbol Description
Pressing this switch will start the procedure for setting, forced operation or option.
Setting/Cancel When this switch is pressed again instead of the SET.END/TRIP switch, data that
SETTING/CANCEL
has been programmed will be all cleared to terminate the selected procedure.The
SETTING/CANCEL indicator LED is lit during the procedure.
This switch is used to select an item number and program item data
during setting, forced operation or option procedure.
Operational key switches

Select/Set SELECT/SET
When data is programmed to be ready for replacing the currently used
setting, the SET.END/TRIP LED will blink.
When the SET.END/TRIP switch is pressed with its LED blinking during
Setting End/Trip SET.END/TRIP setting, forced operation or option procedure, the current setting will be
replaced by data given by programming. The new setting will be thus enabled.

UP These switches are used for selecting data elements. Pressing these
UP select
switches for a while will allow fast forward.
With the cover operating button, you can use the switches without
DOWN select DOWN removing the cover.
Pressing this switch will start or end the display of settings and
Indication/Indication End IND./IND.END measurements. With the cover operating button, you can use the switches
without removing the cover.
Pressing this switch will reset output contacts after the relay operated and
Reset RESET extinguish the operation indicator LEDs. With the cover operating button,
you can use the switches without removing the cover.
A number allocated to the selected setting, forced operation or option item
Item No. Green is indicated here.
Data that corresponds to the item number selected is displayed here. For
Item Data Red the indication of individual letters, see the instruction manual specifically
prepared for each model.
Indicate the result of the auto self-check. The lamp will be lit for normal
RUN Green
Indicator LEDs

conditions while off for abnormal conditions.


Indicate the operational status of the communication card.
With a communication card installed: the lamp will be lit for normal
Communication Green conditions, blinking during communication and off for abnormal conditions.
With a communication card not installed: the lamp will be off.
Unit Yellow Indicate the unit used for the item data.
Phase Yellow Indicate the phase that corresponds to the item data.
Setting/Cancel Yellow This lamp will be lit during setting, forced operation or option procedure.
Setting End/Trip Yellow This lamp will blink when new data is programmed to be ready for
replacing the current setting.
Operation Red Indicate the applicable operation elements and phases of the relay.
This port is used for connecting PC and relay with the dedicated cable
Direct communication port (option). The measuring values, operating conditions and setting changes
can be done by PC with the dedicated software (option).

61
62
Display/Setting Operation
Initial status Start display Select ITEM No. Exit display status

ITEM
ITEM DATA
No.

Note:
SETTING SETTING SETTING SETTING
UP UP UP UP 1) In setting status, to change the group of ITEM No. (500700800)
CANSEL CANSEL CANSEL CANSEL
SELECT SELECT SELECT SELECT
DOWN DOWN DOWN DOWN 2) Plural items can be
SET SET SET SET set at one time.
SET.END IND. SET.END IND. SET.END IND. SET.END IND.
UP
(same setting
IND. IND. IND. IND.
TRIP TRIP TRIP TRIP

DISPLAY
END END END END group only)
OPERATION INDICATOR OPERATION INDICATOR OPERATION INDICATOR OPERATION INDICATOR
(to display the
DOWN last number of Release Press and hold (1s) Release
RESET RESET RESET RESET beginning group)

Nothing displayed at windows Start to display the ITEM No. and Select ITEM No. by UP or DOWN, Exit the display status by
of ITEM No. and ITEM DATA ITEM DATA by pushing IND/IND END ITEM DATA displayed. pushing IND/IND END

Initial status Start setting Select ITEM No. Set ITEM No. Select setting value Admit setting value Make setting value effect

ITEM ITEM ITEM ITEM ITEM ITEM ITEM


ITEM DATA ITEM DATA ITEM DATA ITEM DATA ITEM DATA ITEM DATA ITEM DATA
No. No. No. No. No. No. No.

SETTING SETTING SETTING SETTING SETTING SETTING SETTING


UP UP UP UP UP UP UP
CANSEL CANSEL CANSEL CANSEL CANSEL CANSEL CANSEL
SELECT SELECT SELECT SELECT SELECT SELECT SELECT
DOWN DOWN DOWN DOWN DOWN DOWN DOWN
SET SET SET SET SET SET SET
SET.END IND. SET.END IND. SET.END IND. SET.END IND. SET.END IND. SET.END IND. SET.END IND.
IND. IND. IND. IND. IND. IND. IND.
TRIP END TRIP END TRIP END TRIP END TRIP END TRIP END TRIP END

OPERATION INDICATOR OPERATION INDICATOR OPERATION INDICATOR OPERATION INDICATOR OPERATION INDICATOR OPERATION INDICATOR OPERATION INDICATOR

RESET RESET RESET RESET RESET RESET RESET

Nothing displayed at windows Select ITEM No. by UP or DOWN. Select setting value by UP or Set the selected setting value. All selected setting value are
of ITEM No. and ITEM DATA (ITEM No. LED blinking) DOWN. Please note that selected setting effective by this operation.
(ITEM DATA LED blinking) value is not effective at this moment.

SETTING
ITEM No. ITEM DATA
ITEM
ITEM No. ITEM DATA ITEM DATA
No.

SETTING
UP SETTING
CANSEL SETTING SETTING
UP
CANSEL UP UP
CANSEL CANSEL
SELECT SELECT
DOWN DOWN
SET SET
SET.END IND. SET.END IND.
IND. IND.
TRIP END TRIP END

All indications are changed to


turning off condition.
Please repeat the same operation in case of two or more items setting
(The above is applicable only for the same group classified with the same number of top digit.)

When the product is shipped from the factory, each setting value is "LOCK" (for element with LOCK position) or "minimum setting value" (for element without LOCK position), therefore, please
make new setting as you wish according to the above mentioned procedure for each element.
Safety section
This Safety section should be read before starting any work on the relay. Be sure to read the instruction
manuals and other related documents prior to commencing any work on the relay in order to maintain them
in a safe condition. Be sure to be familiar with the knowledge, safety information and all caution items of the
product prior to use.

CAUTION Caution means that failure to un-observe safety information, incorrect use, or improper use may endanger personnel and equipment and cause personnel injury or physical damage.
Items as classified to the caution may become to occur more sever results according to the circumstance. Therefore, all items described
in the safety section are important and to be respected without fail.

CAUTION
1. Items concerning transportation
(1) Be sure the equipment to be kept in normal direction
(2) Avoid the bumps, shock, and vibration, otherwise the product performance /life might be unfavorably affected.
2. Items concerning storage
(1) Environment shall be as below, otherwise the product performance/life might be unfavorably affected.
-Ambient temperature: -20+60(with no condensation nor freezing)
-Relative humidity: 3080% average of a day
-Altitude: Less than 2000m
-Avoid applying unusual shock, vibration or leaning or magnetic field
-Not expose to harmful smoke, gas, salty air, water, vapor, dust, powder, explosive material or wind, rain.
3. Items concerning mounting/wiring work
(1) Mounting and wiring work should be done correctly. Otherwise, damage, burning or erroneous operation might occur.
(2) Screw terminal should be tightened securely. Otherwise, damage and burning might occur.
(3) Grounding should be done correctly in case it is required. Otherwise, electric shock, damage, burning or erroneous operation might occur.
(4) Wiring should be done without mistake especially observing the correct polarity. Otherwise, damage, burning or erroneous operation might
occur.
(5) Wiring should be done without mistake especially observing the phase ordering. Otherwise, damage, or erroneous operation might occur.
(6) Auxiliary power source, measuring transformer and power source which have enough capacity for correct operation of product should be used.
Otherwise, an erroneous operation might occur.
(7) Be sure to restore the front cover, terminal cover, protection cover, etc to the original position, which have been removed during the mounting/
wiring work. Otherwise, electrical shock might occur at the time of checking.
(8) Connection should be done correctly using designated and right connectors. Otherwise, damage or burning might occur.
(9) Fully insert the sub unit into the case until you can hear a click while pressing the handles located on both sides of the sub unit front face.
Otherwise, incomplete inserting the sub unit might only establish a poor contact with the terminals located on the back side of unit, which might
cause erroneous operation or heating.
4. Concerning equipment operation and settings
(1) Operational condition should be as below. Otherwise, the product performance/life might be unfavorably affected.
-Deviation of auxiliary power: within +10%-15% of rated voltage
-Deviation of frequency: within 5%of rated frequency
-Ambient temperature: 0+40(-10+50 is permissible during couples of hour per day, with no condensation nor freezing)
-Relative humidity: 3080% average of a day
-Altitude: Less than 2000m
-Avoid to be exposed to unusual shock, vibration, leaning or magnetic field
-Not expose to harmful smoke, gas, salty air, water, vapor, dust, powder, explosive material, wind or rain.
(2) Qualified personnel may work on or operate this product, otherwise, the product performance/life might be unfavorably affected and/or
burning or erroneous operation might occur.
(3) Be sure to read and understand the instruction manuals and other related documents prior to commencing operation and maintenance work on
the product. Otherwise, electrical shock, injury, damage, or erroneous operation might occur.
(4) While energizing product, be sure not to remove any unit or parts without permissible one. Otherwise, damage, or erroneous operation might
occur.
(5) While energizing product, be sure to make short circuit of current transformer secondary circuits before setting change or drawing out the sub
unit. Otherwise, secondary circuit of live current transformer might be opened and damage or burning might occur due to the high level
voltage.
(6) While energizing product, be sure to open trip lock terminal before setting change or drawing out the internal unit of product. Otherwise,
erroneous operation might occur.
(7) Be sure to use the product within rated voltage and current. Otherwise, damage or erroneous operation might occur.
(8) While energizing product, be sure not to clean up the product. Only wiping a stain on the front cover of product with a damp waste might be
allowable. (Be sure to wring hardly the water out of the waste.)
5. Items concerning maintenance and checking
(1) Be sure that only qualified personnel might work on or operate this product. Otherwise, electrical shock, injury, damage, or erroneous operation
might occur.
(2) Be sure to read and understand the instruction manuals and other related documents prior to commencing operation and maintenance work on
the product. Otherwise, electrical shock, injury, damage, or erroneous operation might occur.
(3) In case of replacing the parts, be sure to use the ones of same type, rating and specifications, etc. If impossible to use above parts, be sure to
contact the sales office or distributor nearest you. Otherwise, damage or burning might occur.
(4) Testing shall be done with the following conditions.
-Ambient temperature: 2010
-Relative humidity: Less than 90%
-Magnetic field: Less than 80A/m
-Atmospheric pressure: 86106103 Pa
-Installation angle: Normal direction2
-Deviation of frequency: within 1%of nominal frequency
-Wave form (in case of AC): Distortion factor less than 2% (Distortion factor=100%effective value of harmonics/effective value of fundamental)
-Ripple (in case of DC): Ripple factor less than 3% (Ripple factor=100%(max-min)/average of DC)
-Deviation of auxiliary power: within 2% of nominal voltage
-Be sure not to inject the voltage or current beyond the overload immunity. Otherwise, damage or burning might occur.
-Be careful not to touch the energized parts. Otherwise, the electric shock might occur.
6. Items concerning modification and/or repair work
Be sure to ask any modification and/or repair work for product to the sales office or distributor nearest you.
Unless otherwise, any incidents occurred with modification or repair works (including software) done by any other entity than MITSUBIHI
ELECTRIC CORPORATION shall be out of scope on warranty covered by MITSUBISHI ELECTRIC CORPORATION.
7. Items concerning disposal
Particular regulations within the country of operation shall be applied to the disposal.

2 63
MITSUBISHI Numerical Protection Relay
MELPRO -D Series TM

MITSUBISHI Numerical Protection Relay


MELPRO -D Series TM

MELPRO -D TM

Mitsubishi ELectric corporation's PROtection relay for Distribution.

Relays suitable for advanced network


HEAD OFFICE : 7-3 MARUNOUCHI 2-CHOME, CHIYODA-KU systems and strongly support power
TOKYO, 100-8310, JAPAN
CAUTION distribution automation.
TO PREVENT IT FROM THE RISK OF DAMAGE AND MAL FUNCTION,
BE SURE TO READ OPERATING AND MAINTENANCE (SERVICING)
INSTRUCTIONS BEFORE USING.
We are waiting your technical contacts by FAX.
ATTN. Protective relay technical service
FAX NO. JAPAN +81-78-996-7074

SE-E840-C(11.03-1.0)ROS "MELPRO" is a trademark of the Mitsubishi Electric Corporation.


This printed matter has been published March 2011. Please note that specifications are subject to change without notice. Published Mar.2011