Me JOSLYN CLARK CONTROLS, INC. aaazia Diesel Engine Fire Pump Controllers Features: GENERAL Joslyn Clark Diesel Fire Pump Controliers are designed and listed specifically for diasel engine driven fire pump service. These controllers meet ar exceed all toquitements Of the National Fire Protection Association Stancara NEPA 20, are listed by Underwriters Laboratories Ine and are approved by the Factory Mutual System The diese! controtlor provides four (4) major functions: * Starts the diesel engine automatically from water oF nonaurtomatically irom pressure contr ‘manual electsic control * Initiates a weekly program test of the system + Monitors engine as well as systom conditions * Maintains charge on engine starting batteries (ovheo provided with a battery charger) STYLISH COMPACT ENCLOSURE Suited for floor of wall mounting. Space saving in Crowded pump rooms. Dripproat NEAT AND CLEAN APPEARANCE Fee exterior with white interior for best visibility. MODERN Meets current NFPA 20 Standard: FM approved RELIABLE Hybrid electromechanical/solid state circuitry, MAGNETIC RELAYS ARE PLUG-IN ENCLOSED DUSTTIGHT TYPE Applied in circuits best suited ta relay logic, SOLID STATE CRANK CYCLE CONTROL Very reliable, tamper resistant, non-adjustable DUAL BATTERY CHARGER Reliable solid state with current limit contotied 24 hour charge rate capable of simultaneously eharging two 180-225 ampere hour batteries VOLTAGE SENSING UNIT FLOOR MOUNTING ‘Aways powers the control circuit rom the strongest battery to minimize relay thiter often caused by tow voltage WELL ORGANIZED COMPONENT LAYOUT Piping connection, pressure swith, and solenoid drain vale ata located in lower portion of controller to heap water carrying components weil away trom vlacte fosiyn Clark Fire Pump Controlirs for diesel engine devices ~ maels FM requirements and electric motor driven fire punips are desire assembled, wired, and tested by COMPLETE DESIGN Joslyn Clark Controls. INC. Circuits availabe forall isted fire pump engines, P.O. Box 945, ‘including a full assortment of accessories and built-in Lancaster, SC 29720 fications. a0 35-8491 JOSLYN CLARK CONTROLS, INC. BULLETIN 10710 Diesel Engine Fire Pump Controllers Standard Equipment and Performance + Automatic start rasponsive to water pressure + Nonautomati sta from manual elects contol behind break-glass panel for emergency stat ‘Weekly program timer to initiate a weekly automatic: start of the engine and its contraller Signal fights and audible alarm to monitor + Controller set in AUTOMATIC (no audible alara) + Low Ou Pressure * Hot Engine Water + Failure to Start + Overspeed * Battery No.1 Failure + Gallery No.2 Failure * Charger Loss Contacts (SPDT) provided for remote alarm of + Engine Failure - common contacts for alarm ot any of the above failures ‘+ Engine Running ‘+ Controller sat in MANUAL or OFF Control circuit power is always supplied from the strongest battery Crank eycle conto is fully solid state plug-in, tamper resistant, no moving parts, no field adjustment + Plug-in magnetic relays aro dusttight enclosed for standard O1-On logic, no latch or ratenet types are used Terminal boards are conveniently located for field accessible wiring Battery No. 1 Voltmeter Battery No. 3 Ammeter ‘Ausible Aiarm Wiring Diagram Weokly Program Timer « Automatic Stop Timer « Break Glass Pane! Lock Type Door Handle * Schematic Diagram * sure Recorder * Document Pouch « Standard controler requires @ 120 voit, 60 Hz, supply from a reliable separate 20 ampere clicuit, 50 He" ‘operation and builtin step down transtormers from higher voltages are available options. “# Piping connection, solenoid drain value, pressure ‘switch, and optional pressure recorder are located below and away from electrical components Standard internal plumbing is rated 600 psi servic: Pressure suitch and soleneid drain valve are rated 300 si service. Optional 600 psi pressure switen and drain valve are available Dripproot, tockable, enciosure is 14 gauge slee! fed baked ename! painted exterior resists damp Pump room environment; white interior provides good sibility of internat components, Wiring and schomatic diagrams are atached to inside of enciosure door for ready reference Document ouch provides convenient storage for service manuals and ecards Standard onctosure is suitable for lloor oF wall mounting a price savings ts realized by specifying wall mounting, Controller weight without battery charger or floor stant 120 tbs. Add for 12V Battery Charger 28 Ibs ‘Ad for 24v Battery Charger 40 Ibs, ‘Add for Pressure Recorder 6 lbs ‘Add for Floor Mounting Legs Tbs Battery No. 2 Ammeter Battery No 2 Voltmeter Alarm Silence Switen Battery Charger Reset Button Stop Button Bontrol Sel Monitor Lights Switeh Crank Cycle Control Control Relays ++ Como! Terminal Boards Prossure Switch Solenoid Drain Valve WALL MOUNTING toy JOSLYN CLARK CONTROLS, INC. BULLETIN @@ 10710 Diesel Engine Fire Pump Controllers Factory Installed Modifications ‘A’ Wall Mounting Enclosure; standard enclosure Supplied without floor stand. Battery chargers are reliable solid state with current limit controlled 24 hour charge rate capable of simultancousty charging two 150-225 ampere hour, 12 or 24 voll, Lead- Acid or Nicad batteries. They include 2 armmeters, 2 voltmeters, and "Loss of Charger” alatm 8 Dual Battery Charger for Lead-Acid Batteries © Dual lery Chargor for Nicad Batteries” 0 Omit 2 Voltmeters trom Battery Charger Pressure Recorders are seven (7) day chart, AC driven, Units wit Provide up to 60 hours of recording atter AC loss. E1300 psi Pressure Recorder 2 300 psi Pressure Recorder with Spring Motor Backup FT 600 psl Pressure Recorder F2_ 500s! Pressure Recorder with Spring Motor Backup G Automatic Stop. Adjustable (20 to 60 minutes) run Period timer provides automatic shutdown after all automatic start causes have returned to normal and engine has run for at least the run period setting, Terminal board jumper is provided for field conversion to manu! stop. 11 Remote Start. Drop-out relay allows remote start of Contrater when one or more contacts are opened on deluge valves, dry pipo valves, tlow switches, romate start push buttons, etc Effective only when control Isin AUTO, J Power Failure Start. Non-adjustable time delay relay starts controller after 30 seconds of loss of AC power "put a loss of battery charger output Effective anty when controller is in AUTO, K_ Engine Lockout. Prevents controller from starting when relay is energized from external 120 VAC source, typically in event of low suction pressure, low reservoir level, ete. Effective only in AUTO and TEST positions {Sequence Start. Adjustable (0 to 30 seconds) time elay relay provided in each controller of a multiple ‘Pump system permits sequential starting. adjustiment should be §-10 seconds to allow preceding pump to Start Failure of preceding pump does not prevent start of subsequent pump(s). Effective only in AUTO and TEST positions spring motor backup are AC motor wound aad Pump House Local Alarm and Signal Lights in controilor provide local avaible alarm and individual signal lights for ‘monitoring pump nouse supervisory alarm conditions, Pump House Local Alarm and Signal Lights with Individual Contacts tor Remote Signalling also provide SPDT contacts for remote signalling of each (maximum of 4) alarm condition. Option P, Pump House Local Alarm Silence Switch must be specified for “Silence Switc and common-for-all SPOT contacts for remotesignalling Accessory input devices must be separately specified and ordered, with Signal With Signat Lights Only Lights and Indiviguat Contacts Mt Low Fuel Love! co M2 Low Pump House Temp M2 M3 Relief Valve Discharge M13 ma Flow Meter On mis MS Reservoir Low Mis Me Reservoir Emply ws. M7 Low Suction Pressure MAT mo Other (specityy une N_ Pump House Temperature Switch* mounted and wired on controller, Adjustable switch can be sat to close at 36°F to 74°F. Wired to terminal blocks Pump House Local Alarm Silence Switch and ‘common-for-all SPDT contacts for remote alarm of ump house supervisory alarm conditions. Required ‘with Options M2 through M18 and optional with Option M1. Battery Falture Remote Alarm Relay. Provides SPDT Contacts for remote alarm of failure of either battery. S_ Individuel Engine Failure Alarm Contacts. Provides individuat SPDT contacts for remote signalling of each of all engine failures, Low Oit Pressure Hot Engine Water Failure to Start Overspeed Battery No. 1 Failure Batiory No. 2 Failure Loss of Charger T Extra Engine Running Contacts. Provides second set (one included as standard} of SPOT contacts tor Additional remote indication. Required when Bulletin 10865 Type D “Low Suction Pressure Cut Off and Alarm Pane” is installed in conjunction with engine controller ‘Space Heaters are 120 VAC input, 100 Watt output, with Control and devices mounted in controller, W1 Space Heater with Humidistat and Thermostat‘# W2 Space Heater with Thermostat"# See Price Sheet tor Catalog Numbering System and Drserina lastructinns JOSLYN CLARK CONTROLS, INC. Diesel Engine Fire Pump Controllers Enclosure Modifications Drawing Reterenc Dimensions and Modifications _410.954720 ‘Standard Outine Drawing A1o-asazo4 Outdoarfindoor Outing Drawing A10-384756 ‘Alarm Panel Dimensions At0-s06963, Alarm Panel Interconnection A1D-BB47S Accessories for Remote Mounting Remote Alarm Panel NFPA-20 requires that when the pump room is not Constantly attended, audible or visible alarms powered by @ source other than the engine starting batteries and net exceeding 125 Volts, shall be provided at @ point of Constant attendance, Bulletin 10720 Alarm Panat Fequires 120 VAC power source to supply the signal lights and auaibfe atarm for four (2) standard functions: "Power On." "Engine Running,” “Engine Failure,” and *Controlier Off." Standard enclosure accommodates tour (4) additional lights, optional ‘enclosures available for up to twanty (20) total lights Low Fuel Level Switch This oat switch screws into the tank through @ Standard 2" pipe thread tank opening and Provides an alarm signal when. fuel levet drops to 80% of | --~ ) tho tank capacity CO. Te When ordering, tank C dimensions and type aa { = Standard Dripproot Enclosure Outline including optional floor stand. Controtter Drawings: Engine Interconnection Schematic Cumming Models NSSF. V-978F1, Aloas47021 Brogsa6ot-4 V-s78-2, V.50¢F', ¥-804-F2! and VIBE Mocels NT-855F3, NT-SSSF4, A10-954702-2 B10-954601.2 NTASSS-6, NTTASSS5 ane) NTaasF GM, Clarke GM, and 109547024 B10-254601-1 Mviid Murphy, Caterpiiar 109547023 B10-954601.2 BULLETIN 10720 Standard Alarm Pane! (oth “Low Fost Ligh Joslyn Clark Fire Pump Controers for diesel engine nd electric motor driven fie pumps are designed, ‘assembled, wired, and tested by: Joslyn Clark Controls, INC. P.O. Box 945 Lancaster, SC 29720 (803) 286-8491

You might also like