Professional Documents
Culture Documents
CONTENTS PAGES
1. Description, use................................... 1
2. Range ................................................. 1
3. Dimensions ......................................... 1
4. Positioning - Connection ...................... 2
5. General characteristics ........................ 3
6. Equipment and accessories ................. 6
7. Compliance and Approvals .................. 7
1. DESCRIPTION - USE
USE 2. RANGE (continued)
Technology:
. Electromagnetic contactor (monostable relay) 3. DIMENSIONS
Use:
. For controlling a load remotely via a switch
2. RANGE
Types of contact:
. "NO" contact
. "NC" contact
Polarities:
. 2-pole in 1 module (17.8 mm)
- "2NO"
- "2NC"
- "NO+NC"
. 4-pole in 2 modules (35.6 mm)
- "4NO"
- "4NC"
- "2NO + 2NC"
- "3NO + 1 NC"
Operating position:
. Vertical, horizontal, flat (all positions)
Mounting:
. On symmetrical EN 50-055 rail or DIN 35 rail, using two plastic
clips.
Recommended tools:
. For the terminal screws: insulated or non-insulated screwdriver,
Pozidriv no. 1 or with a 4 mm blade.
. For attaching: screwdriver with blade (5.5 mm max) or Pozidriv
no. 1.
Positioning in a row:
. The product profile and positioning of the terminals allow single-
phase and three-phase toothed connection supply busbars to be
passed at the top of the product without impairing accessibility of the
contactor terminals. This way it is possible to select the position of
the pulse operated latching relay freely in the row and to connect the
circuit breakers located on the same rail via a supply busbar.
Contactor
Updated
Technical data sheet: F01332EN/00 Created on: 17/03/11
on:
2/7
16 A and 25 A power contactors Catalogue number(s): 4 125 03 / 04 / 05 / 09 / 10 / 14 /
17 / 21 / 22 / 23 / 24 / 33 / 34 / 35 / 36 / 44 / 51 and
with or without handle 927 02 / 03
Connection: Marking:
. Screw control and power terminals: By indelible pad printing
- Type of terminal: caged . Front panel
- Depth: 12 mm
- Capacity (h x w): 4.7 x 4.7 mm
- Compatible copper conductors
Rigid: 1 x (0.75 to 6 mm) or 2 x (0.75 to 2.5 mm)
Flexible without gland: 1 x (0.75 to 6 mm) or 2 x (0.75 to 2.5 mm)
Flexible with single gland: 1 x (0.75 to 6 mm)
Flexible with double gland: 2 x (0.75 to 4 mm)
- Screw head: mixed head Pozidriv no. 1 and 4 mm blade
- Screw head: mixed M3.5
- Min. tightening torque: 0.5 Nm/max.: 1.2 Nm recommended:
0.8 Nm
. Marking of the terminals:
Length of control lines: Power: 1 to 8 Control: A1 and A2
. with 24 V contactor: 330 m for 1-module contactor or 100 m for Upper terminals
2-module contactor with 1.5 mm cables
. with 230 V contactor: 250 m for 1-module contactor or 400 m for
2-module contactor regardless of the connection cable cross-
section.
Degree of protection:
. Terminals protected against direct contact: IP2x (wired device) Lower terminals
. Front panel protected against direct contact: IP3XD
. Class II, front panel with faceplate
. Protection against impacts: IK04
Resistance to tremors:
. No change in the status of the contacts during the "resistance to
tremors" test as defined by the standard EN 60898
Device handling:
. Via remote control (switch). By laser marking
. Via ergonomic 3-position handle (I, auto, O) if the product is fitted
. Upper panel
with one.
Degree of pollution:
. 2 in accordance with EN 61095
3/7
16A and 25A power contactors Catalogue number(s): 4 125 03 / 04 / 05 / 09 / 10 / 14 /
17 / 21 / 22 / 23 / 24
24 / 33 / 34 / 35 / 36 / 44 / 51 and
with or without handle 927 02 / 03
4/7
16 A and 25 A power contactors Catalogue number(s): 4 125 03 / 04 / 05 / 09 / 10 / 14 /
17 / 21 / 22 / 23 / 24 / 33 / 34 / 35 / 36 / 44 / 51 and
with or without handle 927 02 / 03
Enclosure material:
ELV halogen bulbs with electronic ballast
. Polyamide
Unit power 20 W 35 W 50 W 75 W 100 W 150 W
Plastic material characteristics: 16 A 60 40 28 18 14 9
. Compliance with the resistance to incandescent wire for 30 25 A 80 50 40 26 20 13
Packaged volume: Double series compensated fluorescent tubes with ferromagnetic ballast
. 0.2 dm3 for the 1-pole and 2-pole devices packaged in units Unit power 2 x 20 W 2 x 36 W 2 x 40 W 2 x 58 W 2 x 140
. 1.6 dm3 for the 1-pole and 2-pole devices packaged in packs of 10 16 A 30 24 22 15 6
. 0.4 dm3 for the 4-pole devices packaged in units 25 A 45 38 35 24 10
Contactor selection chart: Quadruple series compensated fluorescent tubes with ferromagnetic
For a 10-year service life with 200 days of usage per year ballast
. Heating Unit power 4 x 18 W
Maximum power depending on the number of operations per day (kW) 16 A 16
Number of operations per day 50 75 100 250 500 25 A 24
Single-phase heating 16 A 3,6 2.8
2.8 2.4
2.4 1.6
1.6 0.8
230 V~ 25 A 5,6 4.4
4.4 3.7
3.7 2.5
2.5 1.25
1.25 Compact fluorescent tubes with integrated starter for ferromagnetic
Three-phase heating ballast
25 A 16 13.
13.7 11.
11.3 5 3.7
3.7
400 V~ Unit power 7W 10 W 18 W 26 W
16 A 50 40 28 19
. Motors (AC-7b) 25 A 60 50 42 28
Maximum power (kW)
Single phase motor 16 A 1.5
1.5
230 V~ 25 A 2.3
2.3
Three-phase motor
25 A 4
400 V~
5/7
16 A and 25 A power contactors Catalogue number(s): 4 125 03 / 04 / 05 / 09 / 10 / 14 /
17 / 21 / 22 / 23 / 24 / 33 / 34 / 35 / 36 / 44 / 51 and
with or without handle 927 02 / 03
Metal halogenide
Unit power 35 W 70 W 100 W 150 W 250 W 400 W
16 A 10 6 5 3 2 1
25 A 15 9 7 5 3 2
6/7
16 A and 25 A power contactors number(s): 4 125 03 / 04 / 05 / 09 / 10 / 14 /
Catalogue number(s):
17 / 21 / 22 / 23 / 24 / 33 / 34 / 35 / 36 / 44 / 51 and
with or without handle 927 02 / 03
. Category F
Plastic materials:
. Plastic material without halogen.
. Labelling of parts compliant with ISO 11469 and ISO 1043.
Packaging:
. Design and manufacture of packaging compliant with decree
98-638 of 20/07/98 and Directive 94/62/EC
Approvals obtained:
. France: NF
7/7