Professional Documents
Culture Documents
ChilledBeams (ASHRAE Chapter Meeting, Jackson, Mar 2011) PDF
ChilledBeams (ASHRAE Chapter Meeting, Jackson, Mar 2011) PDF
High-Performance Systems
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
1
Passive or Active Chilled Beams
primary air
nozzles
coils
ceiling
induced air
induced air +
primary air
active chilled beam
water coil perforated
pipes metal casing
primary
OA air handler
RA
EA active
PA PA chilled beam
RA RA RA
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
2
active chilled beam systems compared to VAV systems
Summary of Todays Technical Session
Potential advantages of ACB Challenges of ACB
Smaller ductwork and High installed cost
smaller air handlers Need to prevent
Primary airflow < supply airflow, condensation
but likely > outdoor airflow Risk of water leaks
Low sound levels No filtration of local
Impact on overall system energy? recirculated air
Primary airflow < supply airflow, Limited heating capability
but constant airflow
Warm water for beams,
but cold water primary AHU
Increased pumping energy
No DCV, limited airside
economizing
10,000,000 Pumps
Fans
Heating
Annual Building Energy U
8,000,000 Cooling
Plug Loads
Lighting
6,000,000
4,000,000
2,000,000
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
3
office building
Example Energy Analysis
Baseline chilled-water VAV system
ASHRAE 90.1-2007, Appendix G (55F supply air)
Active chilled beam system
Four-pipe active chilled beams
Separate primary AHUs for perimeter and
interior areas (with SAT reset and economizers)
Separate water-cooled chiller plants
(low-flow plant supplying primary AHUs)
High-performance chilled-water VAV system
48F supply l air
i (d
(ductwork
t k nott downsized)
d i d)
Optimized VAV system controls
(ventilation optimization, SAT reset)
Parallel fan-powered VAV terminals
Low-flow, water-cooled chiller plant
High-Performance Systems
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
4
High Performance Chilled Beam Systems
How can active chilled beam systems be designed
differently for high performance?
ACB challenges
High Installed Cost
eight
i h (8) active
i chilled
hill d beams,
b
each 4-ft long x 2-ft wide
four (4) active chilled beams,
each 6-ft long x 2-ft wide
10
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
5
System design Impact on installed cost Impact on performance
variable of the chilled beams of the overall system
2-pipe versus 4-pipe A 2-pipe beam provides more cooling Using 2-pipe beams requires a separate
chilled beams capacity than a 4-pipe beam because more heating system, otherwise it can result in
coil surface is available poorer comfort control because either cold
water or warm water is delivered to all zones
Primary airflow rate Increasing the primary airflow rate through Increasing the primary airflow rate increases
(cfm) the nozzles results in more air being primary AHU fan energy use, increases noise
induced from the space
space, which increased in the space
space, and requires a larger primary
the capacity of the chilled beam coils AHU and larger ductwork
Inlet static pressure Increasing the static pressure at the inlet to Increasing the inlet pressure increases
of the primary air the nozzles results in more air being primary AHU fan energy use, and increases
induced from the space, which increased noise in the space
the capacity of the chilled beam coils
Dry-bulb temperature Delivering the primary air at a colder Using a colder primary-air temperature may
of the primary air temperature means that less of the space cause the space to overcool and low sensible
sensible cooling load needs to be offset by cooling loads, thus requiring the chilled beam
the chilled beams (or separate heating system) to add heat to
prevent overcooling space
Entering water Supplying colder water to the chilled beam Using a colder water temperature requires the
temperature increases the cooling capacity of the beam space dew point to be lower to avoid
condensation, which means the primary air
needs to be dehumidified to a lower dew point
Water flow rate Increasing the water flow rate increases the Increasing the water flow rate increases pump
(gpm) cooling capacity of the beam energy use and requires larger pipes and
pumps 11
12
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
6
System design Impact on installed cost Impact on performance
variable of the chilled beams of the overall system
2-pipe versus 4-pipe A 2-pipe beam provides more cooling Using 2-pipe beams requires a separate
chilled beams capacity than a 4-pipe beam because more heating system, otherwise it can result in
coil surface is available poorer comfort control because either cold
water or warm water is delivered to all zones
Primary airflow rate Increasing the primary airflow rate through Increasing the primary airflow rate increases
(cfm) the nozzles results in more air being primary AHU fan energy use, increases noise
induced from the space
space, which increased in the space
space, and requires a larger primary
the capacity of the chilled beam coils AHU and larger ductwork
Inlet static pressure Increasing the static pressure at the inlet to Increasing the inlet pressure increases
of the primary air the nozzles results in more air being primary AHU fan energy use, and increases
induced from the space, which increased noise in the space
the capacity of the chilled beam coils
Dry-bulb temperature Delivering the primary air at a colder Using a colder primary-air temperature may
of the primary air temperature means that less of the space cause the space to overcool and low sensible
sensible cooling load needs to be offset by cooling loads, thus requiring the chilled beam
the chilled beams (or separate heating system) to add heat to
prevent overcooling space
Entering water Supplying colder water to the chilled beam Using a colder water temperature requires the
temperature increases the cooling capacity of the beam space dew point to be lower to avoid
condensation, which means the primary air
needs to be dehumidified to a lower dew point
Water flow rate Increasing the water flow rate increases the Increasing the water flow rate increases pump
(gpm) cooling capacity of the beam energy use and requires larger pipes and
pumps 13
SA SA
Airflow needed to induce
sufficient room air (RA) to
offset the space sensible
cooling load
14
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
7
active chilled beams
Determining Primary Airflow Rate
Example: office space
Minimum OA per ASHRAE 62.1 0.085 cfm/ft2
(to achieve LEED IEQc2) (0.085 1.3 = 0.11 cfm/ft2)
ACB
C system
Airflow required to offset space 0.085 cfm/ft2 (DPTPA = 47F)
latent load 0.11 cfm/ft2 (DPTPA = 49F)
0.36 cfm/ft2 (DPTPA = 53F)
15
16
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
8
High Performance Chilled Beam Systems
How can active chilled beam systems be designed
differently for high performance?
Use
U ttwo-pipe
i b beams as much
h as possible
ibl
Use primary air system for morning warm-up
Consider using a separate heating system
Minimize primary airflow required
Deliver primary air at a cold (rather than neutral) temperature
Use multiple, smaller primary AHUs to allow SAT reset
(maximize cooling benefit
benefit, minimize need for reheat)
17
18
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
9
ACB challenges
Need to Prevent Condensation
19
space 75F DB
50% RH
180
55F DP
humidity ratio, grains/lb of dry air
65 gr/lb 80 160
60 80
space
60
50
40
30
40 PA
20
Qlatent,space = 0.69 CFMPA ((Wspace WPA)
30 40 50 60 70 80 90 100 110
dry-bulb temperature, F
20
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
10
active chilled beams
Primary Air System
OA
primary air handler
EA
with series desiccant wheel
RA
active
PA PA chilled beam
RA RA RA
21
OA OA' MA MA'
EA CA
PA
RA
cooling
coil
22
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
11
OA 95F DB
118 gr/lb
series desiccant requires:
OA' 81F DB less cooling tons
81 gr/lb no reheat
RA 75F DB warmer coil temperature
50% RH than cool + reheat 180
55F DP
hum
160
MA 76F DB
30 40 50 60 70 80 90 100 110
dry-bulb temperature, F
23
24
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
12
System design Impact on installed cost Impact on performance
variable of the chilled beams of the overall system
2-pipe versus 4-pipe A 2-pipe beam provides more cooling Using 2-pipe beams requires a separate
chilled beams capacity than a 4-pipe beam because more heating system, otherwise it can result in
coil surface is available poorer comfort control because either cold
water or warm water is delivered to all zones
Primary airflow rate Increasing the primary airflow rate through Increasing the primary airflow rate increases
(cfm) the nozzles results in more air being primary AHU fan energy use, increases noise
induced from the space
space, which increased in the space
space, and requires a larger primary
the capacity of the chilled beam coils AHU and larger ductwork
Inlet static pressure Increasing the static pressure at the inlet to Increasing the inlet pressure increases
of the primary air the nozzles results in more air being primary AHU fan energy use, and increases
induced from the space, which increased noise in the space
the capacity of the chilled beam coils
Dry-bulb temperature Delivering the primary air at a colder Using a colder primary-air temperature may
of the primary air temperature means that less of the space cause the space to overcool and low sensible
sensible cooling load needs to be offset by cooling loads, thus requiring the chilled beam
the chilled beams (or separate heating system) to add heat to
prevent overcooling space
Entering water Supplying colder water to the chilled beam Using a colder water temperature requires the
temperature increases the cooling capacity of the beam space dew point to be lower to avoid
condensation, which means the primary air
needs to be dehumidified to a lower dew point
Water flow rate Increasing the water flow rate increases the Increasing the water flow rate increases pump
(gpm) cooling capacity of the beam energy use and requires larger pipes and
pumps 25
Waterside Economizer
chillers
57F 42F
variable-flow
pumps
bypass for
minimum flow mixing variable-flow
valve pump
T
54F
63F chilled beams
from
cooling tower waterside economizer
heat exchanger
26
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
13
water chillers
58F 42F
variable-flow
i bl fl
pumps
54F
mixing
valve
from variable-flow
cooling tower pump
waterside economizer
heat exchanger T
63F 58F
active
chilled beams
27
28
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
14
High-Performance Systems
29
30
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
15
Fan-Pressure Optimization
static
pressure
sensor
supply
fan P
system-level controller
31
system-level controller
T T
T T T T
32
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
16
Ventilation Optimization
air-handling (or rooftop) unit
with Traq dampers
Reset outdoor airflow
SA RA
33
34
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
17
Lower Supply-Air Temperature
35
36
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
18
Parallel Fan-Powered VAV
heating coil
(second stage of heat)
37
38
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
19
High-Performance Chilled-Water System
39
Summary
40
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
20
Advanced Energy Design Guides
www.ashrae.org/freeaedg
41
42
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
21
Additional Resources
Understanding Chilled Beam Systems, Trane
Engineers Newsletter ADM-APN034-EN (2009),
www.trane.com/engineersnewsletter
Chilled-Water VAV Systems, Trane
application manual SYS-APM008-EN (2009)
Cold Air Distribution System Design Guide,
ASHRAE (1996)
Advanced Energy Design Guide series,
ASHRAE, www.ashrae.org/freeaedg
43
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
22